BAS-SVX080B-EN
13
Table 3. 7-segment display: Codes and interpretation (continued)
Red/Green LED
7-segment display
Indicates...
Red
4
Booting operating system.
Flashing Red
Corner Dashes
Operating system booted. Preparing to start main program.
Green
-L
Starting main program and loading database.
Green
"Dancing dash" dashes flash one at a
time: top, middle, bottom
Normal operation.
Green
3,-,2,-,1,- (sequence repeats)
Power button was pressed and Symbio 800 is shutting down. May
take 10 or more seconds.
Green
3,2,1 (sequence repeats)
Main program shutting down due to reboot command. In most cases,
the main program will be restarted.
Green
Single digit during operation
Rotary switch was changed. The new setting of the changed switch is
displayed on the 7-segment LED for several seconds.
Flashing Red
ForCE.
We are waiting for the user to change the rotary settings from 999 in
order to force a return to factory defaults.
Flashing Red
CLEAr.
We are clearing the database and returning to factory defaults as
directed by the user.
Flashing Red
r.
We are restoring a database per a user database restore operation.
Flashing Red
donE.
The controller is done performing the requested update and needs a
manual restart.
Flashing Red
HoLd.
The main program has "crashed" too many times in the last 24 hour
period and the controller is now in a "hold" mode.
Flashing Red
rEC.
The controller is booted into recovery mode.
Flashing Red
U0.
Waiting for USB drives to mount.
Flashing Red
F0.
Unknown rotary switch setting.
Flashing Red
U12.
Searching for scfx files.
Flashing Red
F12.
No scfx files found.
Flashing Red
F13.
More than one scfx file found.
Flashing Red
U2.
Checking signature on scfx file.
Flashing Red
U21.
Decrypting scfx file.
Flashing Red
F21.
Invalid scfx file signature by trusted signer.
Flashing Red
F22.
Untrusted signer signed scfx file.
Flashing Red
F23.
No valid signature.
Flashing Red
F24.
No signature data.
Flashing Red
F25.
Invalid or unreadable key or certificate file.
Flashing Red
F26.
Invalid or unreadable input data file.
Flashing Red
F27.
Missing or invalid data in input file.
Flashing Red
F29.
Unknown signature format.
Flashing Red
F212.
Internal error.
Flashing Red
U3.
Checking software maintenance plan.
Flashing Red
F30.
Cannot mount update file. File may be corrupt.
Flashing Red
F31.
Update not allowed by SMP expiration.
Flashing Red
F32.
Internal error.
Содержание TCONT 800 Series