Fault
code
Name of
fault
Judgement
conditions for fault
Fault
phenomenon
Fault possibility and treatment
Fault recovery
E05
Communication
fault of the
indoor and
outdoor unit
Number of the signals
of indoor unit received
by the outdoor unit
is different from the
number of indoor
units on outdoor unit
DIP; conflict among
addresses of the indoor
units; communication
interruption among the
units.
Display the
fault code, the
compressor
stops running
immediately
and shutdown.
Error setting of the number of indoor
units connected to the outdoor unit,
resetting.
Error connection or no connection of
the communication line: communication
interruption appears when two indoor
units are connected, leading to E05
for the indoor unit at output end and
E29 for the indoor unit at input end;
if communication interruption appears
between the indoor and outdoor unit,
E29 is reported for the indoor unit, and
E05 can be found by means of history
enquiry.
For the disturbance from e outside,
remove the disturbance source, to ensure
communication earthing.
PCB board is bad.
When the number of signals
of indoor unit is the same as
DIP number of the outdoor
unit, SLEEP on the wired
controller or TIMING on
the remote controller can
be used to eliminate the
fault, then manually start to
recover.
E06
Communication
fault of the
outdoor system
chip and inverter
chip
The outdoor system
chip and inverter chip
haven
ď
t received any
signal from each other
for 1min continuously or
the signal has error.
Display the
fault code, the
compressor
stops running
immediately
and shutdown.
Bad connection, please check it.
Bad outdoor system chip, please replace
PCB board of the outdoor unit.
Bad inverter chip, replace inverter PCB
board.
Strong interference nearby the unit or the
power system, remove the interference
source.
Bad communication between the main
control PCB board and drive PCB board
of the outdoor unit, please check the
connection.
After the signal becomes
normal, SLEEP on the wired
controller or TIMING on
the remote controller can
be used to eliminate the
fault, then manually start to
recover.
E07
IPM module
protection
Protection signal of
module is received by
the outdoor unit.
Display the
fault code, the
compressor
stops running
immediately
and shutdown.
Temperature of the radiator is too high,
please check the ambient temperature as
well as heat exchange of the radiator and
the fan of outdoor unit, and whether the
radiator is blocked by dirt.
Bad radiator sensor.
Overcurrent and overvoltage appear to
IPM module, please check whether the
power supply and compressor load are
normal.
After the protection is
removed, SLEEP on the
wired controller or TIMING
on the remote controller
can be used to eliminate the
fault, then manually start to
recover.
E08
Reserved Reserved
Reserved
Reserved
Reserved
E09
Exhaust
temperature
protection
of the
compressor
Exhaust temperature
of the compressor
T9
≥
105
ņ
, lasting for
3s
Display the
fault code, the
compressor
stops running
immediately
and shutdown.
Exhaust temperature probe of the
compressor is damaged, please replace
the temperature probe.
Cooling system is blocked, please check if
the elements such as expansion valve are
blocked.
Leakage of refrigerant, please check the
leakage and pump vacuum again and
charge refrigerant.
T9<90
ņ
lasts for 3s, SLEEP
on the wired controller
or TIMING on the remote
controller can be used to
eliminate the fault, then
manually start to recover.
E10
Horsepower
detection
of the
compressor
Horsepower of the
compressor must be
3HP, 4HP and 6HP at
present.
Forbid to start. Error setting of the horsepower of the
outdoor unit, reset it.
Bad PCB board, replace the PCB board of
outdoor unit.
Correct horsepower, SLEEP
on the wired controller
or TIMING on the remote
controller is used to
eliminate the fault.
E11
Exhaust
temperature
T9 sensor
of the
compressor
has fault.
Open circuit or short
circuit appears to the
exhaust temperature T9
sensor of the compressor
Same as E06
Temperature probe is damaged.
Poor contact of the connecting line of
temperature probe.
Same as E06.
Trouble shooting
AMS-SVX01A-EN
43