Space Temperature Averaging
(ReliaTel™ Only)
Space temperature averaging is accomplished by wiring a
number of remote sensors in a series/parallel circuit.
Using the BAYSENS016* or BAYSENS077*, at least four
sensors are required to accomplish space temperature
averaging. See diagram below.
•
Example #1 illustrates two series circuits with two
sensors in each circuit wired in parallel. The square of
any number of remote sensors is required.
•
Example #2 illustrates three sensors squared in a
series/parallel circuit. Using BAYSENS077*, two
sensors are required to accomplish space temperature
averaging.
•
Example #3 illustrates the circuit required for this
sensor.
lists the temperature versus
resistance coefficient for all sensors.
Figure 65. ReliaTel™ control customer low voltage routing (all units)
Refrigeration
Module
Communication
Interface
LTB
ReliaTel
Conventional Wiring
Route Field Wiring as shown
and Secure with 2 Wire Ties
ReliaTel
TBU Wiring
Route Field Wiring as shown
and Secure with 3 Wire Ties
Communication
Interface
Refrigeration
Module
LTB
TBU
Option
Unpowered
Convenience
Outlet
Secure Field
Installed Wiring
for Convenience
Outlet with
Pop-In Wire Tie