4
RAU-SVX01B-E4
Installation
For minimum clearance, consult the
certified submittals, which are
available on request from your Trane
Agency.
Unit nameplate
The unit nameplate gives the
complete model reference numbers.
The unit power rating is shown, and
power supplies should not deviate
by more than 5 % from the rated
power.
Compressor motor amperage is
shown in box I.MAX.
The customer’s electrical installation
must be able to withstand this
current.
Installation instructions
Foundations
No special foundations are required,
provided the supporting surface is
flat and level, and can withstand the
weight or the unit.
Anti-vibration rubber pads
They are supplied as standard with
the machine, and should be placed
between the supporting floor and
the unit to attenuate vibrations.
- 4 pads for the sizes 190 to 300
- 6 pads for the sizes 350 to 800
- Trane does not allow to install
spring isolators.
Clearance
Respect recommended clearance
around the unit to allow
maintenance operation to take place
without obstruction and
recommended clearance around
condenser.
Caution:
Unit operation is function of
the air temperature. Any recycling of
the air fed out by the fans will
increase the air intake temperature
over the condenser fins and can
result in high pressure cut-out.
In this case the standard operating
conditions are modified.
Operation of the unit may be
affected by an increase in air
temperature on the condenser.
When the units are positioned in a
windy area, avoid all the risks of air-
cooled recycling.
See submittals
Handling - Figure 2
Note:
The plates welded at the end of the
bases must not be used for
handling.
Figure 2
Dimensions of recommended slings and swing-bar:
RAU
190
260
300
350
400
450
500
600
700
800
A (mm)
1500
1500
1500
1500
1500
1500
2400
2400
2300
2300
B (mm)
1800
1800
1800
1800
1800
1800
1800
1800
2200
2200
Weight - crated
(kg)
555
625
691
869
959
985
1123
1251
1695
1754
A
B