16
RTAF-SVX001K-EN
Dimensions and Weights
Service Clearance
Notes:
1. Area above unit required for operation, maintenance,
panel access and airflow.
NO OBSTRUCTIONS ABOVE UNIT
2. For installations with obstructions or multiple units,
see Close Spacing and Restricted Airflow Bulletin RLC-
PRB037*-EN.
3. Clearance of 78” (1981 mm) on the side of the unit is
required for coil replacement. If sufficient clearance is
not available on this side of the unit, coil replacement
should be performed through top of unit.
4. A full 36” (914 mm) clearance is required in front of the
control panels. Must be measured from front of panel,
not end of unit base.
5. Clearances shown are sufficient for tube pull.
Unit Dimensions
See unit submittals for specific unit dimensions and water
connection locations.
Figure 4.
RTAF service clearances
NO OBSTRUCTIONS ABOVE UNIT
Unit sizes 115 to 270 tons:
Unit sizes 280 to 520 tons:
24”
(610 mm)
36”
(914mm)
See note 4
36”
(914mm)
78”
(1941mm)
See note 3
36”
(914mm)
See note 4
36”
(914mm)
See note 4
78”
(1941mm)
See note 3
36”
(914mm)
Ckt 1
Panel