Entering air temperature
______
0
46
Heating mode:
Water side heat exchanger (condenser)
Min temperature (°C)
Max temperature (°C)
Entering water temperature (startup)
10
50
Leaving water temperature (running)
30
55
Air side heat exchanger (evaporator)
Min temperature (°C)
Max temperature (°C)
Entering air temperature
-10
21
Partial Heat Recovery mode:
Water side heat exchanger (evaporator)
Min temperature (°C)
Max temperature (°C)
Entering water temperature (startup)
-
45
Leaving water temperature (running)
5
18
Partial heat recovery heat exchanger (Hot water)
Min temperature (°C)
Max temperature (°C)
Entering hot water temperature (startup)
10
50
Entering hot water temperature (running)
25
60
Note:
altitude up to 1000 m above sea level.
NOTICE - Anti-freeze Protection!
Failure to follow the anti-freeze protection of the manual when unit operates in an ambient temperature of