32
RT-PRC016-EN
Performance
Data
Table PD-24 — Air Temperature Rise Across Electric Heaters (Degrees C)
kW
3400 m
3
/h
4100 m
3
/h
5100 m
3
/h
5800 m
3
/h
6800 m
3
/h
380V / 415V
Voltage
Stages
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
07.5 / 09.0
380-415/50/3
2
6.6 / 7.9
—-
—-
—-
—-
10.9 / 13.0
380-415/50/3
2
9.6 / 11.4
—-
—-
—-
—-
11.3 / 13.5
380-415/50/3
1
—-
8.3 / 9.9
6.6 / 7.9
—-
—-
14.4 / 17.2
380-415/50/3
2
12.6 / 15.1
—-
—-
—-
—-
16.9 / 20.2
380-415/50/3
2
—-
12.4 / 14.8
9.9 / 11.8
8.7 / 10.4
7.4 / 8.9
22.6 / 26.9
380-415/50/3
2
—-
16.5 / 19.7
13.2 / 15.7
11.7 / 13.9
9.9 / 11.8
33.8 / 40.4
380-415/50/3
2
—-
—-
—-
—-
14.8 / 17.7
Note:
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:
Temp. Rise (C
0
) across Elect Htr = (kW x 2985)/( m
3
/h)
Table PD-24A — Air Temperature Rise Across Electric Heaters (Degrees F)
kW
2000 CFM
2400 CFM
3000 CFM
3400 CFM
4000 CFM
380V / 415V
Voltage
Stages
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
07.5 / 09.0
380-415/50/3
2
11.9 / 14.2
—-
—-
—-
—-
10.9 / 13.0
380-415/50/3
2
17.2 / 20.5
—-
—-
—-
—-
11.3 / 13.5
380-415/50/3
1
—-
14.9 / 17.8
11.9 / 14.2
—-
—-
14.4 / 17.2
380-415/50/3
2
22.8 / 27.2
—-
—-
—-
—-
16.9 / 20.2
380-415/50/3
2
—-
22.3 / 26.6
17.8 / 21.3
15.7 / 18.8
13.4 / 16.0
22.6 / 26.9
380-415/50/3
2
—-
29.8 / 35.4
23.8 / 28.3
21.0 / 25.0
17.9 / 21.3
33.8 / 40.4
380-415/50/3
2
—-
—-
—-
—-
26.7 / 31.9
Note:
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:
Temp. Rise (F
0