50
BAS-SVX080B-EN
–
All components have been commanded OFF or CLOSED.
–
The supply fan proving logic indicates a no-flow condition has existed for 40 continuous
seconds.
•
When the user removes the unit from active Supply Fan VFD Bypass Mode at the display, all
of the following will be enforced:
–
The Supply Fan Bypass Relay will remain OFF.
–
For Multi Zone – VAV units the VAV Box Relay will be commanded OFF (de-energized) to
indicate normal airflow mode to the system, and the VAV Box Stroke Time will count
down.
–
Once the above conditions have been satisfied the user will be allowed to request Unit
Auto Mode at the display.
•
At all times when the unit is not in an active Supply Fan VFD Bypass Mode, the Supply Fan
Bypass Relay will be commanded OFF (de-energized).
Ventilation Override (if configured)
Allows modification and locking of Ventilation Override Modes.
Table 12.
Ventilation override modes
Value
Settings (Factory
Default)
Description
VOM A Supply Fan
Off (Off, On)
Factory Default Settings - Unit Off
VOM A Supply Fan
Speed
Min (Min, Max, Auto)
VOM A Relief Fan/
Dampers
Off/Closed (Off/Closed,
On/Open)
All components are commanded off and closed.
VOM A Outdoor Air
Damper
Closed (Closed, Open)
VOM A VAV Box Relay
De-energized (De-
energized, Energized)
VOM A Ventilation
Override Relay
De-energized (De-
energized, Energized)
VOM A Lock
Not Locked (Not
Locked, Locked)
VOM A has highest priority, will override B, C, D, and E.
VOM B Supply Fan
On (Off, On)
Factory Default Settings - Pressurize
VOM B Supply Fan
Speed
Max (Min, Max, Auto)
VOM B Relief Fan/
Dampers
Off/Closed (Off/Closed,
On/Open)
Over pressurizes the space to prevent air infiltration from
VOM B Outdoor Air
Damper
Open (Closed, Open)
outside the space.
VOM B VAV Box Relay
Energized (De-
energized, Energized)
VOM B Ventilation
Override Relay
Energized (De-
energized, Energized)
VOM B Lock
Not Locked (Not
Locked, Locked)
VOM B has higher priority than C, D, and E.
VOM C Supply Fan
Off (Off, On)
Factory Default Settings - Relief
VOM C Supply Fan
Speed
Min (Min, Max, Auto)
VOM C Relief Fan/
Dampers
On/Open (Off/Closed,
On/Open)
Performs an exhaust function to remove air from the space.