5

RAU-SVX01B-E4

Refrigerant lines

Calculating and fixing the capacity
of refrigerant lines is necessary to
assure the oil return to the
compressor, avoid refrigerant phase
changes and limit pressure drop.

Liquid lines

Calculate capacity of liquid line, as
per the following criteria.
1. Maximum load operating

conditions.

2. To avoid any evaporation risk:
-

Consider the vertical risers

-

Maximum pressure drop must
not exceed 1 to 2°C

3. Liquid circulation speed in a 0.5

to 2m/s range.

Discharge lines

Discharge lines should be calculated
to obtain the gas displacement
speed in horizontal and vertical lines
required to drive compressor oil.
Determine diameter of discharge
lines as per the following criteria.
1. Speed above 2,5 m/s horizontally.

(Consider minimum speed at
minimum load)

2. Speed above 5,0 m/s vertically

(Vertical risers, consider speed at
minimum load)

3. Maximum speed 20 m/s.
4. Horizontal pipe run must be

pitched of 1cm/m in the same
direction as the refrigerant
circulation

5. An oil trap is necessary for

vertical risers greater than 3m.
For major elevations add an
intermediate oil trap every 5m.

6. Maximum pressure drop between

20 to 50 kPa

7. Install a filter drier adapted to

refrigerant capacity.

Insulation of refrigerant lines

Insulate refrigerant lines from
building itself to avoid transmission
to building structure of vibrations
normally caused by pipework.
Also avoid bypassing the unit's
damping system by fixing the
refrigerant lines or the electrical
ducts very rigidly.Vibrations may
propagate into building structure
through rigidly fixed refrigerant
lines.

Pressure tests. Leak detection

During operations, take the following
precaution:
1. Neither oxygen nor acethylene

should be used instead of
refrigerant and nitrogen to detect
leaks, otherwise a violent
explosion may occur.

2. Always use valves and

manometers to check the test
pressure in system. Excessive
pressure may either cause pipes
to rupture, damage unit, or cause
an explosion, causing possible
physical injury.

Carry out liquid line and hot gas line
pressure tests in accordance with
current standards.
The test pressures applied to the
liquid line and the hot gas suction
line must comply with the country's
standards.

Caution:

Do not go more than 0.7

bar above the high pressure switch
setpoint.

Introduce enough refrigerant into
circuit for 85 to 100 kPa pressure,
pump-injecting dry nitrogen, and
raise pressure to 100 kPa. Search for
possible leaks using detector. This
operation should be carried out with
great care throughout the system.
If leaks are detected, reduce system
pressure, and repair defective
component. Repeat test process, to
check that the repair can withstand
rated pressure.

Caution:

Unit is delivered with a

refrigerant holding charge and
isolating valves.

Содержание RAU-SVX01B-E4

Страница 1: ...Installation Operation Maintenance RAU Air Cooled Condensing Unit Sizes 190 260 300 350 400 450 500 600 700 800 RAU SVX01B E4 To be used with the manual of SMM module Reference L80 IM 022 E...

Страница 2: ...st to the last carrier of the goods within 72 hours of delivery Notify the local Sales Office at the same time The unit should be totally inspected within 7 days of delivery If any concealed damage is...

Страница 3: ...acteristics 7 Electrical connections 10 General start up Preparation 11 Start up 11 Operation Control and unit operation 13 Seasonal shutdown and start up 13 Weekly start up and week end shutdown 13 M...

Страница 4: ...does not allow to install spring isolators Clearance Respect recommended clearance around the unit to allow maintenance operation to take place without obstruction and recommended clearance around co...

Страница 5: ...ing itself to avoid transmission to building structure of vibrations normally caused by pipework Also avoid bypassing the unit s damping system by fixing the refrigerant lines or the electrical ducts...

Страница 6: ...alist who has performed this start up The quantiy of refrigerant and oil added are at the client s charges Refrigerant charge all split system types After system pressure and vacuum testing fill up un...

Страница 7: ...e size mm 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height mm 1219 1219 1219 1219 1219 1219 1219 1219 1219 1219...

Страница 8: ...ate Fin Tube size mm 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height mm 1219 1219 1219 1219 1219 1219 1219 1219...

Страница 9: ...9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height mm 1219 1219 1219 1219 1219 1219 1219 1219 1219 1219 Length mm 2743...

Страница 10: ...s the transformer If the transformer is not ordered it is necessary to foresee the power supply of the electronic module separately Warranty reserves will be formulated if a transformer not supplied b...

Страница 11: ...ing the isolators located under the rails supporting the compressor Put the plexiglass supplied by Trane in front of the power terminal Ensure all refrigerant valves are in service positions Ensure th...

Страница 12: ...C With 407c it should be 20 to 23 C Final check When the unit is operating correctly Check that the unit is clean and clear of any debris tools etc All valves are in operating position Close control...

Страница 13: ...g pressures temperatures amperages and voltage Check operation of machines compare conditions of operation against original commissioning data Push button O of the module Insure that all safeties are...

Страница 14: ...ck operation of all safety devices Inspect contacts tighten terminals Megger the motor compressor windings Record operating pressures temperatures amperages and voltage Carry out leak test Check confi...

Страница 15: ...dryer and sight glass presence Check oil traps presence on discharge line if there vertical risers 3m Check pitch for horizontal lines 1cm m Check refrigerant presence Electrical equipment Check direc...

Страница 16: ...circuit open Compressor sticking damaged or sticking components Discharge pressure too high Discharge pressure too high a Voltage too low b Cooling demand too high or condensing temperature too high N...

Страница 17: ...neven liquid flow b Expansion valve locked in open position Not enough refrigerant Drier filter clogged Superheat not properly adjusted Presence of uncondensable liquids in system or excess refrigeran...

Страница 18: ...too low Excessive pressure drop through filter drier Refrigerant does not flow through thermostatic expansion valve Loss of power Superheat too low Excess cooling demand on evaporator a Expansion valv...

Страница 19: ...15 8 4 1 17 3 4 1 4 C 16 2 4 4 18 2 4 4 20 4 4 4 22 8 4 4 13 0 4 4 14 1 4 4 15 4 4 4 16 8 4 4 2 C 16 6 4 7 18 6 4 7 20 8 4 7 23 2 4 7 12 8 4 7 13 9 4 7 15 1 4 7 16 5 4 7 18 0 4 7 0 C 17 0 5 0 19 0 5...

Страница 20: ...3 6 8 29 1 6 8 19 3 6 8 21 4 6 8 23 8 6 8 26 3 6 8 29 0 6 8 Saturated suction temperature Table 5 RAU 700 R22 RAU 800 R22 Outdoor AmbientTemperature C 25 C 30 C 35 C 40 C 45 C 25 C 30 C 35 C 40 C 45...

Страница 21: ...1 2 2 6 C 10 1 2 3 10 9 2 3 11 9 2 3 13 4 2 3 15 1 2 3 9 9 2 3 10 8 2 3 11 7 2 3 12 6 2 3 13 7 2 3 4 C 9 9 2 5 10 7 2 5 12 0 2 5 13 6 2 5 15 3 2 5 9 8 2 5 10 5 2 5 11 4 2 5 12 4 2 5 13 4 2 5 2 C 9 8 2...

Страница 22: ...12 3 4 2 13 9 4 2 15 6 4 2 17 4 4 2 10 9 4 2 12 3 4 2 13 8 4 2 15 5 4 2 17 3 4 2 Saturated suction temperature Table 10 RAU 700 R134a RAU 800 R134a Outdoor AmbientTemperature C 25 C 30 C 35 C 40 C 45...

Страница 23: ...7 1 9 22 9 29 6 4 4 1 3 7 6 19 0 48 2 43 2 44 0 85 5 83 0 2 0 21 7 28 4 4 5 0 6 7 0 20 0 50 3 45 4 45 0 86 6 84 2 2 1 20 5 27 2 4 6 0 0 6 3 21 0 52 3 47 5 46 0 87 6 85 4 2 2 19 4 26 1 4 7 0 6 5 7 22...

Страница 24: ...15 1 3 7 16 6 3 7 18 2 3 7 4 C 16 4 4 0 18 6 4 0 21 0 4 0 23 6 4 0 26 5 4 0 12 3 4 0 13 4 4 0 14 7 4 0 16 1 4 0 17 7 4 0 2 C 16 8 4 3 19 0 4 3 21 4 4 3 24 0 4 3 27 0 4 3 12 1 4 3 13 2 4 3 14 4 4 3 15...

Страница 25: ...6 6 4 30 6 6 4 19 7 6 4 22 0 6 4 24 6 6 4 27 4 6 4 30 4 6 4 DewTemperature At Evaporating Pressure Table 16 RAU 700 R407C RAU 800 R407C Outdoor AmbientTemperature C 25 C 30 C 35 C 40 C 45 C 25 C 30 C...

Страница 26: ...control validation B08 Auxiliary set point validation B09 Current date display B091 Day B092 Month B093 Year B10 Current time display B101 Hours B102 Minutes B103 Seconds B11 Set this parameter to 0...

Страница 27: ...27 RAU SVX01B E4 Notes...

Страница 28: ...aximum operating life of your equipment We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty Training The eq...

Отзывы: