SS-SVX11K-EN
125
Suction Line Filter
Figure 87.
Suction line filter installation: 20 to 60 Ton
units
Minimum 16" for CSHD straight
unobstructed piping between the
Suction Filter/Drier and the Tee
16
“ min
Figure 88.
Suction line filter installation: 80 to120 Ton
units
25” min
Minimum 25” for CSHN straight
unobstructed piping between the
Suction Filter/Drier and the Tee
Fuse Replacement Data
Table 45.
Fuse replacement selection
Fuse Description
Unit Size
Unit Voltage
Fuse Type
Fuse Size
Condenser Fan Fuse
(1F1-1F3 on 20 - 30 Ton)
(1F1-1F6 on 40 - 60 Ton)
20-60 Ton
200/230
460/575
380/415
Class RK5
25 Amp
15 Amp
Control CKT Fuse 1F7
20 - 30
40 - 60
All
Class CC FNQ
R
3.2
6.25
Compressor Protector Fuse
1F8 on 20 - 60 ton
1F9 on 40 - 60 ton
20 -60 Ton
All
ABC - 6
6 Amp
Control Circuit Fuse 1F1
80 - 120
All
Class CC FNQ-R
10 Amp
Compressor Protector Fuse 1F2 - 1F3
80 - 120
All
ABC - 6
6 AMP
Condenser Fan Fuse
1F4-1F9
80
200 V
230 V
460 V
575 V
Class RK5
30 Amp
25 Amp
20 Amp
15 Amp
Condenser Fan Fuse
1F4-1F9
100 - 120
200 / 230 V
460 V
575 V
Class RK5
35 Amp
25 Amp
20 Amp
Transformer Fuse
1F12 - 1F13
All
200 V
230 V
460 V
FNQ-R
6 Amp
5 Amp
4 Amp