Trouble shooting
Faults of outdoor unit
If the outdoor unit has any fault, fault code will be displayed on all wired controllers of outdoor unit and
indoor unit. After the fault is eliminated, fault code will disappear.
Fault
code
Name of
fault
Judgement
conditions for fault
Fault
phenomenon
Fault possibility and treatment
Fault recovery
E01
Overvoltage/
undervoltage
protection
The power voltage
≥
242V or
≤
187V, lasting
for 5s
Display the
fault code, the
compressor
stops running
immediately
and shutdown.
Poor contact of voltage transformer on
the control board.
Poor contact of 220~240V power wire of
the unit, check whether the power wire is
connected reliably and retighten it.
Problem of power supply, check and
eliminate power supply problem of the
unit.
Voltage 190V < VAC < 238V
lasts for 30s, SLEEP on the
wired controller or TIMING
on the remote controller
is used to eliminate the
fault, then manually start to
recover.
E02
Compressor
exhaust
pressure
protection
High pressure switch
(HPC) disconnects when
exhaust pressure >
4.2MPa is detected.
Display the
fault code, the
compressor
stops running
immediately
and shutdown.
Stop valve not opened,
Pipe is blocked by foreign body
or electronic expansion valve has
adjustment insufficiency, please check
the pipe and valve conditions.
Insufficient heat dissipation of the
condenser, air duct is blocked or air
volume isn
ď
t enough, please check the
fan and clean coil.
Refrigerant is charged too much (at
this time accompanied by high suction
pressure), calculate the charging volume
again and refill refrigerant.
Error between High pressure switch
and main board, check whether it is
connected.
Poor contact of high pressure switch,
check it.
High pressure switch
(HPC) detects that exhaust
pressure < 3.3MPa, SLEEP
on the wired controller
or TIMING on the remote
controller is used to
eliminate the fault, then
manually start to recover.
E03
Suction
pressure
protection of
compressor
Low pressure switch
(LPC) disconnects when
exhaust pressure <
0.15MPa is detected
Display the
fault code, the
compressor
stops running
immediately
and shutdown.
Stop valve not opened,
Pipe is blocked by foreign body
or electronic expansion valve has
adjustment insufficiency, please check
the pipe and valve conditions.
Refrigerant is insufficient, calculate
the charging volume again and refill
refrigerant.
Error between low pressure switch
and main board, check whether it is
connected. Poor contact of low pressure
switch, check it.
Low pressure switch (LPC)
detects that suction pressure
> 0.30MPa, SLEEP on the
wired controller or TIMING
on the remote controller
is used to eliminate the
fault, then manually start to
recover.
E04
Outdoor
condenser
high
temperature
protection
Outdoor condenser
midpoint temperature
T7
≥
63
ņ
, lasting for 3s
under cooling mode.
Display the
fault code, the
compressor
stops running
immediately
and shutdown.
Outdoor fan system has fault.
Ambient temperature is too high.
Condenser is blocked by dirt.
Installation of outdoor unit is
unreasonable, influencing air volume, or
influencing each other among outdoor
units, temperature of return air is high.
Coil temperature sensor of the condenser
has fault.
Outdoor condenser outlet
temperature T7 < 57
ņ
,
lasting for 3s, SLEEP on the
wired controller or TIMING
on the remote controller
is used to eliminate the
fault, then manually start to
recover.
42
AMS-SVX01A-EN