background image

3.12 Operational And Checkout Procedures

3.13 Maintenance

The circuit from R to Y is also completed, energizing the compressor 
contactor of the outdoor unit. The contactor will close and start the 
compressor and condenser fan motor.

Cooling (heat pump)
Constant torque version – When the thermostat calls for cooling, the 
circuit  from  R  to  G  is  completed.  The  blower  motor  is  energized 
directly by the 24VAC signal from the thermostat.

The circuit from R to Y is also completed, energizing the compressor 
contactor of the outdoor unit. The contactor will close and start the 
compressor and condenser fan motor.
Circuit R to O energizes the reversing valve to the cooling position.

Heating (heat pump)
Constant torque version – When the thermostat calls for heating, the 
circuit from R to G is completed and the blower motor is energized 
directly by the 24VAC signal from the thermostat.

The circuit from R to Y is also completed, energizing the compressor 
contactor of the outdoor unit. The contactor will close and start the 
compressor and condenser fan motor.

In the heating mode, the reversing valve of the outdoor unit is not 
energized.

If  the  indoor  temperature  continues  to  fall,  the  R  to  W  circuit  is 
completed, energizing the electric heat contactor(s).

Heating (electric heat only)
Note: The thermostat must be setup to bring the blower on when the 
electric heat is energized.

Constant torque version - When the thermostat calls for heating, the 
circuit from R to G is completed and the blower motor is energized 
directly by the 24VAC signal from the thermostat. The circuit from R 
to W is completed energizing the heating contactor(s).

To obtain proper performance, all units must be operated and charge 
adjustments  made  in  accordance  with  procedures  found  in  the 
Service Facts document of the outdoor unit.

After  installation  has  been  completed,  it  is  recommended  that  the 
entire system be checked against the following list:
[  ] 1. Be sure unit suspension (if used) is secure and there are no 
tools or loose debris in, around or on top of the unit.
[  ] 2. Properly insulate suction lines and fittings.
[  ] 3. Properly secure and isolate all refrigerant lines.
[  ] 4. Verify that all electrical connections are tight.
[  ] 5. Check all duct outlets; they must be open and unrestricted.
[  ] 6. Check drain lines and be sure all joints are tight.
[  ] 7. Be sure the return air filter is installed.
[    ]  8.  Operate  complete  system  in  each  mode  to  verify  proper 
performance. Verify operation of supplementary electric heater.

Defrost
Supplemental heat during defrost can be provided by connecting the 
X2 (black) wire from the outdoor unit to W1 at the indoor unit. This 
will  prevent  cold  air  from  being  discharged  from  the  indoor  unit 
during defrost.

Low  voltage  control  wiring  should  be  18  Awg,  color  coded  (105 
degree  C  minimum).  For  lengths  longer  than  100ft.,  16 Awg  wire 
should be used. Make certain that separation of control wiring and 
power wiring has been maintained.

The system air filter(s) should be inspected, cleaned or replaced at 
least monthly. Make certain that the access panels are replaced and 
secured  properly  before  placing  the  unit  back  in  operation.  This 
product  is  designed  for  dependable  service;  however,  periodic 
maintenance  should  be  scheduled  and  conducted  by  trained 
professional service personnel. This service should be conducted at 
least annually, and should include testing and inspection of electrical 
and  refrigerant  components.  The  heat  transfer  surface  should  be 
cleaned.  The  blower  motor  is  permanently  lubricated  for  normal 
operating conditions.

Section 4. Wiring

R

G

C

W1

R

B

O

Y

X2

R

G

B/C

O

Y

W

HEAT PUMP SYSTEMS

Brown

24 VAC HOT

FAN

24 VAC

Common

SOV

COOL/HEAT

1st STAGE

HEATING

2nd STAGE

Thermostat

Air Handler Outdoor

Unit

Black

White

White

AC  SYSTEMS

R

G

C

W1

B

Y

R

G

B/C

Y

W

Brown

24 VAC HOT

FAN

24 VAC

Common

COOLING

HEAT

Thermostat

Air Handler Outdoor

Unit

3.11 Sequence of Operation 

Cooling (cooling only)

Constant torque version – When the thermostat calls for cooling, the 
circuit  from  R  to  G  is  completed.  The  blower  motor  is  energized 
directly by the 24VAC signal from the thermostat.

7

Содержание TMM5B0A24M21SAA

Страница 1: ...versatile units are applicable to air conditioning and heat pump applications Field installed electric resistance heaters are available All aluminum coil Blower and coil slide out easily for maintenan...

Страница 2: ...state electrical code on requirements for grounding Failure to follow this warning could result in property damage serious personal injury or death HAZARDOUS VAPORS Do not install an air handler with...

Страница 3: ...ns adhesives cleaning compounds and cement creates a corrosive condition which may cause rapid deterioration of the cabinet and internal components CAUTION SAFETY HAZARD Sharp Edge Hazard Be careful o...

Страница 4: ...the air handler above the wall mounting bracket and attach the unit to the installed bracket Reference Figure 3 1 4 Install the additional bottom plate for extra support for this type mounting see fi...

Страница 5: ...dential Winter and Summer Air Conditioning and Equipment Selection Latest editions are available from ACCA Air Conditioning Contractors of America 1513 16th Street N W Washington D C 20036 If duct sys...

Страница 6: ...ze the fan on a demand for heating or cooling Install the thermostat on an inside wall away from drafts lights or other heat sources in a location that has sufficient air circulation from other rooms...

Страница 7: ...uspension if used is secure and there are no tools or loose debris in around or on top of the unit 2 Properly insulate suction lines and fittings 3 Properly secure and isolate all refrigerant lines 4...

Страница 8: ...COMPONENT ARRANGEMENT FM NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE CAUTION ATTENTION TMM5B0A24M21SAA TMM5B0B36M31SAA Fig 4 1 8...

Страница 9: ...COMPONENT ARRANGEMENT FM NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE CAUTION ATTENTION Fig 4 2 TMM5B0B30M21SAA 9...

Страница 10: ...24 36 24 36 24 36 10 Circuit Breaker Minimum CFM MODEL 1 2 3 575 600 625 575 600 625 700 725 750 10 TMM5B0A24M21SAA TMM5B0B30M21SAA TMM5B0B36M31SAA Section 5 Heater Pressure Drop Table Use For All TMM...

Страница 11: ...n dry coil at 230V with no electric heat no filter For 24 30 and 36 sizes airflow at 208V is approximately the same as 230V because the mult tap ECM motor is a constant torque motor The torque doesn t...

Страница 12: ...ection 3 4 female pipe thread NPT Primary drain conncetion 3 4 female pipe thread NPT Front return shown Units may also be installed as bottom return See the applications section for more detail NOTE...

Страница 13: ...ww trane com www americanstandardair com The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice Tran...

Отзывы: