PART-SVN237B-EN

General Information

Initial production RTAE Chillers include 1

st

 Gen GP4 Screw 

Compressors with legacy motors (Phase Motion), external 
inductors between the drive and compressor, and (on 
some units) smaller AFD3 frames compared to second 

generation chillers. While 2

nd

 Gen GP4 Screw 

Compressors include an updated motor (Regal Beloit), no 
external inductors, and (on some units) larger AFD3 
frames.

Table 1.

GP4 classic compressor

Description

1

st

 Gen GP4 Classic Compressor

2

nd 

Gen GP4 Classic Compressor

Motor

Phase Motion

Regal Beloit

External Inductor

Yes

No

AFD3 Frame Size

Smaller on some units

Larger on Some units

With Trane's conversion to the GP4 Variable VI ratio 
(VarVI) compressor architecture, in the event of a 
compressor failure it is not possible to replace 1

st

 or 2

nd

 

Gen GP4 Classic Compressors with the new GP4 VarVi 
model. Thus, a service model GP4 VarVi Compressor was 
developed for replacement of both 1

st

 and 2

nd

 Gen GP4 

Classic Compressors. This service model compressor 
performs similarly as a classic GP4 compressor due to the 
following adaptations:

Locked VI assembly to 'high VI' configuration (same as 
GP4 Classic).

2

nd 

generation motor (Regal Beloit instead of Phase 

Motion).

Removal of external inductors (if installed).

Replacement of a 2

nd

 Gen GP4 Classic Compressor 

requires replacement of the compressor motor terminal 
box but no other adaptations to unit electrical wiring or 
AFD3 programming. Replacement of the 1

st

 Gen GP4 

Classic Compressor requires extra steps to replicate 
similar unit operation. This document outlines extra 
retrofit conversion steps in event of a failure of a 1

st

 Gen 

GP4 Classic Compressor on an RTAE Chiller:

Replacement of 1

st

 Gen GP4 Classic Compressor to 

GP4 Locked VarVI Service Compressor.

Removal of external inductors.

Re-programming of AFD3 (including special RLA 
values for some models).

Addition of common mode chokes.

Replacement of the compressor motor terminal box.

Note: Some units will lose a small portion of top end 

operational capacity due to the difference in motor 
performance and the size of the originally installed 
AFD3 on the 1

st

 Gen RTAE unit. The reduction of 

top end capacity is small, and noted later in this 
document.

Figure 1.

Replacement of 1

st

 or 2

nd

 Gen GP4 classic 

compressor to VarVi service compressor on 
RTAE

1

st

 Gen

GP4 Comp

2

nd

 Gen

GP4 Comp

New Terminal Box
A new cartridge heater
is required

GP4 VarVi

Service Comp

New Terminal Box
Remove inductor
AFD3 re-programming
Add chokes
A new cartridge heater 
is required

Содержание Stealth RTAE

Страница 1: ...stallation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipm...

Страница 2: ...t that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the a...

Страница 3: ...ions Introduction PART SVN237B EN 3 Copyright This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without written permission Trane r...

Страница 4: ...uired 6 GP4 Classic Compressor Parts List 7 Heater Information 8 Compressor Heaters 8 Removal of Output Inductors 1st Gen GP4 Classic Compressor Only 9 Adding Common Mode Chokes 1st Gen GP4 Classic Co...

Страница 5: ...eration motor Regal Beloit instead of Phase Motion Removal of external inductors if installed Replacement of a 2nd Gen GP4 Classic Compressor requires replacement of the compressor motor terminal box...

Страница 6: ...voltage range s Voltage specific replacement compressor for 360 439V or 440 528V depends on chiller rated voltage Refer to chiller nameplate to identify the rated voltage 360 439V motors are used on...

Страница 7: ...red If the unit in the field includes the sound attenuation option then the appropriate kit must be ordered for the new GP4 VarVi frame size Two parts are required for the specific compressor frame si...

Страница 8: ...d locally 6 Inline connectors With removal of the output inductor the power conductors will be need to be spliced together Polaris Electrical Connectors are recommended Catalog No IT 250 Six 6 pieces...

Страница 9: ...tor See Step 6 Figure 3 Electrical schematic with output inductor circuit1 401A 404A 28A 28A 27A 26A 25A 20A 19A 21A 1R3 U1 U2 1R3 V1 V2 1R3 W1 W2 3M1 M T1 T2 T3 BLK BLK 402A 403A 1X3 10 1B3 1 2 430A...

Страница 10: ...24B 411B 411A 424C 4B2 P 1XJ44 1 1XJ44 2 1XP44 1 1XP44 2 1X3 14 424D 1T2 U V W R1 R2 S1 S2 T1 T2 G CON 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 CON 3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 CON 7 1 2 3...

Страница 11: ...8 1M5 1R3 1B3 1T1 1F1 1F38 1F33 1F34 1T2 B B 1T11 1T12 1T13 1T10 1T14 1T15 1K15 1K6 1K3 1K2 1K8 1K5 1K4 1K9 1K13 1K12 1X4 1XJ3 1K10 1K17 1K18 1K19 1K22 Output Inductor location Output Inductor locatio...

Страница 12: ...ing 3 Way Modulating Valve UC800 Temp Sensor Expansion Tank Active ID BP Bypass Valve BP Brazed Plate Heat Exchanger ID AFD IGBT Diodes Heat Exchanger Figure 7 Insulated in line connectors Installatio...

Страница 13: ...conductors Refer to the schematic and image below With removal of the output inductor the power conductors will be need to be spliced together Polaris electrical connectors are recommended Catalog No...

Страница 14: ...y Table 8 Programming values for AFD3 drive AFD3 Parameter Name FCAT GP4 Gen Replacing GP4 VarVi Service Model Number a FA EA EB b CA BA EB b FC FB EC FD CB BB Motor Type MTPx Internal Permanent Magne...

Страница 15: ...mation is stored in the 6th and 7th digit of the model number For example the digits in bold of this model number correspond to the information in the tables above CHHSRB1A1A0 b Motor model EB is uniq...

Страница 16: ...Figure 12 Cartridge heater location Cartridge heater location Band heater can be reused Figure 13 Band heater location Band heater location Installation 16 PART SVN237B EN...

Страница 17: ...e switch location Location of high pressure switch Reuse fitting from old compressor Figure 15 Intermediate oil pressure transducer location Location of intermediate oil pressure transducer Installati...

Страница 18: ...Figure 16 Solenoid stems Leave solenoid stems capped Figure 17 Piping modifications Installation 18 PART SVN237B EN...

Страница 19: ...Figure 18 Fitting installation for suction transducer in the suction line Figure 19 Threadelet installation 1 4 inch pipe thread Installation PART SVN237B EN 19...

Страница 20: ...Figure 20 Follow standard welding procedures when welding 1 4 inch pipe thread threadelet in place Figure 21 Pressure teat and paint threadelet Installation 20 PART SVN237B EN...

Страница 21: ...Figure 22 Install existing suction transducer Installation PART SVN237B EN 21...

Страница 22: ...Notes 22 PART SVN237B EN...

Страница 23: ...Notes PART SVN237B EN 23...

Страница 24: ...re committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial a...

Отзывы: