26
RT-PRC016-EN
Performance
Data
Table PD-13 — Belt Drive Evaporator Fan Performance -TSC102AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.50 Nom kW Std Mtr & Low Static Drive
1.50 Nom kW Standard Motor & Drive
4620
-
-
-
-
646
0.50
689
0.58
734
0.67
781
0.77
826
0.88
865
0.98
898
1.07
928
1.16
5200
616
0.51
654
0.57
693
0.64
735
0.73
773
0.82
812
0.92
855
1.03
897
1.15
934
1.27
969
1.38
5780
675
0.68
711
0.75
743
0.82
781
0.91
819
1.01
853
1.11
886
1.21
925
1.34
964
1.47
1000
1.60
6350
735
0.89
770
0.97
799
1.04
830
1.12
865
1.23
899
1.34
930
1.45
960
1.56
994
1.68
1028
1.82
6930
796
1.14
828
1.23
857
1.31
883
1.39
913
1.48
945
1.60
977
1.72
1006
1.84
1034
1.96
1061
2.08
1.50 Nom kW Std Mtr
2.24 Nom kW Over-Sized
& High Static Drive
Motor & High Static Drive
External Static Pressure (Pascals)
275
300
325
350
375
400
425
450
475
500
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.50 Nom kW Standard Motor & High Static Drive
4620
956
1.25
982
1.33
1008
1.42
1033
1.51
1056
1.60
1079
1.69
1102
1.78
1125
1.87
1146
1.95
1168
2.04
5200
999
1.49
1026
1.58
1052
1.68
1078
1.78
1101
1.88
1124
1.98
1146
2.08
1168
2.18
1188
2.27
1209
2.37
5780
1034
1.73
1067
1.86
1094
1.97
1120
2.08
1145
2.20
1168
2.31
1191
2.42
1213
2.53
1234
2.63
1254
2.74
6350
1063
1.96
1098
2.11
1129
2.26
1158
2.40
1185
2.53
1210
2.66
1234
2.78
1256
2.90
1278
3.03
1299
3.15
6930
1093
2.23
1125
2.38
1157
2.53
1188
2.70
1218
2.86
1245
3.01
1273
3.16
1297
3.31
-
-
-
-
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
← ← ← ← ←
Table PD-13a — Belt Drive Evaporator Fan Performance -TSC102AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2 HP Std Mtr & Low Static Drive
2 HP Standard Motor & Drive
2720
-
-
-
-
646
0.67
689
0.78
734
0.90
781
1.04
826
1.18
865
1.31
898
1.44
928
1.56
3060
616
0.69
654
0.77
693
0.86
735
0.98
773
1.10
812
1.23
855
1.39
897
1.55
934
1.70
969
1.85
3400
675
0.92
711
1.01
743
1.10
781
1.22
819
1.36
853
1.49
886
1.62
925
1.79
964
1.97
1000
2.14
3740
735
1.20
770
1.30
799
1.40
830
1.51
865
1.65
899
1.79
930
1.94
960
2.09
994
2.26
1028
2.44
4080
796
1.53
828
1.65
857
1.76
883
1.86
913
1.99
945
2.15
977
2.30
1006
2.47
1034
2.63
1061
2.79
3 HP Over-Sized Mtr & Drive
2 HP Std Motor &
Hi Static Driv
e
← ← ← ← ←
←←←←←
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2 HP Standard Motor & High Static Drive
3 HP Over-Sized Motor & Drive
2720
956
1.67
982
1.79
1008
1.91
1033
2.03
1056
2.14
1079
2.26
1102
2.38
1125
2.5
1146
2.62
1168
2.74
3060
999
1.99
1026
2.12
1052
2.26
1078
2.39
1101
2.52
1124
2.66
1146
2.79
1168
2.92
1188
3.05
1209
3.18
3400
1034
2.32
1067
2.49
1094
2.64
1120
2.79
1145
2.94
1168
3.09
1191
3.24
1213
3.39
1234
3.53
1254
3.68
3740
1063
2.63
1098
2.84
1129
3.03
1158
3.21
1185
3.39
1210
3.56
1234
3.73
1256
3.89
1278
4.06
1299
4.23
4080
1093
2.99
1125
3.19
1157
3.40
1188
3.62
1218
3.83
1245
4.03
1273
4.24
1297
4.44
-
-
-
-
3 HP Over-Sized Motor & Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.