Test 4 - LED Indicator Test, (SYS ON, HEAT, & COOL)

Method 1

Testing the LED using a meter with diode test function. Test
both forward and reverse bias. Forward bias should measure a
voltage drop of 1.5 to 2.5 volts, depending on your meter.
Reverse bias will show an Over Load, or open circuit indication
if LED is functional.

Method 2

Testing the LED with an analog Ohmmeter. Connect Ohmme-
ter across LED in one direction, then reverse the leads for the
opposite direction. The LED should have at least 100 times
more resistance in reverse direction, as compared with the
forward direction. If high resistance in both directions, LED is
open. If low in both directions, LED is shorted.

Method 3

To test LED’s with ZSM connected to unit, test voltages at LED
terminals on ZSM. A measurement of 32 VDC, across an unlit
LED, means the LED has failed.

Note: Measurements should be made from LED common (ZSM
terminal 6 to respective LED terminal). Refer to the Zone
Sensor Module (ZSM) Terminal Identification table at the
beginning of this section.

Trouble Shooting
ReliaTel

TM

 Controls

Programmable & Digital Zone Sensor Test

Testing serial communication voltage

1. Verify 24 VAC is present between terminals J6-14 & J6-11.

2. Disconnect wires from J6-11 and J6-12. Measure the volt-

age between J6-11 and J6-12, should be about 32 VDC.

3. Reconnect wires to terminals J6-11 and J6-12. Measure

voltage again between J6-11 and J6-12, voltage should
flash high and low every 0.5 seconds. The voltage on the
low end will measure about 19 VDC, while the voltage on
the high end will measure from approximately 24 to 38
VDC.

4. Verify all modes of operation, by running the unit through

all of the steps in the “Test Modes” section discussed in
“Unit Start-Up”.

5. After verifying proper unit operation, exit the test mode.

Turn the fan on continuously at the ZSM, by pressing the
button with the fan symbol. If the fan comes on and runs
continuously, the ZSM is good. If you are not able to turn
the fan on, the ZSM is defective.

RTCI Loss of communications

If the RTCI loses input from the building management system,
the RTRM will control in the default mode after approximately
15 minutes. If the RTRM loses the Heating and Cooling
setpoint input, the RTRM will control in the default mode
instantaneously. The temperature sensing thermistor in the
Zone Sensor Module is the only component required for the
“Default Mode” to operate.

Содержание TTA075AD series

Страница 1: ...ensers 7 1 2 20 Tons September 2004 Models 60 Hz TTA090A F TTA120A F TTA120B E TTA120C G TTA150B E TTA180B F TTA180C G TTA240B F TTA SVX02C EN 18 AC60D8 1 50 Hz TTA075AD F TTA085AD F TTA100AD F TTA100...

Страница 2: ...at the end of this manual Should equipment failure occur contact a qualified service organization with qualified experienced HVAC technicians to properly diagnose and repair this equipment NOTICE War...

Страница 3: ...ing Procedure 14 Electrical Wiring 15 Low Voltage Wiring Electromechanical 16 Low Voltage Wiring ReliaTel 17 ReliaTel thermostat zone sensor and night setback wiring 18 Typical Split System Cooling Di...

Страница 4: ...nsing Unit Model Nomenclature T T A 0 9 0 A 3 0 0 B A 1 2 3 4 5 6 7 8 9 10 11 12 Digits 1 2 3 Product Type Digit 8 Electrical Characteristics TTA Split System Cooling 3 208 230 60 3 4 460 60 3 Digits...

Страница 5: ...2C EN 5 Figure 1 TTA075A TTA090A Dimensional Data Connection Location Clearances Corner Weights Figure 2 TTA085A TTA100A TTA120A Dimensional Data Connection Location Clearances Corner Weights Unit Dim...

Страница 6: ...EN Figure 3 TTA100B TTA120B TTA125B TTA150B Dimensional Data Connection Location Clearances Corner Weights Figure 4 TTA100C TTA120C Dimensional Data Connection Location Clearances Corner Weights Unit...

Страница 7: ...TTA SVX02C EN 7 Figure 5 TTA155B TTA180B Dimensional Data Connection Location Clearances Corner Weights Unit Dimensions...

Страница 8: ...8 TTA SVX02C EN Figure 6 TTA155C TTA180C Dimensional Data Connection Location Clearances Corner Weights Unit Dimensions...

Страница 9: ...TTA SVX02C EN 9 Figure 7 TTA200B TTA240B Dimensional Data Connection Location Clearances Corner Weights Unit Dimensions...

Страница 10: ...22 0 156 0 1 1 6 0 17 0 TTA150B4 460 60 3 414 506 25 2 35 2 10 0 70 0 1 1 2 7 7 0 TTA150BK 380 60 3 342 418 27 5 35 2 10 7 70 0 1 1 3 4 7 8 TTA150BW 575 60 3 518 632 20 5 25 2 8 2 54 0 1 1 2 0 5 7 TT...

