background image

Introduction

The pedestal is used to allow airflow into the F-size enclosure to provide proper cooling. These instructions detail the mounting of
an F-size enclosure enclosure onto a pedestal.

More installation information, such as ambient conditions, cooling requirements, and dimensions can be found in the operating
instructions, design guide, and installation drawings.

Safety Instructions

Discharge Time

WARNING

Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Disconnect all electric power, including remote disconnects and discharge all motor start/ run capacitors before servicing.
Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for
allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged.

For additional information regarding the safe discharge of capacitors, see PROD-SVB06AEN.

The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered.
High voltage can be present even when the warning indicator lights are off. Failure to wait for a minimum of 40 minutes after
power has been removed before performing service or repair work can result in death or serious injury.

1.

Stop the motor.

2.

Disconnect AC mains and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other
frequency converters.

3.

Disconnect or lock PM motor.

4.

Wait 40 minutes for the capacitors to discharge.

5.

Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the
capacitors are fully discharged.

Positioning the Pedestal

1.

Place the pedestal in the desired location, paying attention to the following:

Ambient conditions

Cooling requirements

Unit dimensions and door clearances

2.

Pull the mains and motor cables up through the pedestal.

3.

Bolt the pedestal to the floor.

 All rights reserved.

BAS-SVN021

B

-EN

Содержание TR200 Series

Страница 1: ...rting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment ...

Страница 2: ... appropriate voltmeter that all capacitors have discharged For additional information regarding the safe discharge of capacitors see PROD SVB06AEN The frequency converter contains DC link capacitors which can remain charged even when the frequency converter is not powered High voltage can be present even when the warning indicator lights are off Failure to wait for a minimum of 40 minutes after po...

Страница 3: ...ables chains or slings may not be of the same length Adjust as necessary for even unit lift NOTICE Equipment Damage Failure to follow instructions below could result in equipment damage Do not carry or lift the unit by the discharge plate Use only the hangar brackets located at each corner to carry or lift the unit 1 Lift the frequency converter and position it on the pedestal 2 Verify that there ...

Страница 4: ...lt with lock washer and flat washer 2 M10x30 mm bolt with captive lock washer and flat washer Figure 2 Attaching the Gland Plates Illustration 1 2 Attaching the Gland Plates 1 Motor cables 2 Motor gland plate 3 Mains gland plate 4 Mains cables Installation Instructions Pedestal Kit for F size Enclosures TR200 Series BAS SVN021B EN All rights reserved 3 ...

Страница 5: ...Installation Instructions Pedestal Kit for F size Enclosures TR200 Series All rights reserved BAS SVN021B EN ...

Страница 6: ... to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial and residential applications For more information please visit trane com or tranetechnologies com BAS SVN021B EN 18 Aug 2020 Supersedes BAS SVN021A EN Jun 2016 130R0682 M0025401 130R0682 ...