Trane Purifier Plus Purge Скачать руководство пользователя страница 7

PRG-IOM-3E

7

Installation

Initial Installation

The mounting location of the Purifier Plus™ canister is determined by:

1. The style of chiller
2. Chiller options such as free-cooling, hot gas bypass, etc.
3. Service access to the chiller and canister

It is recommended that it be securely mounted to the chiller, off the floor in a 
dry, clean location. See Figure 2 for possible mounting locations on a CVHE-
style chiller.

1.  Mount the canister in the holding bracket. The bracket has holes in both 

the bottom and back plates for mounting directly to chiller leg (Figure 2, 
Option 3). V-Brackets are included in the kit for mounting to the curved 
surface of the condenser (Figure 2, Option 1 or 2). See Figure 6 for 
dimensions.

2. Install 3/8” OD copper tube from the purge exhaust to the canister inlet. 

(The inlet is in the center of the tank.) Install 3/8” OD copper tube from 
the canister outlet to the chiller vent line. (See Figure 3).

3. Insure there are no restrictions in the exhaust line. If any valves are 

included in the line, they must be fully open during use.

4. Install or modify the Change Purifier Plus Canister label (Figure 4) on the 

Purifier Purge near the minute timer. Add the applicable value from Table 
1 to the current value on the purge minute timer. Record this number on 
line A. Add three years to the installation date and record on line B.

5. Record the requested information on the canister nameplate. (See Figure 

5), including refrigerant type in appropriate check box.

Do not pressurize from an external 

source. Pressurizing tank from an 

external source could cause tank 

to rupture, resulting in death or 

serious injury.

WARNING

!

Before installation, verify the 

refrigerant type marked on the 

Purifier Plus canister is the same 

as the refrigerant in the chiller. DO 

NOT CONTAMINATE THE 

CANISTER WITH THE WRONG 

REFRIGERANT.

Caution:

!

The refrigerant must be evacuated 

from the chiller before welding of 

any kind is done to the condenser 

shell.

Caution:

!

Condenser

Evaporator

Option # 1
Mount on top 
od condenser.

Option # 2
Mount on side of 
condenser.

Option # 3
Mounted to 
condenser 
leg.

Figure 2 — Recommended Purifier Plus Mounting 
Locations

Figure 3 — Purifier Plus Connection

Содержание Purifier Plus Purge

Страница 1: ...PRG IOM 3E Installation Operation Maintenance Purifier Plus Purge Emission Collection Canister...

Страница 2: ...on 3 Model Number Description 3 Warnings and Cautions 4 Literature History 4 About this Manual 5 Receiving 5 Installation 7 Tank Replacement 9 Return Instructions 10 Maintenance 11 Specifications 11 D...

Страница 3: ...4 Development Sequence A First Development Digit 5 6 Future Use Digit 7 Tank Origin 0 Trane 1 Out source Digit 8 Tank Type N New R Regenerated Digit 9 Refrigerant 1 R11 2 R123 3 R113 4 Generic R11 R1...

Страница 4: ...Manual revised to include Updated canister drawing PRG IOM 3D October 1998 Manual revised to include Deletion of Hazardous shipping form information Added Pressurized Tank Warning PRG IOM 3E October...

Страница 5: ...ges Use with other purges may result in a potential safety hazard and or damage to the purge due to partial restriction of the purge exhaust Receiving Upon receipt of the unit inspect the shipping car...

Страница 6: ...ts 3 8 OD refrigeration grade copper tubing Length determined by location of canister 4 Bolts Use when canister is bolted directly to chiller such as Option 3 in Figure 2 Figure 1 Purifier Plus Canist...

Страница 7: ...valves are included in the line they must be fully open during use 4 Install or modify the Change Purifier Plus Canister label Figure 4 on the Purifier Purge near the minute timer Add the applicable...

Страница 8: ...pump out timer value at installation plus appropriate value from Table 1 B Installation date plus 3 years Figure 5 Typical Unit Nameplate Order No Example Model No PRPA000N2A0 Serial No L93C02684 For...

Страница 9: ...the temperature and pressure of the carbon At typical equipment room temperatures the Purifier Plus canister will hold approxi mately 12 lbs of refrigerant If the current tank weight is any more than...

Страница 10: ...onfirm the items listed under replacement canister were received 2 Document It Record all information on the data sheet enclosed in this IOM and or on tank labels and return the completed sheet with t...

Страница 11: ...ize Including bracket 21 H X 13 W X 14 L Connection sizes Inlet 3 8 Male flare Outlet 3 8 Male flare Temperature Range Operating 40 to 120 F Shipping and Storage 40 to 150 F DO NOT PAINT THE TANK The...

Страница 12: ...Empty Weight of Cylinder from sticker on bottom of tank Refrigerant type Chiller Model Number 1st 12 digits Chiller Serial Number Chiller Sales Order Number Tank Order Number or N A From Nameplate Tan...

Страница 13: ...SV CAP PP PRG IOM 3E 1001 Supersedes PRG IOM 3D Stocking Location La Crosse The Trane Company Aftermarket Business Unit 3600 Pammel Creek Road La Crosse WI 54601 www trane com An American Standard Com...

Отзывы: