Installation procedures should be performed in the
sequence that they appear in this manual. Do not destroy or
remove the manual from the unit. The manual should
remain weather-protected with the unit until all installation
procedures are complete.

Note: 

It is not the intention of this manual to cover all possible

variations in systems that may occur or to provide
comprehensive information concerning every possible
contingency that may be encountered during an installation. If
additional information is required or if specific problems arise
that are not fully discussed in this manual, contact your local
Sales office.

Note: 

“Warnings” and “Cautions” 

appear at appropriate

places in this manual. Your personal safety and the proper
operation of this machine require that you follow them
carefully. The Company assumes no liability for installations or
servicing performed by unqualified personnel.

Installation Checklist

An “Installation Checklist” is provided at the end of the
installation section of this manual. Use the checklist to verify
that all necessary installation procedures have been
completed. Do not use the checklist as a substitute for reading
the information contained in the manual. Read the entire
manual before beginning installation procedures.

Unit Inspection

Inspect material carefully for any shipping damage. If
damaged, it must be reported to, and claims made against the
transportation company. Compare the information that
appears on the unit nameplate with ordering and submittal
data to insure the proper unit was shipped. Available power
supply must be compatible with electrical characteristics
specified on component nameplates. Replace damaged parts
with authorized parts only.

Inspection Checklist

To protect against loss due to damage incurred in transit,
complete the following checklist upon receipt of the unit.

[ ] Inspect individual pieces of the shipment before accepting

the unit. Check for obvious damage to the unit or packing
material.

[ ] Inspect the unit for concealed damage before it is stored

and as soon as possible after delivery. Concealed damage
must be reported within 15 days. If concealed damage is
discovered, stop unpacking the shipment. Do not remove
damaged material from the receiving location. Take photos
of the damage if possible. The owner must provide reason-
able evidence that the damage did not occur after delivery.

[ ] Notify the carrier’s terminal of damage immediately by

phone and by mail. Request an immediate joint inspection
of the damage by the carrier and the consignee.

[ ] Notify the sales representative and arrange for repair. Do

not repair the unit until the damage is inspected by the
carrier’s representative.

Initial Leak Test

All 

TTA 

units are shipped with a holding charge of nitrogen

in each circuit. Remove the compressor access panel(s)
shown in Figure 1 through Figure 7. Locate the liquid line or
suction line service valve for each circuit. Install gauges to
determine if the circuits are still pressurized. If not, the
charge has escaped. Repair as required to obtain a leak-free
circuit.

Lifting Recommendations

Before preparing the unit for lifting, estimate the approximate
center of gravity for lifting safety. Because of placement of
internal components, the unit weight may be unevenly
distributed. Approximate unit weights are given in Table 4.

Table 4. Total Unit Weight and Corner Weights (lbs)

Shipping

Net Corner 

Weights

Model

Maximum Maximum #1

#2

#3

#4

TTA090A

370

326

105

83

61

77

TTA075A

TTA085A

443

399

149

116

78

100

TTA120A

TTA100A

 

TTA120B

481

427

133

135

87

85

TTA100B

TTA120C

492

437

133

122

87

95

TTA100C

 

TTA150B

481

427

133

135

87

85

TTA125B

  

TTA180B

764

679

196

193

144

146

TTA155B

 

TTA180C

764

679

196

193

144

146

TTA155C

TTA240B

915

830

247

247

168

168

TTA200B

  ON-SIGHT LIFTING

EQUIPMENT MUST BE CAPABLE OF LIFTING THE
UNIT WEIGHT WITH AN ADEQUATE SAFETY FACTOR.
THE USE OF UNDER-CAPACITY LIFTING DEVICES
MAY RESULT IN SEVERE PERSONAL INJURY OR
DEATH AND CAN SERIOUSLY DAMAGE THE UNIT

The crated unit can be moved using a forklift of suitable
capacity. For lifting the unit, attach lifting straps or slings
securely to the lifting holes at each corner. Use spreader
bars to protect the unit casing from damage. Test lift the unit to
determine proper balance and stability.

CAUTION: Use spreader bars to prevent lifting straps
from damaging the unit. Install bars between lifting
straps. This will prevent the straps from crushing the
unit cabinet or damaging the unit finish.

Installation

Содержание TTA075AD series

Страница 1: ...ensers 7 1 2 20 Tons September 2004 Models 60 Hz TTA090A F TTA120A F TTA120B E TTA120C G TTA150B E TTA180B F TTA180C G TTA240B F TTA SVX02C EN 18 AC60D8 1 50 Hz TTA075AD F TTA085AD F TTA100AD F TTA100...

Страница 2: ...at the end of this manual Should equipment failure occur contact a qualified service organization with qualified experienced HVAC technicians to properly diagnose and repair this equipment NOTICE War...

Страница 3: ...ing Procedure 14 Electrical Wiring 15 Low Voltage Wiring Electromechanical 16 Low Voltage Wiring ReliaTel 17 ReliaTel thermostat zone sensor and night setback wiring 18 Typical Split System Cooling Di...

Страница 4: ...nsing Unit Model Nomenclature T T A 0 9 0 A 3 0 0 B A 1 2 3 4 5 6 7 8 9 10 11 12 Digits 1 2 3 Product Type Digit 8 Electrical Characteristics TTA Split System Cooling 3 208 230 60 3 4 460 60 3 Digits...

