background image

12

TWA-SVX01A-EN

CAUTION:

 Do not apply heat to remove seal caps until

they have been punctured. If seal caps are intact,
application of heat may generate excessive pressure in
the unit and result in damage to the coil or expansion
valve.

1. Remove both seal caps from the indoor unit connection

stubs.

CAUTION:

 Do not remove seal caps until prepared to

braze refrigerant lines to the connections. Extended
exposure to atmosphere may allow moisture or dirt to
contaminate the system, damaging valve seats and
causing ice formation in system components.

2. Turn nitrogen supply on. Nitrogen enters thorough liquid

line gauge port.

3. Braze the liquid line connections.

4. Open the gauge port on the suction line and then braze the

suction line to the connection stub. Nitrogen will bleed out
the open gauge port on the suction line.

5. Shut off nitrogen supply.

Leak Check

After the brazing operation of refrigerant lines to both the
outdoor and indoor unit is completed, the field brazed con-
nections must be checked for leaks. Pressurize the system
through the service valve with dry nitrogen to 200 psi. Use
soap bubbles or other leak-checking methods to ensure
that all field joints are leak free. If not, release pressure,
repair and repeat leak test.

System Evacuation

1. After completion of leak check, evacuate the system.

2. Attach appropriate hoses from manifold gauge to gas and

liquid line pressure taps.

Note: 

Unnecessary switching of hoses can be avoided

and 

complete evacuation of all lines leading to sealed

system can be accomplished with manifold center hose
and connecting branch hose to a cylinder of R-22 and
vacuum pump.

3. Attach center hose of manifold gauages to vacuum pump.

4. Evacuate the system to hold a 350 micron vacuum.

5. Close off valve to vacuum pump and observe the micron

gauge. If gauge pressure rises above 500 microns in one
(1) minute, then evacuation is incomplete or the system
has a leak.

6. If vacuum gauge does not rise above 500 microns in one

(1) minute, the evacuation should be complete.

7. With vacuum pump and micron gauge blanked off, open

valve on R-22 cylinder and allow refrigerant pressure to
build up to about 40 psig.

8. Close valve on the R-22 supply cylinder. Close valves on

manifold gauge set and remove refrigerant charging hoses
from liquid and gas gauge ports.

9. Leak test the entire system. Using proper procedures and

caution, repair any leaks found and repeat the leak test.

Refrigerant Charging Procedure

If charging by weight, refer to refrigerant charges that are
given in Table 3. If additional refrigerant is needed because
of length of line, calculate the requirement using Table 4.
Charge by weight through the gauge port on the liquid line.
Once the charge enters the system, backseat (open) the
liquid line service valve and disconnect the charging line
and replace the cap on the gauge port.

Insulating and Isolating Refrigerant Lines

Insulate the entire suction line with refrigerant piping insula-
tion. Also insulate any portion of the liquid line exposed to
temperature extremes. Insulate and isolate liquid and suction
lines from each other. Isolate refrigerant lines from the
structure and any duct work.

Note: 

To prevent possible noise or vibration problems, be

certain to isolate refrigerant lines from the building.

Table 3 - TWA Refrigerant Charge (R-22)

1

Model Number

Refrigerant Charge

TWA090A

18 lbs. 0.0 oza.

TWA075A

TWA120A

31 lbs. 8.0 ozs.

TWA100A

TWA180B

18 lbs. 0.0 ozs. (per circuit)

TWA155B

TWA240B

22 lbs. 4.0 ozs. (per circuit)

TWA200B

1

 Sufficient operating charge for outdoor unit and

  25 feet of nominally sized refigerant piping.

Table 4 -  Additional Required Refrigerant

Additional Additional 

R-22 

Tubing Length

Required (lbs.)

15 ft.

1 lb.     4 oz.

25 ft.

2 lbs.   1 oz.

32 ft.

2 lbs.  11 oz.

40 ft.

3 lbs.   5 oz.

¹ Based on 1-3/8" dia. Suction line, 1/2" liquid line.
² Add .5 lbs. R-22 for each additional six feet of
  tubing length over 40 feet.

