RAU-SVX01B-E4

Operating parameters statement:

- Switch on main power supply

switch.

- Start-up the unit pushing button

”I” of control module. The green
LED must be lit, the SMM control
module must be in”cooling mode”.

- After unit start up, leave  in

operation for at least 15 minutes,
to insure pressures are stabilized.

Then check:
- voltage.
- compressors and fan-motors

currents.

- suction temperature and pressure.
- ambient  air temperature.
- blowing air temperature.
- discharge pressure and

temperature.

- liquid refrigerant temperature and

pressure.

- operating parameters:
- superheat: difference between

suction temperature and dew
point temperature. Normal
superheat must be within 5°C and
10°C.

- sub-cooling: difference between

liquid temperature and bubble
point temperature. Normal sub-
cooling on standard unit with R22
or 134a should be 5 to 10°C, and  2
to 5°C with 407c.

- difference between dew point

temperature in high pressure and
condenser air inlet temperature.
Normal value on standard unit
with R22 or 134a and all the fans
operating should be 15 to 18°C.
With 407c, it should be 20 to 23°C.

Final check:

When the unit is operating correctly:
-  Check that the unit is clean and

clear of any debris, tools, etc…

- All valves are in operating

position.

- Close control and starter panel

doors and check panels fixation.

Caution

- For the warranty to apply, any

start-up carried out directly by the
customer must be recorded in a
detailed report, which must be sent
as soon as possible to the nearest
Trane office.

- Do not start-up a motor whose

insulation resistance is less than
2 meghoms.

- Phase imbalance should not be

greater than 2%.

- The voltage supplied to motors

should be within 5% of the rated
voltage on the compressor
nameplate.

- Excessive emulsion of the oil in

the compressor shows that
refrigerant is present in the oil and
the result will be that compressor
is not lubricated enough. Shut
down compressor and consult
Trane technician.

- Excess oil in compressor can

damage the compressor. Before
adding oil, consult Trane
technician. Use only Trane products
recommended.

- The compressors must operate in

a single direction of rotation. If
refrigerant high pressure remains
stable in the 30 seconds after
compressor start-up, immediately
shut down unit and check the
direction of rotation using
phasemeter.

Содержание RAU-SVX01B-E4

Страница 1: ...Installation Operation Maintenance RAU Air Cooled Condensing Unit Sizes 190 260 300 350 400 450 500 600 700 800 RAU SVX01B E4 To be used with the manual of SMM module Reference L80 IM 022 E...

Страница 2: ...st to the last carrier of the goods within 72 hours of delivery Notify the local Sales Office at the same time The unit should be totally inspected within 7 days of delivery If any concealed damage is...

Страница 3: ...acteristics 7 Electrical connections 10 General start up Preparation 11 Start up 11 Operation Control and unit operation 13 Seasonal shutdown and start up 13 Weekly start up and week end shutdown 13 M...

Страница 4: ...does not allow to install spring isolators Clearance Respect recommended clearance around the unit to allow maintenance operation to take place without obstruction and recommended clearance around co...

Страница 5: ...ing itself to avoid transmission to building structure of vibrations normally caused by pipework Also avoid bypassing the unit s damping system by fixing the refrigerant lines or the electrical ducts...

Страница 6: ...alist who has performed this start up The quantiy of refrigerant and oil added are at the client s charges Refrigerant charge all split system types After system pressure and vacuum testing fill up un...

Страница 7: ...e size mm 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height mm 1219 1219 1219 1219 1219 1219 1219 1219 1219 1219...

Страница 8: ...ate Fin Tube size mm 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height mm 1219 1219 1219 1219 1219 1219 1219 1219...

Страница 9: ...9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height mm 1219 1219 1219 1219 1219 1219 1219 1219 1219 1219 Length mm 2743...

Страница 10: ...s the transformer If the transformer is not ordered it is necessary to foresee the power supply of the electronic module separately Warranty reserves will be formulated if a transformer not supplied b...

Страница 11: ...ing the isolators located under the rails supporting the compressor Put the plexiglass supplied by Trane in front of the power terminal Ensure all refrigerant valves are in service positions Ensure th...

Страница 12: ...C With 407c it should be 20 to 23 C Final check When the unit is operating correctly Check that the unit is clean and clear of any debris tools etc All valves are in operating position Close control...

Страница 13: ...g pressures temperatures amperages and voltage Check operation of machines compare conditions of operation against original commissioning data Push button O of the module Insure that all safeties are...

