19
RT-PRC016-EN
Table PD-6 — Belt Drive Evaporator Fan Performance - TSC060AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Low Static Drive
1.12 Nom kW Standard Motor & Drive
2720
-
-
703
0.27
757
0.31
806
0.35
854
0.39
899
0.43
944
0.49
985
0.54
1023
0.59
1060
0.64
3060
706
0.32
760
0.35
815
0.40
861
0.45
904
0.49
947
0.54
988
0.58
1028
0.64
1067
0.70
1104
0.76
3400
773
0.43
821
0.46
873
0.51
918
0.57
958
0.62
998
0.67
1036
0.71
1073
0.76
1111
0.82
1147
0.89
3740
840
0.56
885
0.60
930
0.65
977
0.71
1016
0.77
1053
0.82
1089
0.88
1124
0.93
1158
0.98
1191
1.03
4080
909
0.71
950
0.76
990
0.80
1034
0.87
1074
0.93
1110
1.00
1143
1.06
1177
1.12
1209
1.17
1241
1.23
External Static Pressure (Pascals)
275
300
325
350
375
CFM
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Drive
2720
1093
0.69
1126
0.74
1160
0.79
1190
0.84
1222
0.90
3060
1138
0.82
1171
0.87
1203
0.93
1232
0.98
1262
1.04
3400
1182
0.96
1215
1.02
1246
1.09
1276
1.15
1306
1.21
3740
1226
1.10
1258
1.17
1290
1.25
-
-
-
-
4080
1272
1.29
-
-
-
-
-
-
-
-
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1
.12 Nom kW Standard Motor &
Hi Static Drive
←
←
←
←
←
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Table PD-6a — Belt Drive Evaporator Fan Performance -TSC060AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Low Static Drive
1-1/2 HP Standard Motor & Drive
1600
-
-
703
0.36
757
0.41
806
0.47
854
0.52
899
0.58
944
0.65
985
0.73
1023
0.79
1060
0.86
1800
706
0.42
760
0.47
815
0.54
861
0.60
904
0.66
947
0.72
988
0.78
1028
0.86
1067
0.94
1104
1.02
2000
773
0.57
821
0.62
873
0.69
918
0.76
958
0.83
998
0.90
1036
0.96
1073
1.02
1111
1.10
1147
1.19
2200
840
0.75
885
0.80
930
0.87
977
0.95
1016
1.03
1053
1.10
1089
1.17
1124
1.24
1158
1.31
1191
1.39
2400
909
0.96
950
1.02
990
1.08
1034
1.16
1074
1.25
1110
1.34
1143
1.419
1177
1.50
1209
1.57
1241
1.65
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Drive
1600
1093
0.92
1126
0.99
1160
1.06
1190
1.13
1222
1.20
1800
1138
1.10
1171
1.17
1203
1.25
1232
1.32
1262
1.39
2000
1182
1.28
1215
1.37
1246
1.46
1276
1.54
1306
1.62
2200
1226
1.48
1258
1.57
1290
1.67
-
-
-
-
2400
1272
1.73
-
-
-
-
-
-
-
-
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
1
-1/2 HP Standard Motor &
Hi Static Drive
←
←
←
←
←
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Performance
Data