background image

10

TWA-SVX01A-EN

A. Do not install the unit under a low overhang. Condenser

discharge must not be restricted. See Figure 1, Figure 2 or
Figure 3.

Important:

 

Do not obstruct condenser discharge air.

This can result in warm air recirculation through the
coil.

B. Do not locate the unit in a position where runoff water can

fall into the fan discharge openings.

C. Condenser intake air is supplied from three sides of the

unit. Adhere to the minimum required clearances given in
Figure 1, Figure 2 or Figure 3.

Snow Belt Recommendations

In regions where deep snow is encountered, raise the unit a
minimum distance of 8 to 12 inches above the mounting
surface. This will reduce the risk of snow blocking the coil and
inproves runoff of water produced during the defrost cycle.
Avoid locating the unit where snow tends to drift. Snow
accumulations must be removed from around the unit
immediately to prevent drastic efficiency reduction. A snow
drift barrier may be constructed around the unit to prevent
snow blockage. Clearance between the snow barrier and the
unit must comply with the clearances given in Figure 1, Figure
2 or Figure 3 .

Unit Mounting

Rooftop Mounting

If the unit will be roof mounted, determine for certain that
the structure is strong enough to support the unit and any
required accessories. Unit weights are given in Table 2.
The unit should be elevated on a level, field fabricated four-
inch steel or wood 4" x 4" mounting frame. Complete the frame
and secure it into position before lilfting the unit to the roof.
The mounting frame must support a minimum of three of the
unit’s four sides and should span roof supports to distribute
the load on the roof.

Figure 4 Roof Mounted Unit

 

Ensure that the roof

structure supports are strong enough to support the
weight of the unit and any accessories. Failure to do this
can result in personal injury or death due to  structural
failure and can seriously damage the unit and the
building.

The following warning complies with State of California law,
Proposition 65.

This product contains

fiberglass wool insulation!

 Fiberglass dust and ceramic

fibers are believed by the state of California to cause
cancer through inhalation. Glasswool fibers may also
cause respiratory, skin, or eye irritation. See page 13 for
precautionary and first aid measures.

Ground Level Mounting

“For ground level installation, the unit base should be ade-
quately supported and hold the unit near level. The installation
must meet the guidelines set forth in local codes.” The support
should extend two inches beyond the unit base channels at all
points. The unit and support must be isolated from any
adjacent structure to prevent possible noise or vibration
problems. Any ground level location must comply with required
clearances given in Figure 1, Figure 2 or Figure 3.

Installation

Содержание TWA Series

Страница 1: ...n Operation Maintenance Split System Heat Pump Condensers 7 1 2 20 Tons February 2004 Models 60 Hz TWA090A F TWA120A F TWA180B F TWA240B F TWA SVX01A EN 18 BC60D5 50 Hz TWA075AD F TWA100AD F TWA155BD F TWA200BD F ...

Страница 2: ... a qualified service organization with qualified experienced HVAC technicians to properly diagnose and repair this equipment NOTICE Warnings and Cautions appear at appropriate sections throughout this manual Read these carefully WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which ...

Страница 3: ... 9 Clearances 9 Snow Belt Mounting 10 Unit Mounting 10 Refrigerant Piping 11 Leak Check 12 System Evacuation 12 Refrigerant Charging Procedure 12 Electrical Wiring 13 Low Voltage Wiring 13 Typical Split System Heat Pump Diagram 14 Typical Field Wiring 15 Safety Controls 16 Installation Checklist 16 Sequence of Operation 17 Maintenance 19 Warranty 21 22 ...

Страница 4: ... to refer to the specific model number serial number and DL number if applicable stamped on the unit nameplate Split System Condensing Unit Model Nomenclature T W A 0 9 0 A 1 0 0 E A 1 2 3 4 5 6 7 8 9 10 11 12 Digits 1 2 3 Product Type Digit 8 Electrical Characteristics TWA Split System Heat Pump 3 208 230 60 3 Outdoor Unit 4 460 60 3 W 575 60 3 Digits 4 5 6 Nominal Gross Cooling Capacity MBh D 38...

Страница 5: ...SVX01A EN 5 Unit Dimensions Figure 1 TWA075A TWA090A Dimensional Data Connection Locations Clearances Corner Weights Figure 2 TWA100A TWA120A Dimensional Data Connection Locations Clearances Corner Weights ...

Страница 6: ...6 TWA SVX01A EN Unit Dimensions Figure 3 TWA155B TWA180B Dimensional Data Connection Locations Clearances Corner Weights ...

Страница 7: ...TWA SVX01A EN 7 Unit Dimensions Figure 4 TWA200B TWA240B Dimensional Data Connection Locations Clearances Corner Weights ...

Страница 8: ...7 254 48 1 70 1 33 7 278 0 1 1 6 0 17 5 TWA120A4 460 60 3 414 506 23 3 35 1 16 5 124 0 1 1 2 7 7 0 TWA120AW 575 60 3 518 632 18 8 25 1 13 4 92 0 1 1 2 0 5 7 TWA100AD 380 415 50 3 380 415 22 5 35 1 15 8 124 0 1 1 2 7 7 0 TWA180B3 208 230 60 3 187 254 62 7 80 2 25 1 182 0 2 1 2 3 1 8 1 TWA180B4 460 60 3 414 506 32 9 45 2 13 2 94 9 2 1 2 1 6 3 7 TWA180BW 575 60 3 518 632 26 3 35 2 10 6 70 0 2 1 2 1 2...

