13
RT-PRC016-EN
General
Data
Table GD - 1 — General Data
Convertible Units
Convertible Units
Convertible Units
Convertible Units
Convertible Units
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Cooling Performance
1
Gross Capacity - kW (MBh)
18.2 (62.0)
23.2 (79.0)
26.7 (91.0)
31.1 (106.0)
34.9 (119.0)
COP (EER)
2
2.99 (10.2)
3.08 (10.5)
3.02 (10.3)
3.02 (10.3)
2.99 (10.2)
Nominal Airflow - m
3
/h (cfm)
3400 (2000)
4080 (2400)
5100 (3000)
5780 (3400)
6800 (4000)
Rated Airflow - m
3
/h (cfm)
3400 (2000)
3570 (2100)
4460 (2625)
5100 (3000)
5950 (3500)
Net Capacity - kW (MBh)
17.3 (59.0)
22.0 (75.0)
25.2 (86.0)
29.9 (102.0)
33.1 (113.0)
System Power - kW
5.78
7.14
8.35
9.90
11.08
Compressor
Number - Type
1-Climatuff Scroll
1-Trane 3-D Scroll
1-Trane 3-D Scroll
2-Climatuff Scroll
2-Climatuff Scroll
Outdoor Sound Rating - dB
3
80
85
85
83
79
Outdoor Coil - Type
Lanced
Lanced
Lanced
Lanced
Lanced
Tube Size - in. OD
0.3125
0.3125
0.3125
0.3125
0.3125
Face Area - m
2
(sq ft)
1.02 (10.96)
1.29 (13.88)
1.29 (13.88)
1.75 (18.89)
2.41 (25.92)
Rows / FPI
3 / 17
2 / 17
2 / 17
2 / 17
2 / 17
Indoor Coil - Type
Lanced
Lanced
Lanced
Lanced
Lanced
Tube Size OD - in.
0.3125
0.3125
0.3125
0.3125
0.3125
Face Area - m
2
(sq ft)
0.62 (6.68)
0.92 (9.89)
0.92 (9.89)
1.15 (12.36)
1.15 (12.36)
Rows / FPI
3 / 16
2 / 16
3 / 16
3 / 16
4 / 16
Refrigerant Control
Short Orifice
Short Orifice
Short Orifice
Short Orifice
Short Orifice
Drain Connection No. / Size - in.
1 / 0.75 NPT
1 / 0.75 NPT
1 / 0.75 NPT
1 / 0.75 NPT
1 / 0.75 NPT
Outdoor Fan - Type
Propeller
Propeller
Propeller
Propeller
Propeller
No. Used / Diameter - in.
1 / 22
1 / 26
1 / 26
1 / 26
1 / 26
Drive Type / No. Speeds
Direct / 1
Direct / 1
Direct / 1
Direct / 1
Direct / 1
CFM
2900
5100
5200
5500
5800
No. Motors / kW (HP)
1 / 0.30 (0.40)
1 / .56 (0.75)
1 / .56 (0.75)
1 / .56 (0.75)
1 / .56 (0.75)
Motor RPM
950
950
950
950
950
Belt Drive Indoor Fan
- Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used
1
1
1
1
1
Fan Diameter x Width - mm (in.)
280 X 280 (11 x 11)
305 X 305 (12 x 12)
305 X 305 (12 x 12)
381 X 381 (15 x 15)
381 X 381 (15 x 15)
Drvie Type / No. Speeds
Belt / Variable Speed
Belt / Variable Speed
Belt / Variable Speed
Belt / Variable Speed
Belt / Variable Speed
No. Motors
1
1
1
1
1
Standard Motor Power - kW (HP)
1.1 (1.5)
1.1 (1.5)
1.5 (2.0)
1.5 (2.0)
2.2 (3.0)
Oversized Motor Power - kW (HP)
-
1.5 (2.0)
2.2 (3.0)
2.2 (3.0)
-
Motor RPM - Standard / Oversized
1450 / -
1450 / 1450
1450 / 2850
1450 / 2850
2850 / -
Motor Frame Size
56
56
56
56
56
Filters - Type Furnished
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
(No.) Size Reccommended - mm
(2) 508 X 762 X 25
(4) 406 X 635 X 50
(4) 406 X 635 X 50
(4) 508 X 635 X 50
(4) 508 X 635 X 50
(No.) Size Reccommended - in.
(2) 20 X 30 X 1
(4) 16 X 25 X 2
(4) 16 X 25 X 2
(4) 20 X 25 X 2
(4) 20 X 25 X 2
Refrigerant Charge - kg (lbs) of R-22
4
3.7 (8.2)
3.7 (8.2)
4.5 (10.0)
Circuit 1 - 3.8 (8.3)
Circuit 1 - 3.4 (7.5)
Circuit 2 - 2.0 (4.4)
Circuit 2 - 3.3 (7.3)
Notes:
1. Cooling Performance is rated at 35.0 C (95 F) ambient, 26.7 C (80 F) entering dry bulb, 19.4 C (67 F) entering wet bulb. Gross capacity does not include the effect of fan motor
heat. Net capacity includes the effect of fan motor heat. Units are suitable for operation to ± 20 % of nominal airflow.
2. EER are rated at ARI conditions.
3. Outdoor Sound rating shown is tested in accordance with ARI Standard 270. For more information refer to Performance Data Table "Sound Power Level".
4. Refrigerant charge is an approcimate value. For a more precise value, see unit nameplate and service literature.