20
RT-PRC016-EN
Performance
Data
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1/2 HP Standard Motor & Drive
1-1/2 HP Standard Motor & Hi Static Drive
1600
1206
1.12
1241
1.20
1275
1.28
1306
1.37
1338
1.46
1800
1256
1.32
1291
1.41
1326
1.50
1359
1.60
1390
1.69
2000
1309
1.56
1343
1.66
1376
1.76
-
-
-
-
2200
-
-
-
-
-
-
-
-
-
-
2400
-
-
-
-
-
-
-
-
-
-
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
External Static Pressure (Pascals)
275
300
325
350
375
CFM
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Drive
2720
1206
0.83
1241
0.89
1275
0.96
1306
1.02
1338
1.09
3060
1256
0.99
1291
1.05
1326
1.12
1359
1.19
1390
1.26
3400
1309
1.16
1343
1.24
1376
1.31
-
-
-
-
3740
-
-
-
-
-
-
-
-
-
-
4080
-
-
-
-
-
-
-
-
-
-
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1
.12 Nom kW Standard Motor &
Hi Static Drive
←
←
←
←
←
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Table PD-7 - Belt Drive Evaporator Fan Performance- TSC060AD - Horizontal Configuration - (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Std Motor & Low Static Drive
1.12 Nom kW Standard Motor & Drive
2720
707
0.26
774
0.31
837
0.37
898
0.43
953
0.48
1001
0.54
1045
0.59
1087
0.65
1129
0.71
1168
0.77
3060
778
0.36
840
0.41
897
0.48
953
0.54
1008
0.60
1058
0.67
1102
0.73
1143
0.79
1181
0.85
1219
0.92
3400
850
0.48
908
0.54
961
0.60
1012
0.67
1062
0.74
1111
0.81
1157
0.88
1198
0.95
1237
1.02
1274
1.09
3740
923
0.63
978
0.69
1028
0.76
1075
0.83
1120
0.91
1166
0.99
1211
1.06
1254
1.14
1294
1.22
1330
1.29
4080
997
0.80
1049
0.87
1096
0.94
1140
1.02
1183
1.10
1223
1.18
1266
1.27
-
-
-
-
-
-
1.12 Nom kW Standard Motor & Hi Static Drive
← ← ← ← ←
Table PD-7a - Belt Drive Evaporator Fan Performance- TSC060AD - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor &
Low Static Drive
1-1/2 HP Standard Motor & Drive
1600
707
0.35
774
0.42
837
0.50
898
0.57
953
0.65
1001
0.72
1045
0.80
1087
0.87
1129
0.95
1168
1.03
1800
778
0.48
840
0.56
897
0.64
953
0.72
1008
0.81
1058
0.89
1102
0.98
1143
1.06
1181
1.15
1219
1.23
2000
850
0.65
908
0.73
961
0.81
1012
0.90
1062
1.00
1111
1.09
1157
1.19
1198
1.28
1237
1.37
1274
1.47
2200
923
0.84
978
0.93
1028
1.02
1075
1.12
1120
1.22
1166
1.32
1211
1.43
1254
1.53
1294
1.63
1330
1.74
2400
997
1.07
1049
1.17
1096
1.27
1140
1.37
1183
1.48
1223
1.59
1266
1.70
-
-
-
-
-
-
1-1/2 HP Standard Motor & Hi Static Drive
← ← ← ← ←