Страница 14: ...ck operation of all safety devices Inspect contacts tighten terminals Megger the motor compressor windings Record operating pressures temperatures amperages and voltage Carry out leak test Check confi...

Страница 15: ...dryer and sight glass presence Check oil traps presence on discharge line if there vertical risers 3m Check pitch for horizontal lines 1cm m Check refrigerant presence Electrical equipment Check direc...

Страница 16: ...circuit open Compressor sticking damaged or sticking components Discharge pressure too high Discharge pressure too high a Voltage too low b Cooling demand too high or condensing temperature too high N...

Страница 17: ...neven liquid flow b Expansion valve locked in open position Not enough refrigerant Drier filter clogged Superheat not properly adjusted Presence of uncondensable liquids in system or excess refrigeran...

Страница 18: ...too low Excessive pressure drop through filter drier Refrigerant does not flow through thermostatic expansion valve Loss of power Superheat too low Excess cooling demand on evaporator a Expansion valv...

Страница 19: ...15 8 4 1 17 3 4 1 4 C 16 2 4 4 18 2 4 4 20 4 4 4 22 8 4 4 13 0 4 4 14 1 4 4 15 4 4 4 16 8 4 4 2 C 16 6 4 7 18 6 4 7 20 8 4 7 23 2 4 7 12 8 4 7 13 9 4 7 15 1 4 7 16 5 4 7 18 0 4 7 0 C 17 0 5 0 19 0 5...

Страница 20: ...3 6 8 29 1 6 8 19 3 6 8 21 4 6 8 23 8 6 8 26 3 6 8 29 0 6 8 Saturated suction temperature Table 5 RAU 700 R22 RAU 800 R22 Outdoor AmbientTemperature C 25 C 30 C 35 C 40 C 45 C 25 C 30 C 35 C 40 C 45...

Страница 21: ...1 2 2 6 C 10 1 2 3 10 9 2 3 11 9 2 3 13 4 2 3 15 1 2 3 9 9 2 3 10 8 2 3 11 7 2 3 12 6 2 3 13 7 2 3 4 C 9 9 2 5 10 7 2 5 12 0 2 5 13 6 2 5 15 3 2 5 9 8 2 5 10 5 2 5 11 4 2 5 12 4 2 5 13 4 2 5 2 C 9 8 2...

Страница 22: ...12 3 4 2 13 9 4 2 15 6 4 2 17 4 4 2 10 9 4 2 12 3 4 2 13 8 4 2 15 5 4 2 17 3 4 2 Saturated suction temperature Table 10 RAU 700 R134a RAU 800 R134a Outdoor AmbientTemperature C 25 C 30 C 35 C 40 C 45...

Страница 23: ...7 1 9 22 9 29 6 4 4 1 3 7 6 19 0 48 2 43 2 44 0 85 5 83 0 2 0 21 7 28 4 4 5 0 6 7 0 20 0 50 3 45 4 45 0 86 6 84 2 2 1 20 5 27 2 4 6 0 0 6 3 21 0 52 3 47 5 46 0 87 6 85 4 2 2 19 4 26 1 4 7 0 6 5 7 22...

Страница 24: ...15 1 3 7 16 6 3 7 18 2 3 7 4 C 16 4 4 0 18 6 4 0 21 0 4 0 23 6 4 0 26 5 4 0 12 3 4 0 13 4 4 0 14 7 4 0 16 1 4 0 17 7 4 0 2 C 16 8 4 3 19 0 4 3 21 4 4 3 24 0 4 3 27 0 4 3 12 1 4 3 13 2 4 3 14 4 4 3 15...

Страница 25: ...6 6 4 30 6 6 4 19 7 6 4 22 0 6 4 24 6 6 4 27 4 6 4 30 4 6 4 DewTemperature At Evaporating Pressure Table 16 RAU 700 R407C RAU 800 R407C Outdoor AmbientTemperature C 25 C 30 C 35 C 40 C 45 C 25 C 30 C...

Страница 26: ...control validation B08 Auxiliary set point validation B09 Current date display B091 Day B092 Month B093 Year B10 Current time display B101 Hours B102 Minutes B103 Seconds B11 Set this parameter to 0...

Страница 27: ...27 RAU SVX01B E4 Notes...

Страница 28: ...aximum operating life of your equipment We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty Training The eq...

Отзывы: