Overview and specifications
Figure 2.
Metal-cover model dimensions and clearances
Agency listing/compliance
CE—Immunity: EN 50082-1:1997; EN 50082-2:1995
CE—Emissions: EN 50081-1:1992 (CISPR 22) Class B
UL and C-UL 916 listed: Energy management system
UL 94-5V (UL flammability rating for plenum use)
FCC Part 15, Class A
ASHRAE Cycle 1 & Cycle 2 control sequences
Additional components
The Tracer ZN521 zone controller requires the use of additional components for monitoring and
proper control of the associated equipment. The use of specific components depends on the
application. These components are not included with the Tracer ZN521 zone controller.
Power transformer
Use a UL-listed Class 2 power transformer supplying a nominal 24 Vac (19–30 Vac) to power both
the Tracer ZN521 zone controller (14 VA) and its associated output devices, including relays and
actuators, to a maximum of 12 VA per output utilized.
Water, duct, and outdoor-air temperature sensors
Temperature sensors must be Trane 10 k
Ω
(at 25°C) thermistors. Entering water and discharge air
inputs may use a sealed temperature sensor (part number 4190 1100).
9 in.
(229 mm)
2.25in.
(58 mm)
1 in.
(25 mm)
1 in.
(25 mm)
9 in.
(229 mm)
24 in.
(610 mm)
2 in.
(51 mm)
Clearances
Dimensions
2 in.
(51 mm)
1 in.
(25 mm)
7 in.
(178 mm)
1.875 in.
(48 mm)
0.28 in.
(7 mm)
6.5 in.
(165 mm)
10.25 in.
(260 mm)
width without cover
10.37 in.
(263 mm)
width with cover