25
RT-PRC016-EN
Performance
Data
Table PD-12 — Belt Drive Evaporator Fan Performance -TSC102AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.50 Nom kW Standard Motor & Low Static Drive
1.50 Nom kW Standard Motor & Drive
4620
-
-
-
-
-
-
613
0.45
655
0.54
695
0.62
733
0.71
769
0.81
802
0.90
833
1.00
5200
-
-
-
-
611
0.48
650
0.55
688
0.64
725
0.73
761
0.83
796
0.93
828
1.03
861
1.13
5780
-
-
612
0.51
651
0.59
689
0.68
724
0.76
759
0.86
792
0.96
825
1.07
856
1.18
887
1.28
6350
622
0.56
659
0.64
693
0.72
729
0.82
764
0.92
795
1.01
826
1.11
857
1.22
887
1.34
916
1.46
6930
671
0.71
706
0.80
738
0.89
770
0.98
804
1.09
834
1.19
864
1.30
892
1.40
920
1.52
948
1.64
1.50
Nom kW Standard
Motor & Hi Static Drive
← ← ← ← ←
External Static Pressure (Pascals)
275
300
325
350
375
400
425
450
475
500
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.50 Nom kW Std Mtr & Drive
1.50 Nom kW Std Mtr & Hi Static Dr
4620
863
1.11
892
1.21
920
1.33
946
1.44
973
1.55
999
1.67
1025
1.79
1050
1.90
1073
2.02
1098
2.14
5200
891
1.24
919
1.35
946
1.46
973
1.58
999
1.71
1024
1.83
1048
1.96
1072
2.09
1096
2.22
1119
2.34
5780
917
1.40
946
1.51
974
1.63
1001
1.75
1026
1.88
1051
2.01
1074
2.14
1099
2.27
1121
2.41
1143
2.55
6350
945
1.58
974
1.70
1001
1.82
1028
1.95
1054
2.08
1079
2.20
1103
2.34
1126
2.48
1148
2.62
1170
2.76
6930
976
1.78
1002
1.91
1029
2.04
1055
2.17
1081
2.30
1105
2.43
1130
2.58
1154
2.72
1176
2.85
1199
3.01
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Table PD-12a — Belt Drive Evaporator Fan Performance -TSC102AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2 HP Standard Motor & Low Static Drive
2 HP Standard Motor & Drive
2720
-
-
-
-
-
-
613
0.60
655
0.72
695
0.84
733
0.95
769
1.08
802
1.21
833
1.34
3060
-
-
-
-
611
0.64
650
0.74
688
0.85
725
0.98
761
1.11
796
1.25
828
1.38
861
1.52
3400
-
-
612
0.68
651
0.79
689
0.91
724
1.02
759
1.15
792
1.29
825
1.43
856
1.58
887
1.72
3740
622
0.76
659
0.86
693
0.97
729
1.10
764
1.23
795
1.35
826
1.49
857
1.64
887
1.79
916
1.96
4080
671
0.96
706
1.08
738
1.19
770
1.32
804
1.46
834
1.60
864
1.74
892
1.88
920
2.04
948
2.20
2 HP Standard Motor &
Hi Static Drive
← ← ← ← ←
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2 HP Standard Mtr & Drive
2 HP Std Motor & Hi Static Drive
2720
863
1.48
892
1.63
920
1.78
946
1.93
973
2.08
999
2.24
1025
2.39
1050
2.55
1073
2.71
1098
2.88
3060
891
1.66
919
1.81
946
1.96
973
2.12
999
2.29
1024
2.46
1048
2.63
1072
2.80
1096
2.98
1119
3.14
3400
917
1.87
946
2.03
974
2.18
1001
2.34
1026
2.52
1051
2.69
1074
2.86
1099
3.05
1121
3.23
1143
3.41
3740
945
2.11
974
2.28
1001
2.44
1028
2.61
1054
2.78
1079
2.96
1103
3.14
1126
3.32
1148
3.51
1170
3.71
4080
976
2.38
1002
2.56
1029
2.73
1055
2.91
1081
3.09
1105
3.26
1130
3.45
1154
3.65
1176
3.83
1199
4.03
3 HP Over-Sized Motor & Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.