Installation

Содержание TWA Series

Страница 1: ...n Operation Maintenance Split System Heat Pump Condensers 7 1 2 20 Tons February 2004 Models 60 Hz TWA090A F TWA120A F TWA180B F TWA240B F TWA SVX01A EN 18 BC60D5 50 Hz TWA075AD F TWA100AD F TWA155BD F TWA200BD F ...

Страница 2: ... a qualified service organization with qualified experienced HVAC technicians to properly diagnose and repair this equipment NOTICE Warnings and Cautions appear at appropriate sections throughout this manual Read these carefully WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which ...

Страница 3: ... 9 Clearances 9 Snow Belt Mounting 10 Unit Mounting 10 Refrigerant Piping 11 Leak Check 12 System Evacuation 12 Refrigerant Charging Procedure 12 Electrical Wiring 13 Low Voltage Wiring 13 Typical Split System Heat Pump Diagram 14 Typical Field Wiring 15 Safety Controls 16 Installation Checklist 16 Sequence of Operation 17 Maintenance 19 Warranty 21 22 ...

Страница 4: ... to refer to the specific model number serial number and DL number if applicable stamped on the unit nameplate Split System Condensing Unit Model Nomenclature T W A 0 9 0 A 1 0 0 E A 1 2 3 4 5 6 7 8 9 10 11 12 Digits 1 2 3 Product Type Digit 8 Electrical Characteristics TWA Split System Heat Pump 3 208 230 60 3 Outdoor Unit 4 460 60 3 W 575 60 3 Digits 4 5 6 Nominal Gross Cooling Capacity MBh D 38...

Страница 5: ...SVX01A EN 5 Unit Dimensions Figure 1 TWA075A TWA090A Dimensional Data Connection Locations Clearances Corner Weights Figure 2 TWA100A TWA120A Dimensional Data Connection Locations Clearances Corner Weights ...

Страница 6: ...6 TWA SVX01A EN Unit Dimensions Figure 3 TWA155B TWA180B Dimensional Data Connection Locations Clearances Corner Weights ...

Страница 7: ...TWA SVX01A EN 7 Unit Dimensions Figure 4 TWA200B TWA240B Dimensional Data Connection Locations Clearances Corner Weights ...

Страница 8: ...7 254 48 1 70 1 33 7 278 0 1 1 6 0 17 5 TWA120A4 460 60 3 414 506 23 3 35 1 16 5 124 0 1 1 2 7 7 0 TWA120AW 575 60 3 518 632 18 8 25 1 13 4 92 0 1 1 2 0 5 7 TWA100AD 380 415 50 3 380 415 22 5 35 1 15 8 124 0 1 1 2 7 7 0 TWA180B3 208 230 60 3 187 254 62 7 80 2 25 1 182 0 2 1 2 3 1 8 1 TWA180B4 460 60 3 414 506 32 9 45 2 13 2 94 9 2 1 2 1 6 3 7 TWA180BW 575 60 3 518 632 26 3 35 2 10 6 70 0 2 1 2 1 2...

Страница 9: ...aged material from the receiving location Take photos of the damage if possible The owner must provide reason able evidence that the damage did not occur after delivery Notify the carrier s terminal of damage immediately by phone and by mail Request an immediate joint inspection of the damage by the carrier and the consignee Notify the sales representative and arrange for repair Do not repair the ...

Страница 10: ...it weights are given in Table 2 The unit should be elevated on a level field fabricated four inch steel or wood 4 x 4 mounting frame Complete the frame and secure it into position before lilfting the unit to the roof The mounting frame must support a minimum of three of the unit s four sides and should span roof supports to distribute the load on the roof Figure 4 Roof Mounted Unit Ensure that the...

Страница 11: ...ble contamination 1 Remove the compressor service access panel 2 Locate the liquid and suction line service valves Check that the piping connection stubs on the valves Figure 5 line up properly with the holes in the unit cabinet Figure 5 3 Remove the refrigerant connection seal caps and open the service valve slowly to release the nitrogen from the unit CAUTION Do not remove the seal caps from ref...

