BAS-SVX080B-EN
9
Callout Number in
Figure
Symbio 800 Components Description
6
Status LED
7
IMC LEDs
8
Service button and LED
Note:
Pressing the Service button turns the LED on. The button has no field function. It
may be used for advanced service by Trane technical support.
9
USB service tool port for Tracer TU or Web UI at address 198.80.18.1
10
Ethernet network connection 2: supports Trane TD7 or TD12 display at 198.80.18.9
11
Ethernet network connection 1: supports TCP/IP, BACnet/IP, and Modbus TCP
communication
12
Ethernet LEDs, Ports 1 and 2 link activity
13
Micro SD card slot: support for backups (up to 10 backup files, FIFO)
14
USB 2.0 ports: support for Tracer USB LonTalk module, WiFi, LTE Modem, and USB mass
storage
15
Rotary switches
16
7–segment display
17
RS-485 communication link LEDs
Specifications
Tracer Symbio 800 conforms to the specifications shown in the following table.
Table 1. Specifications
Storage
Temperature:
-67°F to 203°F (-55°C to 95°C)
Relative humidity:
Between 5% to 95% (non-condensing)
Operating
Temperature:
-40°F to 158°F (-40°C to 70°C)
Humidity:
Between 5% to 95% (non-condensing)
Power:
Input: If the max operating temperature is 60°F or less, the current draw
for the Symbio 800 is 400mA at 24VDC, which includes up to 1000mA of
current supplied to the USB host ports.
See Symbio 800 Power Requirements for more information.
Time Clock:
On-board real time clock with battery backup
Mounting weight of controller:
Mounting surface must support 1.3 lb. (0.6 kg)
Environmental rating (enclosure):
NEMA 1, IP3x (ingress protection)
Installation:
UL 840: Category 3
Pollution:
UL 840: Degree 2
Processor
Arm A9 Cortex Dual Core
Memory
FLASH 4 GB eMMC SDRAM 1 GB DDR3
Agency Listings
•
UL916 PAZX, Open Energy Management Equipment
•
UL94-5VA Flammability
•
CE
•
FCC Part 15, Subpart B, Class B Limit
•
BTL Listed - B-BC, B-ACC See Symbio 800 BTL listing for details.