18
BAS-SVX080B-EN
Table 5.
24 Vdc current draw per component on a Symbio 800 controller
Component
Current withdraw
Symbio 800 controller
400mA (-40 to 60 Celsius)
WCI
50mA
New WCI (see note)
10mA
Trane BACnet Terminator
8mA
XM30
110mA
XM32
100mA
XM70 and XM90
N/A (both XM70 and XM90 and AC powered devices)
N
No
otte
e:: New WCI part numbers: X13790901030 (Field Installed Indoor), X13790941030 (Field
Installed Outdoor), X13790902030 (Service Indoor Flush), X13790903030 (Factory Indoor),
and X13790904030 (Factory Indoor Flush).
Symbio 800 DC Power Budget
Depending on the power source, Symbio 800 has a maximum current available for peripheral
devices. It is a best practice to erform a power budget if you have more than three external
devices connected through the IMC.
Using the values from
calculate the power draw for all the components connected
to the Symbio 800.
USB Port Power Requirements
The table below states the 5 Vdc power available for all four USB Ports. No single port can
support a sustained load of 500mA, or 510mA intermittent. Overloading a port , or ports may
cause the USB load switch to shut down. The USB load switch will shut down very quickly during
a direct short circuit.
Table 6. 5 Vdc current draw per component on the Symbio 800 USB ports
Component
Current withdraw
Trane Wi-Fi Module (either X13651705001 or
X13651743002)
250 mA
Trane U60 LON Adapter
110 mA
Trane USB Cellular Module (Verizon, USA)
450mA