Страница 12: ...n one 1 minute then evacuation is incomplete or the system has a leak 6 If vacuum gauge does not rise above 500 microns in one 1 minute the evacuation should be complete 7 With vacuum pump and micron gauge blanked off open valve on R 22 cylinder and allow refrigerant pressure to build up to about 40 psig 8 Close valve on the R 22 supply cylinder Close valves on manifold gauge set and remove refrig...

Страница 13: ...ove the charging system from the unit and close the opening in the bottom of the control box with the pivotal cover before attempting to replace access panel 6 Replace all panels Electrical Wiring TWA field wiring consists of providing power supply to the unit installing the system indoor thermostat and providing low voltage system interconnecting wiring Access to elec trical connection locations ...

Страница 14: ...14 TWA SVX01A EN Figure 7 Typical Split System Heat Pump Refrigerant Circuits Installation ...

Страница 15: ...NES IS TO BE FURNISHED AND INSTALLED ELECTRIC HEAT ADD 1 ADDITIONAL WIRE 24 VOLTS BY THE CUSTOMER ALL CUSTOMER SUPPLIED WIRING MUST BE COPPER ONLY AND MUST CONFORM TO NEC AND LOCAL ELECTRICAL CODES CODES MAY REQUIRE LINE OF SIGHT BETWEEN DISCONNECT SWITCH AND UNIT 2 WHEN ELECTRIC HEATER ACCESSORY IS USED SINGLE POINT POWER ENTRY OR DUAL POINT POWER ENTRY IS FIELD OPTIONAL SINGLE POINT POWER ENTRY ...

Страница 16: ...sor motor windings It will shut off the compressor if the temperature or current of the compressor motor windings exceeds it s design trip temperature Note The IOL will put the compressor back in opera tion once the compressor motor heat has dropped below the trip setting however a check of the refrigerant and electrical system should be made to determine the cause and be corrected System Pre Star...

Страница 17: ...us energized This signal causes an output to the switch over valve SOV B placing it in the cooling mode System Start Procedure Heating Mode With the system switch on the thermostat set to the HEAT position and the room temperature drops approximately 1 degrees below the thermostat setting a heating cycle is initiated by closing of the TSH 1 contacts When closed these contacts supply power from R t...

Страница 18: ...ns unchanged at this point The outdoor thermostats if used are by passed System Start Procedure T Thermistor Circuit The T circuit used with both the manual and automatic changeover thermostats in conjunction with heat pump applications is used for anticipation of outdoor condition changes This thermistor varies the resistance as temperature varies in an inverse proportional relationship It is loc...

Страница 19: ...d or dirt from the unit casing 4 Remove corrosion from any surface and repaint Check the gasket around the control panel door to insure it fits cor rectly and is in good condition to prevent water leakage 5 Inspect the evaporator fan belt If it is worn or frayed re place it 6 Inspect the control panel wiring to insure that all connec tions are tight and that the insulation is intact Lubricate the ...

Страница 20: ...Log Date Ambient Evaporator Temp Entering Air Compressor Superheat Subcooling F Dry Wet Suction Discharge Circuit 1 Circuit 1 Bulb Bulb Pressure Pressure F F Perform each inspection once per month during cooling season while unit is operating ...

Страница 21: ... and liabilities under this warranty are limited to furnishing F O B factory or ware house at the warrantor designated shipping point freight allowed toBuyer s city or port of export for shipments outside the con terminous United States a replacement product or at the option of the warrantor parts for the repair of the product not conforming to this warranty and which have been returned to the war...

Страница 22: ...ntor s products not conforming to this warranty Warrantor shall not be obligated to pay for the cost of lost refrigerant No liability whatever shall attach to Warrantor until said products have been paid for and then said liability shall be limited to the purchase price of the equipment shown to be defective THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABIL...

Страница 23: ...23 TWA SVX01A EN ...

Страница 24: ...cy of continuous product and product data improvement and reserves the right to change design and specifications without notice Literature Order Number File Number Supersedes Stocking Location TWA SVX01A EN New Webb Mason SV UN TWA SVX01A EN 2 04 ...

Отзывы: