Table 12.
Ventilation override modes (continued)
Value
Settings (Factory
Default)
Description
VOM C Outdoor Air
Damper
Closed (Closed, Open)
VOM C VAV Box Relay
De-energized (De-
energized, Energized)
VOM C Ventilation
Override Relay
Energized (De-
energized, Energized)
VOM C Lock
Not Locked (Not
Locked, Locked)
VOM C has higher priority than D, and E.
VOM D Supply Fan
On (Off, On)
Factory Default Settings - Purge
VOM D Supply Fan
Speed
Max (Min, Max, Auto)
VOM D Relief Fan/
Dampers
On/Open (Off/Closed,
On/Open)
Exchanges the air in the space with fresh air.
VOM D Outdoor Air
Damper
Open (Closed, Open)
VOM D VAV Box Relay
Energized (De-
energized, Energized)
VOM D Ventilation
Override Relay
Energized (De-
energized, Energized)
VOM D Lock
Not Locked (Not
Locked, Locked)
VOM D has higher priority than E.
VOM E Supply Fan
On (Off, On)
Factory Default Settings - Purge w/ Discharge Air Pressure
Control
VOM E Supply Fan
Speed
Auto (Min, Max, Auto)
VOM E Relief Fan/
Dampers
On/Open (Off/Closed,
On/Open)
Exchanges the air in the space with fresh air while performing
duct
VOM E Outdoor Air
Damper
Open (Closed, Open)
static pressure control within a multizone application.
VOM E VAV Box Relay
Energized (De-
energized, Energized)
VOM E Ventilation
Override Relay
Energized (De-
energized, Energized)
VOM E Lock
Not Locked (Not
Locked, Locked)
VOM E has lowest priority.
Arbitration Method
Allows selection of the active source of setpoints and settings:
•
F
Fu
ullll S
So
ou
urrcce
e – Result of arbitration from external controls (For example: Tracer
®
SC+, TGP2,
3
rd
party system control).
•
L
Lo
occa
all S
So
ou
urrcce
e – Isolates unit setpoints, settings, and sensors to local wired or wireless
sources. Removes Full Sources.
•
D
De
effa
au
ulltt S
So
ou
urrcce
e – Isolates unit to TD7 Display setpoints and settings, and local sensors.
Removes Local Source and Full Sources.