4

PRGD-SVX01F-EN

EarthWise Purge System Nameplate . . . . . . . 5

EarthWise Purge System Model
Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Purge System Overview . . . . . . . . . . . . . . . . . . . . 7

General Information . . . . . . . . . . . . . . . . . . . . . . 7

Reference Sources. . . . . . . . . . . . . . . . . . . . . . . . 7

How a Purge System Works . . . . . . . . . . . . . . . 7

Refrigeration Circuit Subsystem. . . . . . . . 8
Purge Tank Subsystem . . . . . . . . . . . . . . . 11
Pump-out Subsystem . . . . . . . . . . . . . . . . 11
Carbon Tank and Regeneration
Subsystem . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Tracer AdaptiView Control
Subsystem . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Sequence of Operations . . . . . . . . . . . . . . . . . . . 13

Purge Operating Modes . . . . . . . . . . . . . . . . . . 13

Adaptive Mode . . . . . . . . . . . . . . . . . . . . . . 13
Adaptive Mode Process—Chiller
Compressor On . . . . . . . . . . . . . . . . . . . . . . 13
Adaptive Mode Procedure—Chiller
Compressor Off . . . . . . . . . . . . . . . . . . . . . . 14

Typical Purge Refrigeration Circuit
Operating Cycle . . . . . . . . . . . . . . . . . . . . . . . . . 16

Air Removal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Pump-out Operating Sequence . . . . . . . . . . . 18

Non-condensable Pump-out
Algorithm . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Non-condensable Pump-out
cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Establishing a Daily Pump-out Limit . . . . . . . 20

Carbon Tank and Regeneration
Subsystem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Carbon Regeneration Algorithm. . . . . . . 21
Carbon Tank Regeneration
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Operator Interface . . . . . . . . . . . . . . . . . . . . . . . . . 23

Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Log Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Purge Operating Modes . . . . . . . . . . . . . . 23

Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Purge Settings . . . . . . . . . . . . . . . . . . . . . . . 24
Manual Control Settings . . . . . . . . . . . . . . 24

Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Weekly Maintenance. . . . . . . . . . . . . . . . . . . . . 25

Semi-Annual Maintenance . . . . . . . . . . . . . . . 25

Annual Maintenance . . . . . . . . . . . . . . . . . . . . . 25

Replacing the Filter-Drier Assembly . . . . . . . 25

Inspecting the Moisture Indicator . . . . . . . . . 26

Maintaining the Moisture-Indicating
Sight Glass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Removing Air After Servicing the
Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Carbon Regeneration Temperature
Diagnostic Procedure . . . . . . . . . . . . . . . . . . . . 30

Purge Refrigeration Circuit Diagnostic
Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Taking Surface Temperature
Measurements. . . . . . . . . . . . . . . . . . . . . . . 30

Determining the Refrigerant Charge
Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Determining Proper Expansion Valve
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Determining Correct Vapor Pick-up
and Liquid Return Line Connection
Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Using the Service Functions . . . . . . . . . . 31
Purge Regen Cycle . . . . . . . . . . . . . . . . . . . 31
Purge Exhaust Circuit Test . . . . . . . . . . . . 31
Exhaust Circuit Pressure Check. . . . . . . . 32
Exhaust Circuit Vacuum Check . . . . . . . . 32

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Schematic Wiring Diagram . . . . . . . . . . . . . . . . 34

EarthWise Purge System with Tracer
AdaptiView Controls . . . . . . . . . . . . . . . . . . . . . 34

Table of Contents

Содержание PRGD series

Страница 1: ...raining Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment July 2017 P PR RG GD D S SV VX X0 01 1F F E EN N EarthWise Purge System with Tracer AdaptiView Control for Water Cooled CenTraVac Chi...

Страница 2: ... jo ob b b be ei in ng g u un nd de er rt ta ak ke en n c co ou ul ld d r re es su ul lt t i in n d de ea at th h o or r s se er ri io ou us s i in nj ju ur ry y T Te ec ch hn ni ic ci ia an ns s i in n o or rd de er r t to o p pr ro ot te ec ct t t th he em ms se el lv ve es s f fr ro om m p po ot te en nt ti ia al l e el le ec ct tr ri ic ca al l m me ec ch ha an ni ic ca al l a an nd d c ch he ...