Страница 5: ...2C EN 5 Figure 1 TTA075A TTA090A Dimensional Data Connection Location Clearances Corner Weights Figure 2 TTA085A TTA100A TTA120A Dimensional Data Connection Location Clearances Corner Weights Unit Dim...

Страница 6: ...EN Figure 3 TTA100B TTA120B TTA125B TTA150B Dimensional Data Connection Location Clearances Corner Weights Figure 4 TTA100C TTA120C Dimensional Data Connection Location Clearances Corner Weights Unit...

Страница 7: ...TTA SVX02C EN 7 Figure 5 TTA155B TTA180B Dimensional Data Connection Location Clearances Corner Weights Unit Dimensions...

Страница 8: ...8 TTA SVX02C EN Figure 6 TTA155C TTA180C Dimensional Data Connection Location Clearances Corner Weights Unit Dimensions...

Страница 9: ...TTA SVX02C EN 9 Figure 7 TTA200B TTA240B Dimensional Data Connection Location Clearances Corner Weights Unit Dimensions...

Страница 10: ...22 0 156 0 1 1 6 0 17 0 TTA150B4 460 60 3 414 506 25 2 35 2 10 0 70 0 1 1 2 7 7 0 TTA150BK 380 60 3 342 418 27 5 35 2 10 7 70 0 1 1 3 4 7 8 TTA150BW 575 60 3 518 632 20 5 25 2 8 2 54 0 1 1 2 0 5 7 TT...

Страница 11: ...cealed damage is discovered stop unpacking the shipment Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must provide reason able evidence tha...

Страница 12: ...h State of California law Proposition 65 This product contains fiberglass wool insulation Fiberglass dust and ceramic fibers are believed by the state of California to cause cancer through inhalation...

Страница 13: ...n seal caps and open the service valve slowly to release the nitrogen from the unit CAUTION Do not remove the seal caps from refrigerant connections until prepared to braze refrigerant lines to the co...

Страница 14: ...pump and observe the micron gauge If gauge pressure rises above 500 microns in one 1 minute then evacuation is incomplete or the system has a leak 6 If vacuum gauge does not rise above 500 microns in...

Страница 15: ...L IS REMOVED AND POWER IS APPLIED TO THE UNIT FAILURE TO OBSERVE ALL SAFETY PRECAUTIONS COULD RESULT IN SEVERE PERSONAL INJURY OR DEATH 2 Turn on power to the unit Allow the system to run for five to...

Страница 16: ...4 VOLTS 2 WIRES FOR SINGLE PHASE ONE STAGE ELECTRIC HEAT ADD 1 ADDITIONAL WIRE 24 VOLTS C COOLING ONLY THERMOSTAT 4 WIRES 24 VOLTS TWO STAGE ELECTRIC HEAT ADD 2 ADDITIONAL WIRES 24 VOLTS ONE STAGE ELE...

Страница 17: ...TTA120A TWE240B B 3 POWER WIRES LINE VOLTAGE FOR 3 PHASE FIELD WIRING 2 WIRES FOR SINGLE PHASE A 3 POWER WIRES LINE VOLTAGE C COOLING ONLY THERMOSTAT 4 WIRES 24 VOLTS B 3 POWER WIRES LINE VOLTAGE FOR...

Страница 18: ...18 TTA SVX02C EN Figure 8 Night Setback Panel Field Wiring Figure 9 Zone Sensor Field Wiring Figure 10 Thermostat Field Wiring Installation...

Страница 19: ...TTA SVX02C EN 19 Installation Figure 11 Typical Split System Cooling...

Страница 20: ...pressor will cycle back on Internal Overload Protector IOL This device is a current thermal actuated warp switch imbedded in the compressor motor windings It will shut off the compressor if the temper...

Страница 21: ...Indoor Supply Air TheevaporatorfaniscontrolledbyanON AUTOswitchon theroomthermostat WiththeswitchpositionedatAUTOand thesystemoperatinginthecoolingmode fanoperation coincideswiththecoolingruncycles If...

Страница 22: ...control algorithmscallingforadditionalcooling For Thermostat Control Whentheroomthermostatsystemswitchispositionedat COOL andthefanswitchisat AUTO theRTRMenergizes the compressor relay coil located on...

Страница 23: ...esistance Test Mode This method can be used for start up providing a decade box for variable resistance outputs is available This method initiates the different components of the unit one at a time wh...

Страница 24: ...hat mode for up to one hour while trouble shooting Refer to the sequence of operations for each mode to assist in verifying proper operation Make the necessary repairs and proceed to Steps 7 and 8 7 I...

Страница 25: ...n switch at the zone sensor to the OFF position After approxi mately 30 seconds turn the MODE selection switch to the desired mode i e HEAT COOL or AUTO Method 2 To reset the system at the unit cycle...

Страница 26: ...nsor Test Testing serial communication voltage 1 Verify 24 VAC is present between terminals J6 14 J6 11 2 Disconnect wires from J6 11 and J6 12 Measure the volt age between J6 11 and J6 12 should be a...

Страница 27: ...t from the unit casing 4 Remove corrosion from any surface and repaint Check the gasket around the control panel door to insure it fits cor rectly and is in good condition to prevent water leakage 5 I...

Страница 28: ...porator Temp Entering Air Compressor Superheat Subcooling F Dry Wet Suction Discharge Circuit 1 Circuit 1 Bulb Bulb Pressure Pressure F F Perform each inspection once per month during cooling season w...