background image

Carefully  unpack  the  unit  and  inspect  the  contents  for  damage.  If 
any damage is found at the time of delivery, proper notification and 
claims should be made with the carrier.
Check  the  rating  plate  to  assure  model  number  and  voltage. 
Furthermore,  check  that  kits  match  with  what  was  ordered.The 
manufacturer should be notified within 5 days of any discrepancy or 
parts shortage.

The  small  air  handler  should  be  centrally  located  and  may  be 
installed  in  a  closet,  alcove,  utility  room,  or  basement.  Minimum 
clearances must be met.

The  air  handler  comes  standard  with  two  different  options  for 
mounting, wall mount or frame mount. Both mounting options require 
the unit to be level from side to side and from front to back in order to 
allow condensate to properly drain from the unit. Failure to do this will 
result  in  condensate  leaking  out  from  the  unit,  potentially  causing 
structural  damage  to  the  surrounding  support  structures,  dry  wall, 
carpet,  etc.  Also,  both  mounting  structures  require  the  ability  to 
accommodate a minimum of 150 lb load. Failure to do this will cause 
damage to the support structure and potentially damage the unit.  

The air handler comes standard with a wall mounting bracket and air 
handler mounting bracket. Reference Figure 3-1 for more detail.
1. Remove lower wall  mounting bracket from the back of the unit by
removing one screw which attaches the bracket to the air handler.
Note: Discard the screw after you have removed the wall mounting
bracket.
2. Install bracket on the wall by using 3 wood screws (not provided).
Make sure the bracket is level in order to provided proper drainage
from  the  unit.  Note:  Do  not  attach  the  wall  mounting  bracket  into
unsupported dry wall. Make sure that the wood screws are going into
a structure that can suppport a minimum load of 150 lb.
3. Lift the air handler above the wall mounting bracket and attach the
unit to the installed bracket. Reference Figure 3-1.
4. Install the additional bottom plate for extra support for this type
mounting (see figure 3-1).
Note: The additional plate is shipped in the bottom of the shipping
carton.

3.2.1 WALL MOUNT

 Fig. 3-2 FRAME MOUNT

3.2.2 FRAME MOUNT

PROVIDED WALL

MOUNT BRACKET

WALLMOUNT BRACKET

WOOD SCREWS

SUPPORTING 2˝X4˝

STRUCTURE

WALL STRUTURE

WOOD SCREWS

WOOD SCREWS

PROVIDED WALL
MOUNT BRACKET

NOTE: MOUNTING WALL AND SUPPORTING 

STRUCTURE MUST BE ABLE TO SUPPORT A 

MINIMUM OF 150 LBS.

PROVIDED AIR HANDLER

MOUNTING BRACKET

 Fig. 3-1 WALL MOUNT

WOOD SCREWS

Section 3. Installation Instructions

3.1 Unpacking

3.2 Location

NOTE:

IN ORDER TO PREVENT

AIR LEAKAGE,THE TABS

AND SCREW HOLES

NEED TO BE SEALED

UP WHEN THEY ARE

NOT TO BE USED.

OFFSET HANGING 

BRACKET

IMPORTANT: The (8) wood screws are not provided with the unit. 
#12 x 1 ½˝ wood screws are recommended. When the unit is installed 
on a wood frame, the screws should be used to fix the unit to the 
studs.  If  they  are  not  used,  the  unit  may  fall  down  or  cause  other 
damage. See Figure 3-2 for frame mount installation.

The air handler comes with 8 clearance holes (4 on each side). These
holes are used to mount the air handler inside of a frame structure
(see Figure 3-2). When mounting in this fashion, make sure that the
wood screws are mounted from within the air handler and not from
outside the unit in order to avoid damaging the coil. If the frame does
not provide support in the front of the unit and additional support is
needed,  open  up  the  tabs  and  fix  the  unit  to  the  frame  or  other
support structure with screws. Select a solid and level site to ensure
proper installation of the frame mount. Verify that there is sufficient
space for installation and maintenance.(see Figure. 3-3)

WALL STRUCTURE

SUPPORTING

2˝X4˝ STRUCTURE

WOOD SCREWS

SUPPORTING

2˝X4˝ STRUCTURE

STUD ATTACHMENT

HOLES

THE TABS

BRACKET PLACEMENT FOR 

HANGING IN A CLOSET

(ONLY FOR 30K/36K) 

4

Содержание TMM5B0A24M21SAA

Страница 1: ...versatile units are applicable to air conditioning and heat pump applications Field installed electric resistance heaters are available All aluminum coil Blower and coil slide out easily for maintenan...

Страница 2: ...state electrical code on requirements for grounding Failure to follow this warning could result in property damage serious personal injury or death HAZARDOUS VAPORS Do not install an air handler with...

Страница 3: ...ns adhesives cleaning compounds and cement creates a corrosive condition which may cause rapid deterioration of the cabinet and internal components CAUTION SAFETY HAZARD Sharp Edge Hazard Be careful o...

Страница 4: ...the air handler above the wall mounting bracket and attach the unit to the installed bracket Reference Figure 3 1 4 Install the additional bottom plate for extra support for this type mounting see fi...

Страница 5: ...dential Winter and Summer Air Conditioning and Equipment Selection Latest editions are available from ACCA Air Conditioning Contractors of America 1513 16th Street N W Washington D C 20036 If duct sys...

Страница 6: ...ze the fan on a demand for heating or cooling Install the thermostat on an inside wall away from drafts lights or other heat sources in a location that has sufficient air circulation from other rooms...

Страница 7: ...uspension if used is secure and there are no tools or loose debris in around or on top of the unit 2 Properly insulate suction lines and fittings 3 Properly secure and isolate all refrigerant lines 4...

Страница 8: ...COMPONENT ARRANGEMENT FM NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE CAUTION ATTENTION TMM5B0A24M21SAA TMM5B0B36M31SAA Fig 4 1 8...

Страница 9: ...COMPONENT ARRANGEMENT FM NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE CAUTION ATTENTION Fig 4 2 TMM5B0B30M21SAA 9...

Страница 10: ...24 36 24 36 24 36 10 Circuit Breaker Minimum CFM MODEL 1 2 3 575 600 625 575 600 625 700 725 750 10 TMM5B0A24M21SAA TMM5B0B30M21SAA TMM5B0B36M31SAA Section 5 Heater Pressure Drop Table Use For All TMM...

Страница 11: ...n dry coil at 230V with no electric heat no filter For 24 30 and 36 sizes airflow at 208V is approximately the same as 230V because the mult tap ECM motor is a constant torque motor The torque doesn t...

Страница 12: ...ection 3 4 female pipe thread NPT Primary drain conncetion 3 4 female pipe thread NPT Front return shown Units may also be installed as bottom return See the applications section for more detail NOTE...

Страница 13: ...ww trane com www americanstandardair com The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice Tran...

Отзывы: