Installation
RT-SVX19A-E4
18
Table 8 - TKD/TKH Pressure drop through accessories
Filter
Filter
Economizer
Economizer
Electric
Hot water coil
Airflow
EU2/G2
EU4/G4
100%
outside air
100%
return air
heater
Downflow only
TKD/TKH 155
6800
13
27
8
6
7
33
7650
16
30
10
7
9
40
8500
19
34
12
8
11
48
9350
22
37
14
9
13
56
10200
26
40
16
10
16
65
TKD/TKH 175
7870
17
30
10
7
10
42
8860
21
34
12
8
13
51
9850
25
38
15
9
16
61
10840
30
43
17
11
19
72
11830
35
47
20
12
23
83
TKD 200
8970
12
26
29
6
13
33
10090
15
30
37
8
17
40
11210
19
33
45
9
21
48
12330
23
37
55
11
25
56
13450
27
41
65
13
30
65
TKH 200
8970
11
23
33
6
13
-
10090
14
26
41
8
17
-
11210
17
29
51
9
21
-
12330
20
33
61
11
25
-
13450
23
36
72
13
30
-
TKD 250
11280
18
32
46
10
20
49
12690
24
36
58
12
25
59
14100
29
41
71
14
32
71
15510
36
46
86
17
38
82
16920
43
51
102
19
46
95
TKH 250
11280
17
30
52
10
19
-
12690
21
34
65
12
24
-
14100
26
38
80
14
29
-
15510
31
43
96
17
35
-
16920
36
47
114
19
42
-