Страница 11: ...cealed damage is discovered stop unpacking the shipment Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must provide reason able evidence tha...

Страница 12: ...h State of California law Proposition 65 This product contains fiberglass wool insulation Fiberglass dust and ceramic fibers are believed by the state of California to cause cancer through inhalation...

Страница 13: ...n seal caps and open the service valve slowly to release the nitrogen from the unit CAUTION Do not remove the seal caps from refrigerant connections until prepared to braze refrigerant lines to the co...

Страница 14: ...pump and observe the micron gauge If gauge pressure rises above 500 microns in one 1 minute then evacuation is incomplete or the system has a leak 6 If vacuum gauge does not rise above 500 microns in...

Страница 15: ...L IS REMOVED AND POWER IS APPLIED TO THE UNIT FAILURE TO OBSERVE ALL SAFETY PRECAUTIONS COULD RESULT IN SEVERE PERSONAL INJURY OR DEATH 2 Turn on power to the unit Allow the system to run for five to...

Страница 16: ...4 VOLTS 2 WIRES FOR SINGLE PHASE ONE STAGE ELECTRIC HEAT ADD 1 ADDITIONAL WIRE 24 VOLTS C COOLING ONLY THERMOSTAT 4 WIRES 24 VOLTS TWO STAGE ELECTRIC HEAT ADD 2 ADDITIONAL WIRES 24 VOLTS ONE STAGE ELE...

Страница 17: ...TTA120A TWE240B B 3 POWER WIRES LINE VOLTAGE FOR 3 PHASE FIELD WIRING 2 WIRES FOR SINGLE PHASE A 3 POWER WIRES LINE VOLTAGE C COOLING ONLY THERMOSTAT 4 WIRES 24 VOLTS B 3 POWER WIRES LINE VOLTAGE FOR...

Страница 18: ...18 TTA SVX02C EN Figure 8 Night Setback Panel Field Wiring Figure 9 Zone Sensor Field Wiring Figure 10 Thermostat Field Wiring Installation...

Страница 19: ...TTA SVX02C EN 19 Installation Figure 11 Typical Split System Cooling...

Страница 20: ...pressor will cycle back on Internal Overload Protector IOL This device is a current thermal actuated warp switch imbedded in the compressor motor windings It will shut off the compressor if the temper...

Страница 21: ...Indoor Supply Air TheevaporatorfaniscontrolledbyanON AUTOswitchon theroomthermostat WiththeswitchpositionedatAUTOand thesystemoperatinginthecoolingmode fanoperation coincideswiththecoolingruncycles If...

Страница 22: ...control algorithmscallingforadditionalcooling For Thermostat Control Whentheroomthermostatsystemswitchispositionedat COOL andthefanswitchisat AUTO theRTRMenergizes the compressor relay coil located on...

Страница 23: ...esistance Test Mode This method can be used for start up providing a decade box for variable resistance outputs is available This method initiates the different components of the unit one at a time wh...

Страница 24: ...hat mode for up to one hour while trouble shooting Refer to the sequence of operations for each mode to assist in verifying proper operation Make the necessary repairs and proceed to Steps 7 and 8 7 I...

Страница 25: ...n switch at the zone sensor to the OFF position After approxi mately 30 seconds turn the MODE selection switch to the desired mode i e HEAT COOL or AUTO Method 2 To reset the system at the unit cycle...

Страница 26: ...nsor Test Testing serial communication voltage 1 Verify 24 VAC is present between terminals J6 14 J6 11 2 Disconnect wires from J6 11 and J6 12 Measure the volt age between J6 11 and J6 12 should be a...

Страница 27: ...t from the unit casing 4 Remove corrosion from any surface and repaint Check the gasket around the control panel door to insure it fits cor rectly and is in good condition to prevent water leakage 5 I...

Страница 28: ...porator Temp Entering Air Compressor Superheat Subcooling F Dry Wet Suction Discharge Circuit 1 Circuit 1 Bulb Bulb Pressure Pressure F F Perform each inspection once per month during cooling season w...

Страница 29: ...toflostrefrigerant No liabilityshallattachtoWarrantoruntilproductshavebeenpaidforandthenliability shallbelimitedsolelytothepurchasepriceoftheequipmentunderwarrantyshown tobedefective THE WARRANTY AND...

Страница 30: ...roductsnotconformingtothiswarranty Warrantorshallnotbeobligatedtopayforthecostoflostrefrigerant Noliability whatevershallattachtoWarrantoruntilsaidproductshavebeenpaidforandthen saidliabilityshallbeli...

Страница 31: ...31...

Страница 32: ...ous product and product data improvement and reserves the right to change design and specifications without notice Literature Order Number File Number Supersedes Stocking Location TTA SVX02C EN Webb M...

Отзывы: