Oil charge
Attention: The oil quantity necessary
for the split system has also to be
adjusted according to the diameter
and the length of the refrigerant
piping work.
Important note:
These operations
have to be performed by a specialist
according to the rules of the art. The
results have to be written on a start
up record by the Trane engineer or
the client's specialist who has
performed this start up. The quantiy
of refrigerant and oil added are at
the client's charges.
Refrigerant charge (all split
system types)
After system pressure and vacuum
testing, fill up unit with refrigerant as
per indicated in table Refrigerant
Charge. The refrigerant complement
will be charged according to the
diameter and the length of the
refrigerant piping work up to obtain
the correct superheat and subcooling
temperatures.
Refrigerant Charge
Size
190
260
300
350
400
450
500
600
700
800
Circuit A
(kg)
9
10
13
9
13
13
10
13
24
24
Circuit B
(kg)
-
-
-
6
6
6
10
13
24
24