Страница 3: ...es ss su ur re e F Fa ai il lu ur re e t to o f fo ol ll lo ow w i in ns st tr ru uc ct ti io on ns s b be el lo ow w c co ou ul ld d r re es su ul lt t i in n a an n e ex xp pl lo os si io on n w wh hi ic ch h c co ou ul ld d r re es su ul lt t i in n d de ea at th h o or r s se er ri io ou us s i in nj ju ur ry y o or r e eq qu ui ip pm me en nt t d da am ma ag ge e S Sy ys st te em m c co on nt...

Страница 4: ...ce 21 Operator Interface 23 Reports 23 Log Sheet 23 Purge Operating Modes 23 Settings 24 Purge Settings 24 Manual Control Settings 24 Alarms 24 Maintenance 25 Weekly Maintenance 25 Semi Annual Maintenance 25 Annual Maintenance 25 Replacing the Filter Drier Assembly 25 Inspecting the Moisture Indicator 26 Maintaining the Moisture Indicating Sight Glass 27 Removing Air After Servicing the Chiller 27...

Страница 5: ...dentifies the operating components and option for that specific unit see EarthWise Purge System Model Number p 6 for detailed information The model number is also printed on the unit nameplate It is important to refer to the model number when ordering parts or requesting technical assistance Figure 1 Example of a typical nameplate ...

Страница 6: ...4 with Hersite Condensing Unit S Special Digit 6 Control Options 0 Without Power Supply 1 With Power Supply 2 Standard Condenser Pressure Cutout 3 ASME Condenser Pressure Cutout Digit 7 Control Interface 0 Chiller Interface 1 Purge Interface Digit 8 Frequency 1 60 Hz 2 50 Hz Digit 9 Vacuum Pump A Standard Vacuum Pump B High Vacuum Pump C Industrial Vacuum Pump Digit 10 11 Design Sequence A0 Origin...

Страница 7: ...unted on the chiller Its purpose is to remove non condensable materials that have leaked into the machine N No ot te e For convenience the term air is often used in describing non condensables removed by the purge system although any other non condensable materials that may exist in the chiller are also removed by the purge system Reference Sources The following reference documents may be helpful ...

Страница 8: ...he purge tank When the purge refrigeration system is running refrigerant from the chiller condenser is attracted to the cold surface of the purge evaporator When the gaseous refrigerant contacts the surface of the purge evaporator coil it condenses into a liquid leaving a partial vacuum behind More refrigerant vapor from the chiller condenser migrates to the purge tank to fill the vacuum The liqui...

Страница 9: ...lief device fusible plug 4 Pump out solenoid valve 5 Automatic expansion valve 6 Carbon tank 7 Carbon tank temperature sensor 8 Carbon tank heater 9 Exhaust solenoid valve 10 Pump out compressor 11 Float switch 12 Compressor suction temperature sensor 13 Chiller refrigerant return line 14 Filter drier canister P Pu ur rg ge e S Sy ys st te em m O Ov ve er rv vi ie ew w ...

Страница 10: ...sure relief valve 3 Exhaust solenoid valve 4 Pump out compressor 5 Carbon tank heater 6 Automatic expansion valve 7 Pump out solenoid valve 8 Pressure relief device fusible plug 9 Carbon tank 10 Purge tank 11 Condensing unit 12 Chiller refrigerant supply line P Pu ur rg ge e S Sy ys st te em m O Ov ve er rv vi ie ew w ...

Страница 11: ...ugh idle chillers chillers installed outdoors or in unconditioned spaces or any application that may cause very low condenser water temperatures Carbon Tank and Regeneration Subsystem The discharge from the pump out compressor is piped through the carbon tank The special carbon in the tank effectively scrubs and collects refrigerant molecules from the non condensable gas before the gas passes thro...

Страница 12: ...ank of the purge system It provides feedback to the carbon regeneration algorithm The sensor and the controller function much the same as a thermostat to control the carbon tank heater L Li iq qu ui id d l le ev ve el l s se en ns so or r This sensor resides in the purge control panel It monitors the status of the normally closed float switch which is mounted in the bottom of the purge tank If an ...

Страница 13: ...it only when needed to remove non condensables rather than running it continuously The Adaptive mode requires historical operating data so that the controller can make optimal decisions regarding how to run the purge refrigeration circuit in the future On initial start up of a chiller that is in Adaptive mode the purge refrigeration circuit runs continuously for 168 hours 7 days The chiller compre...

Страница 14: ...ur Pumpout Time 8 minutes No Off cycle During the purge refrigeration circuit Off cycle the time remaining is displayed as Time Until Next Purge Run in the Log Sheet that you can view from the Tracer AdaptiView display refer to Log Sheet p 23 If the compressor is turned Off during the purge refrigeration circuit Off cycle the purge transfers to Adaptive Mode Procedure Chiller Compressor Off Figure...

Страница 15: ...ith the chiller On over the last 7 days N No ot te e These two values can be seen on the Tracer AdaptiView display Figure 5 Adaptive chiller OFF flow chart The purge will be shut down for a corresponding period of time as shown in the following table Pumpout Time with chiller On or Off over the last 24 hours or daily average over the last 7 days whichever is greater Purge Off cycle duration Pumpou...

Страница 16: ... F 37 8 C condensing the purge refrigeration cycle should have the temperatures shown in the following figure for Locations 1 5 N No ot te e To troubleshoot the system by taking these temperatures refer to Taking Surface Temperature Measurements p 30 Figure 6 Purge refrigeration circuit showing temperatures at various locations in operating cycle Temperatures at numbered locations 1 After expansio...

Страница 17: ...urning to the purge condensing unit compressor suction has a high superheat heat added past the point of evaporation because of the heat removed from the condensing chiller refrigerant vapor in the purge tank As air accumulates in the purge tank it displaces the chiller refrigerant vapor and decreases the amount of coil surface that is exposed to the vapor Less heat is removed from the vapor and t...

Страница 18: ...of 34 psia 234 4 kPaA Therefore refrigerant is metered into the coil as a two phase refrigerant mixture at a constant saturation temperature of approximately 16 F 8 9 C The cold coil creates a low vapor pressure near its outside surface which draws refrigerant from the chiller condenser into the purge tank and to the coil surface When the refrigerant gets close enough to the coil surface it conden...

Страница 19: ...ions are met a carbon regeneration cycle is NOT in process and the refrigeration circuit is on If at any time except as described above the purge refrigerant compressor suction temperature drops below the pump out initiate value the following sequence is initiated by the controls The controller starts the pump out compressor and opens the exhaust solenoid valve After 5 seconds the pump out solenoi...

Страница 20: ...ting conditions and operating schedule Carefully monitor the purge pump out activity for each chiller for an appropriate period of time one week or more in order to establish a baseline value for a Purge Daily Pumpout Limit that is appropriate for that specific installation Set the Purge Daily Pumpout Limit high enough to avoid nuisance trips but low enough to trigger an alarm diagnostic should th...

Страница 21: ...tank capacity remaining 100 80 500 100 84 The purge controls may initiate a carbon tank regeneration cycle when the remaining carbon tank capacity is calculated to be less than 80 percent However the continued stable operation of the chiller is always more important than the regeneration of the carbon tank Therefore the following rules apply 1 If the Daily Pump out Limit is disabled a regeneration...

Страница 22: ...nostic is to identify a failed heater or temperature sensor It prevents automatic regeneration from occurring but a service technician can initiate a manual regeneration for testing purposes All other purge algorithms continue to function If the carbon tank temperature does not reach the minimum regeneration temperature setpoint within four hours the controller generates a non latching diagnostic ...

Страница 23: ...g 168 hour window that the chiller was operating You can use it to help determine if a leak is present on the high side or the low side of the chiller P Pu um mp po ou ut t C Ch hi il ll le er r O On n 7 7 D Da ay ys s Indicates the percentage of the total purge pump out time during the past seven days that occurred while the chiller was operating You can use it to help determine if a leak is pres...

Страница 24: ... range is from 1 to 50 minutes the factory default is 10 minutes D Di is sa ab bl le e D Da ai il ly y P Pu um mp po ou ut t L Li im mi it t Use it to disable alarms for a specified time that are associated with exceeding the daily pumpout limit This is useful when large amounts of purging are needed following chiller servicing or operator error The range is from 0 to 72 hours the factory default ...

Страница 25: ...e ex xc ce ee ed d 3 30 00 0 F F 1 15 50 0 C C T To o a av vo oi id d p po os ss si ib bl le e s sk ki in n b bu ur rn ns s s st ta ay y c cl le ea ar r o of f t th he es se e s su ur rf fa ac ce es s I If f p po os ss si ib bl le e a al ll lo ow w s su ur rf fa ac ce es s t to o c co oo ol l b be ef fo or re e s se er rv vi ic ci in ng g I If f s se er rv vi ic ci in ng g i is s n ne ec ce es ss ...

Страница 26: ...drain valve Then check for leaks 10 Release the pressure remove hoses and replace all valve caps 11 Set the purge operating mode to On and wait for the purge pump out compressor to start 12 Open the isolation valves on the vapor inlet lines and the liquid return line 13 After purge pump out stops or after several minutes return the purge operating mode to Auto or Adaptive recommended using the Tra...

Страница 27: ...urge system has a faster air exhaust rate than previous purge systems which makes bypassing or removing the restrictor unnecessary The Daily Pumpout Limit determines how long the purge pump out compressor can operate continuously without generating a Purge Daily Pumpout Exceeded diagnostic which will shut off the purge system You can disable the Daily Pumpout Limit to allow the purge to pump out f...

Страница 28: ...rs so on na al l P Pr ro ot te ec ct ti iv ve e E Eq qu ui ip pm me en nt t P PP PE E Diagnostics The chiller controller generates diagnostics to alert the operator to abnormal conditions There are two kinds of diagnostics Non latching diagnostics Operation continues Alarms resolve themselves and the alarm disappears They are informational only Latching diagnostics Operation stops until the condit...

Страница 29: ...ed if the purge is functioning correctly If a large amount of air is removed leak test the chiller and repair leaks Consider using the Adaptive mode to run the purge as required when the chiller is Off If non condensable removal is required during chiller operation relocate the vapor liquid connections to a more effective location Pump out restrictor plugged Clean out restrictor orifice with compr...

Страница 30: ...gs with an accurate 1 F 0 55 C surface mounted thermocouple type temperature probe that has a range of 40 F 40 0 C to 200 F 93 3 C The locations to be measured are shown in Figure 6 p 16 The temperatures that you should expect to find under typical operating conditions are given in the same figure 1 To ensure accurate measurements remove any ice that may exist on measuring surfaces before attachin...

Страница 31: ... to take manual control to test the operation of specific functions Refer to the following table as you test the functions in this section Table 3 Purge component status Displayed purge status Condensing unit Pump out compressor Pump out solenoid Exhaust solenoid Regeneration solenoid Carbon tank heater Refrigerant Circuit On o o o o o Refrigerant Circuit Idle o o o o o o Pumping Out X o o Regener...

Страница 32: ...for leaks by using a soap solution 5 Relieve the testing pressure from the exhaust circuit before disabling this test When the test is disabled the exhaust solenoid valve re closes Exhaust Circuit Vacuum Check The Exhaust Circuit Vacuum Check enables the servicing technician to check the exhaust circuit components and lines for leakage by placing a vacuum on the exhaust circuit N No ot te e This t...

Страница 33: ...tage 175 W Alarm relay output rating 120 Vac 1 3 hp 7 2 FLA Operating temperature range 34 F to 110 F 1 1 C to 43 3 C Storage temperature range 40 F to 150 F 40 0 C to 65 5 C Storage and operating humidity range 5 to 95 relative humidity non condensing Mounting Direct mounted on condenser shell above the liquid level of highest condenser Dimensions approximate 25 3 4 in 65 4 cm high x 27 1 2 in 69...

Страница 34: ...er r l lo oc ck ko ou ut t t ta ag go ou ut t p pr ro oc ce ed du ur re es s t to o e en ns su ur re e t th he e p po ow we er r c ca an n n no ot t b be e i in na ad dv ve er rt te en nt tl ly y e en ne er rg gi iz ze ed d V Ve er ri if fy y t th ha at t n no o p po ow we er r i is s p pr re es se en nt t w wi it th h a a v vo ol lt tm me et te er r N NO OT TI IC CE E U Us se e C Co op pp pe er r...

Страница 35: ...PRGD SVX01F EN 35 S Sc ch he em ma at ti ic c W Wi ir ri in ng g D Di ia ag gr ra am m ...

Страница 36: ...36 PRGD SVX01F EN S Sc ch he em ma at ti ic c W Wi ir ri in ng g D Di ia ag gr ra am m ...

Страница 37: ...PRGD SVX01F EN 37 N No ot te es s ...

Страница 38: ...38 PRGD SVX01F EN N No ot te es s ...

Страница 39: ...PRGD SVX01F EN 39 N No ot te es s ...

Страница 40: ...d protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice We are committed to using environmentally conscious pr...

Отзывы: