45

RT-PRC016-EN

Mechanical
Specifications

General

The units shall be convertible airflow. The
operating range shall be between 46°C
and -18°C (115°F and 0°F) in cooling as
standard from the factory for all units. All
units shall be factory assembled,
internally wired, fully charged with R-22,
and 100 percent run tested to check
cooling operation, fan and blower
rotation, and control sequence before
leaving the factory. Wiring internal to the
unit shall be colored and numbered for
simplified identification.

Casing

Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Cabinet construction shall allow for all
maintenance on one side of the unit.
Service panels shall have lifting handles
and be removed and reinstalled by
removing only a single fastener while
providing a water and air tight seal. All
exposed vertical panels and top covers in
the indoor air section shall be insulated
with a cleanable foil-faced, fire-retardent
permanent, odorless glass fiber material.
The base of the unit shall be insulated
with 13 mm, 16 kg (1/2 inch, 1 pound)
density foil-faced, closed-cell material. All
insulation edges shall be either captured
or sealed.The unit’s base pan shall have
no penetrations within the perimeter of
the curb other than the raised 29 mm (1

1

/

8

inch high downflow supply/return
openings to provide an added water
integrity precaution, if the condensate
drain backs up. The base of the unit shall
have provisions for forklift and crane
lifting, with forklift capabilities on three
sides of the unit.

Unit Top

The top cover shall be one piece
construction or where seams exist, it
shall be double-hemmed and gasket-
sealed.  The ribbed top adds extra
strength and prevents water from
pooling on unit top.

Filters

One inch, throwaway filters shall be
standard on all 5 ton units. The filter rack
can be converted to two inch capability.
50 mm (2 inch) filters shall be factory
supplied on all 6-10 ton units. Optional 50
mm (2 inch) pleated filters shall be
available.

Compressors

All units shall have direct-drive, hermetic,
scroll type compressors with centrifugal
type oil pumps. Motor shall be suction
gas-cooled and shall have a voltage
utilization range of plus or minus 10
percent of unit nameplate voltage.
Internal overloads shall be provided with
the scroll compressors. Low and high
pressure switches shall be standard.

Refrigerant Circuits

Service pressure ports, and refrigerant
line filter driers are factory-installed as
standard. An area shall be provided for
replacement suction line driers.

Evaporator and Condenser Coils

Internally finned, 8 mm (

5

/

16

”) copper

tubes mechanically bonded to a
configured aluminum plate fin shall be
standard. Coils shall be leak tested at the
factory to ensure the pressure integrity.
The evaporator coil and condenser coil
shall be leak tested to 1375 kPa (200 psig)
and pressure tested to 3100 kPa (450
psig). The condenser coil shall have a
patent pending 1 + 1 + 1 hybrid coil
designed with slight gaps for ease of
cleaning. A removeable, reversible,
double-sloped condensate drain pan with
provision for through the base
condensate drain is standard.

Outdoor Fans

The outdoor fan shall be direct-drive,
statically and dynamically balanced,
draw-through in the vertical discharge
position. The fan motor shall be
permanently lubricated and shall have
built-in thermal overload protection.

Indoor Fan

All units shall have belt drive motors.
Units with belt drive motors shall have
an adjustable idler-arm assembly for
quick-adjustment to fan belts and motor
sheaves. All motors shall be thermally
protected. Oversized motors shall be
available for high static operations.

Controls

Unit shall be completely factory-wired
with necessary controls and contactor
pressure lugs or terminal block for
power wiring. Units shall have single
point power connection as standard.
Unit shall provide an external location
for mounting a fused disconnect device.

Microprocessor controls provide for all
24 volt control functions. The resident
control algorithms shall make all
heating, cooling, and/or ventilating
decisions in response to electronic
signals from sensors measuring indoor
and outdoor temperatures. The control
algorithm maintains accurate
temperature control, minimizes drift
from set point, and provides better
building comfort. A centralized
Microprocessor shall provide anti-short
cycle timing and time delay between
compressors to provide a higher level of
machine protection.

Содержание TSC060-120

Страница 1: ...Packaged Cooling with Electric Heat Rooftop Units Precedent TSC060 120 50 Hz RT PRC016 EN February 2004...

Страница 2: ...ity for the simplest to the most sophisticated applications In addition to controls Precedent offers many other outstanding features and option choices With its sleek compact cabinet rounded corners a...

Страница 3: ...Application Considerations Selection Procedure Model Number Description General Data Performance Data Zone Controls Electrical Data Jobsite Connections Dimensional Data Weights Mechanical Specificati...

Страница 4: ...drain trap on either side of the unit Through the Base Condensate Every unit includes provisions for through the base condensate drain connections This allows the drain to be connected through the roo...

Страница 5: ...re built to order in our standard shortest in the industry ship cycle time Standardized Components Components are placed in the same location on all Precedent units Familiarize yourself with one Prece...

Страница 6: ...i short cycle timer time delay relay and minimum on time controls These controls are factory tested to assure proper operation Requires no special tools to run the Precedent unit through its paces dur...

Страница 7: ...lter or a fan that s not working The field installation charges for these valuable feedback devices often eliminate them from consideration Factory installation can make such features a good investmen...

Страница 8: ...ately Every unit receives a 100 unit run test before leaving the production line to make sure it lives up to rigorousTrane requirements We test designs at our factory not on our customers Quality And...

Страница 9: ...pers and relieving the conditioned space NOTE THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED PRESSURE DROP OF THE RETURN AIR SYSTEM SHOULD BE CONSIDERED T...

Страница 10: ...ucted the pressure drop for a 25 mm filter already in the unit see note belowTable PD 6 Therefore the actual total static pressure is 169 17 fromTable PD 21 152 Pa With 3400 m3 h and 152 Pa Table PD 6...

Страница 11: ...ducted the pressure drop for a 1 in filter already in the unit see note belowTable PD 6a Therefore the actual total static pressure is 0 69 0 15 fromTable PD 21a 0 50 wg With 2000 cfm and 0 50 wg Tabl...

Страница 12: ...Type Motor 0 Standard Drive 1 Oversized Motor Digit 16 Hinged Service Access Filters 0 Standard Panels Standard Filters A Hinged Access Panels Standard Filters B Standard Panels 50 mm 2 Pleated Filte...

Страница 13: ...1 Direct 1 CFM 2900 5100 5200 5500 5800 No Motors kW HP 1 0 30 0 40 1 56 0 75 1 56 0 75 1 56 0 75 1 56 0 75 MotorRPM 950 950 950 950 950 Belt Drive Indoor Fan Type FC Centrifugal FC Centrifugal FC Ce...

Страница 14: ...Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 1a Gross Cooling Capacities MBH _ TSC060AD _ IP Enter 85 95 105 115 Dry Bulb CFM Temp 61 67 73 61 67 73 61 67 73 61 67 73 Airflow F TGC SHC T...

Страница 15: ...t 2 TGC Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 2a Gross Cooling Capacities MBH TSC072AD IP Enter 85 95 105 115 Dry Bulb CFM Temp 61 67 73 61 67 73 61 67 73 61 67 73 Airflow F TGC S...

Страница 16: ...t 2 TGC Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 3a Gross Cooling Capacities MBH TSC090AD IP Enter 85 95 105 115 Dry Bulb CFM Temp 61 67 73 61 67 73 61 67 73 61 67 73 Airflow F TGC S...

Страница 17: ...hown are gross and have not considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 TGC Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 4 Gross Cooling Capacities kW TSC...

Страница 18: ...Bulb CFM Temp 61 67 73 61 67 73 61 67 73 61 67 73 Airflow F TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 75 109 9 96 4 122 1 73 8 128 5 47 6 101 2 9...

Страница 19: ...NuisanceTripping Or Premature Motor Failure Our Product s Warranty Will Not Be Affected Table PD 6a Belt Drive Evaporator Fan Performance TSC060AD Downflow Configuration IP External Static Pressure In...

Страница 20: ...ping Or Premature Motor Failure Our Product s Warranty Will Not Be Affected Table PD 7 Belt Drive Evaporator Fan Performance TSC060AD Horizontal Configuration SI External Static Pressure Pascals 25 50...

Страница 21: ...ata Will Not Result In NuisanceTripping Or Premature Motor Failure Our Product s Warranty Will Not Be Affected Table PD 8a Belt Drive Evaporator Fan Performance TSC072AD Downflow Configuration IP Exte...

Страница 22: ...rTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure Our Product s Warranty Will Not Be Affected Table PD 9 Belt Drive Evaporator Fan Performance TSC072AD Horizontal Configurat...

Страница 23: ...OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure Our Product s Warranty Will Not Be Affected Table PD 10a Belt Drive Evaporator Fan Performance TSC090AD Downflow Configur...

Страница 24: ...OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure Our Product s Warranty Will Not Be Affected Table PD 11a Belt Drive Evaporator Fan Performance TSC090AD Horizontal Confi...

Страница 25: ...Tabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure Our Product s Warranty Will Not Be Affected Table PD 12a Belt Drive Evaporator Fan Performance TSC102AD Downflow Configurati...

Страница 26: ...bular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure Our Product s Warranty Will Not Be Affected Table PD 13a Belt Drive Evaporator Fan Performance TSC102AD Horizontal Configurat...

Страница 27: ...82 1001 1 95 8160 803 1 21 833 1 31 861 1 42 887 1 52 916 1 64 945 1 77 972 1 90 997 2 02 1022 2 14 1046 2 27 Table PD 14a Belt Drive Evaporator Fan Performance TSC120AD Downflow Configuration IP Ext...

Страница 28: ...r Data Will Not Result In Nuisance Tripping Or Premature Motor Failure Our Product s Warranty Will Not Be Affected Table PD 15a Belt Drive Evaporator Fan Performance TSC120AD Horizontal Configuration...

Страница 29: ...ave Fan Speed RPM Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turns Model No Open Open Open Open Open Open Closed TSC060AD N A 1243 1311 1379 1450 1515 1588 TSC072AD N A 967 1021 1075 1128 1183 123...

Страница 30: ...pers2 Accessory kW 3 Unit Airflow Standard Pleated Filters 100 OA 100 RA 100 OA 100 RA Model No CFM Filters1 2 inch Downflow Horizontal 9 13 27 40 TSC060AD 1600 0 10 0 15 0 12 0 04 0 12 0 01 0 045 0 0...

Страница 31: ...5 33 9 40 4 2 11 3 13 10 22 5 26 9 Notes 1 Does not include indoor fan power or heat 2 Heaters are rated at 380V 415V For other than rated voltage CAP Voltage Rated Voltage 2 x Rated Cap Table PD 23A...

Страница 32: ...calculate temp rise at differrent airflow use following formula Temp Rise C0 across Elect Htr kW x 2985 m3 h Table PD 24A AirTemperature Rise Across Electric Heaters Degrees F kW 2000 CFM 2400 CFM 30...

Страница 33: ...System Switch Fan Auto or Off Switch One temperature setpoint lever Manual Automatic Changeover Auto Heat Cool or Off System Switch Fan Auto or Off Switch Two temperature setpoint levers Optional Stat...

Страница 34: ...42 456 23 2 35 24 2 35 TSC090AD 342 456 24 8 35 26 5 35 TSC102AD 342 456 26 8 35 28 5 35 TSC120AD 342 456 31 2 40 31 2 40 Notes 1 All units to be installed under local codes Table ED 2 UnitWiringWith...

Страница 35: ...the customer DISCONNECT SWITCH BY OTHERS ROOFTOP UNIT ZONE SENSOR OR THERMOSTAT Jobsite Connections Zone Sensors Typical Number Of Wires A Manual Changeover 4 Manual Auto Changeover 5 Manual Auto Chan...

Страница 36: ...36 RT PRC016 EN Dimensional Data All dimensions are in inches millimeters TSC060 TSC060...

Страница 37: ...37 RT PRC016 EN Dimensional Data TSC060 All dimensions are in inches millimeters TSC060 Horizontal Airflow Supply Return TSC060 Downflow Airflow Supply Return TSC060 Unit Clearance and Roof Opening...

Страница 38: ...38 RT PRC016 EN Dimensional Data TSC060 All dimensions are in inches millimeters TSC060 Downflow Duct Connections Field Fabricated TSC060 Roof Curb...

Страница 39: ...39 RT PRC016 EN Dimensional Data TSC072 120 All dimensions are in inches millimeters TSC072 090 TSC102 120...

Страница 40: ...6 EN Dimensional Data TSC072 120 All dimensions are in inches millimeters TSC072 120 Downflow Airflow Supply and Return TSC072 120 Horizontal Airflow Supply and Return TSC072 120 Unit Clearance and Ro...

Страница 41: ...41 RT PRC016 EN Dimensional Data TSC072 120 All dimensions are in inches millimeters ALL FLANGES 1 1 4 31 MM TSC072 120 Downflow Duct Connections Field Fabricated TSC072 120 Roof Curb...

Страница 42: ...ensional Data TSC060 Options Accessories All dimensions are in inches millimeters TSC060 Economizer Manual or Motorized Fresh Air Damper TSC060 Barometric Relief Damper Hood TSC060 Swing Diameter for...

Страница 43: ...PRC016 EN Dimensional Data TSC072 120 Options Accessories All dimensions are in inches millimeters TSC072 120 Economizer and Barometric Relief Damper Hoods TSC072 120 Swing Diameter for Hinged Door s...

Страница 44: ...87 982 323 253 178 229 39 22 Notes 1 Corner weights are given for information only All models must be supported continuously by a curb or equivalent frame support 2 Weights are approximate Table W 2 A...

Страница 45: ...ssors with centrifugal type oil pumps Motor shall be suction gas cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage Internal overloads shall be pro...

Страница 46: ...by the installing contractor Phase Monitor Phase monitor shall provide 100 protection for motors and compressors against problems caused by phase loss phase imbalance and phase reversal Phase monitor...

Страница 47: ...on for microprocessor controlled units The fan failure switch will disable all unit functions and flash the Service LED on the zone sensor The dirty filter switch will light the Service LED on the zon...

Страница 48: ...and reserves the right to change design and specifications without notice Trane A business of American Standard Companies www trane com For more information contact your local district office or e mai...

Отзывы: