Specifications of wiring
Notes:
Flexible wire is recommended because the wire needs to be bent during installation, otherwise
•
it will produce installation problem.
Data in the following table only correspond to the stranded copper core fl exible wire. If other
•
wire will be chosen, please refer to the electrical engineering handbook in accordance with the
wiring current provided in the table.
For the safety of the unit, wiring shall not be based on the rated current, because the operating
•
conditions will change with the season.
Electrical parameters of outdoor unit
Model
Frequency
DŽ
Hz
Dž
Rated
voltage
DŽ
V
Dž
Lower
limit of
voltage
DŽ
V
Dž
Upper
limit of
voltage
DŽ
V
Dž
Maximum
start
current of
compressor
MSC
(A)
Rated
current of
compressor
RLA
(A)
Rated
current of
fan motor
FLA
(A)
Minimum
line current
MCA
(A)
Recommended
specification of
fuse
RDE
(A)
Maximum
specification
of fuse
MFA
(A)
Minimum
diameter
specification
of the
copper core
wire
DŽ
mm
2
Dž
TX(U)M524AMAA
50
220
~
240
198
264
11.4
11.4
0.6
21
25
35
4
TX(U)M536AMAA
14.5
14.5
0.6
22
25
35
4
TX(U)M542AMAA
20
20
1.2
27
30
50
6
TX(U)M548AMAA
23
23
1.2
31
35
55
6
TX(U)M548ADAA
50
380
342
418
8
8
1.2
11
14
20
2.5
DIP setting for the controller of outdoor unit
SW1 (upper DIP)
Outdoor unit capacity
DIP
Indoor unit quantity DIP
Limit of cooling and heating
temperature range
Forced
cooling
S1
S2
S3
S4
S5
S6
S7
S8
SW2 (lower DIP)
Outdoor unit
address DIP
System connecting pipe
length correction
Cooling
only/Heating
pump
Assigned
address mode
Indoor unit address
setting way
S1
S2
S3
S4
S5
S6
S7
S8
30
AMS-SVX01A-EN
Electrical control installation