Страница 9: ...aged material from the receiving location Take photos of the damage if possible The owner must provide reason able evidence that the damage did not occur after delivery Notify the carrier s terminal of damage immediately by phone and by mail Request an immediate joint inspection of the damage by the carrier and the consignee Notify the sales representative and arrange for repair Do not repair the ...

Страница 10: ...it weights are given in Table 2 The unit should be elevated on a level field fabricated four inch steel or wood 4 x 4 mounting frame Complete the frame and secure it into position before lilfting the unit to the roof The mounting frame must support a minimum of three of the unit s four sides and should span roof supports to distribute the load on the roof Figure 4 Roof Mounted Unit Ensure that the...

Страница 11: ...ble contamination 1 Remove the compressor service access panel 2 Locate the liquid and suction line service valves Check that the piping connection stubs on the valves Figure 5 line up properly with the holes in the unit cabinet Figure 5 3 Remove the refrigerant connection seal caps and open the service valve slowly to release the nitrogen from the unit CAUTION Do not remove the seal caps from ref...

Страница 12: ...n one 1 minute then evacuation is incomplete or the system has a leak 6 If vacuum gauge does not rise above 500 microns in one 1 minute the evacuation should be complete 7 With vacuum pump and micron gauge blanked off open valve on R 22 cylinder and allow refrigerant pressure to build up to about 40 psig 8 Close valve on the R 22 supply cylinder Close valves on manifold gauge set and remove refrig...

Страница 13: ...ove the charging system from the unit and close the opening in the bottom of the control box with the pivotal cover before attempting to replace access panel 6 Replace all panels Electrical Wiring TWA field wiring consists of providing power supply to the unit installing the system indoor thermostat and providing low voltage system interconnecting wiring Access to elec trical connection locations ...

Страница 14: ...14 TWA SVX01A EN Figure 7 Typical Split System Heat Pump Refrigerant Circuits Installation ...

Страница 15: ...NES IS TO BE FURNISHED AND INSTALLED ELECTRIC HEAT ADD 1 ADDITIONAL WIRE 24 VOLTS BY THE CUSTOMER ALL CUSTOMER SUPPLIED WIRING MUST BE COPPER ONLY AND MUST CONFORM TO NEC AND LOCAL ELECTRICAL CODES CODES MAY REQUIRE LINE OF SIGHT BETWEEN DISCONNECT SWITCH AND UNIT 2 WHEN ELECTRIC HEATER ACCESSORY IS USED SINGLE POINT POWER ENTRY OR DUAL POINT POWER ENTRY IS FIELD OPTIONAL SINGLE POINT POWER ENTRY ...

Страница 16: ...sor motor windings It will shut off the compressor if the temperature or current of the compressor motor windings exceeds it s design trip temperature Note The IOL will put the compressor back in opera tion once the compressor motor heat has dropped below the trip setting however a check of the refrigerant and electrical system should be made to determine the cause and be corrected System Pre Star...

Страница 17: ...us energized This signal causes an output to the switch over valve SOV B placing it in the cooling mode System Start Procedure Heating Mode With the system switch on the thermostat set to the HEAT position and the room temperature drops approximately 1 degrees below the thermostat setting a heating cycle is initiated by closing of the TSH 1 contacts When closed these contacts supply power from R t...

Страница 18: ...ns unchanged at this point The outdoor thermostats if used are by passed System Start Procedure T Thermistor Circuit The T circuit used with both the manual and automatic changeover thermostats in conjunction with heat pump applications is used for anticipation of outdoor condition changes This thermistor varies the resistance as temperature varies in an inverse proportional relationship It is loc...

Страница 19: ...d or dirt from the unit casing 4 Remove corrosion from any surface and repaint Check the gasket around the control panel door to insure it fits cor rectly and is in good condition to prevent water leakage 5 Inspect the evaporator fan belt If it is worn or frayed re place it 6 Inspect the control panel wiring to insure that all connec tions are tight and that the insulation is intact Lubricate the ...

Страница 20: ...Log Date Ambient Evaporator Temp Entering Air Compressor Superheat Subcooling F Dry Wet Suction Discharge Circuit 1 Circuit 1 Bulb Bulb Pressure Pressure F F Perform each inspection once per month during cooling season while unit is operating ...

Страница 21: ... and liabilities under this warranty are limited to furnishing F O B factory or ware house at the warrantor designated shipping point freight allowed toBuyer s city or port of export for shipments outside the con terminous United States a replacement product or at the option of the warrantor parts for the repair of the product not conforming to this warranty and which have been returned to the war...

Страница 22: ...ntor s products not conforming to this warranty Warrantor shall not be obligated to pay for the cost of lost refrigerant No liability whatever shall attach to Warrantor until said products have been paid for and then said liability shall be limited to the purchase price of the equipment shown to be defective THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABIL...

Страница 23: ...23 TWA SVX01A EN ...

Страница 24: ...cy of continuous product and product data improvement and reserves the right to change design and specifications without notice Literature Order Number File Number Supersedes Stocking Location TWA SVX01A EN New Webb Mason SV UN TWA SVX01A EN 2 04 ...

Отзывы: