Flow should be smooth and even, with no bubbles
once the system has stabilized.
N
No
otte
e:: Sight glass moisture indicator may show
caution or wet at startup. May need up to 12
hours of operation for system to reach
equilibrium and correctly show moisture.
Normal startup will occur provided that Tracer
™
Summit is not controlling the module outputs or the
generic BAS is not keeping the unit off. To prevent
Tracer Summit from affecting unit operation, remove
Tracer wiring and make required changes to setpoint
and sensor sources.
Operating and Programming Instructions
See Self-Contained Programming Guide, PKG-SVP01*-
EN, for available unit operating setpoints and
instructions. A copy ships with each unit. For units with
VFD option, see installer guide that ships with each
VFD.
Startup Log
Unit:
Unit Location:
Unit Voltage
Evaporator
Evaporator fan motor horsepower:
Evaporator fan motor amps:
Evaporator fan rpm (actual):
Evaporator system static (from test and
balance report or actual readings)
Supply duct static:
Return duct static:
Evaporator system cfm (test and balance
sheet or actual tested):
Evaporator Air Conditioners (with all compressor operating)
Entering
Leaving
Dry-bulb °F:
Dry-bulb °F:
Wet-bulb °F:
Wet-bulb °F:
Water-Cooled Units
Circuit A
Circuit B
Circuit C
Circuit D
Entering water temp °F
Leaving water temp °F
Entering water
pressure psig
Leaving water
pressure psig