General Information
12
RT-SVX46G-EN
System Input Devices and Functions
The RTRM must have a zone sensor or thermostat input in
order to operate the unit. The flexibility of having several
mode capabilities depends upon the type of zone sensor
or thermostat selected to interface with the RTRM.
The descriptions of the following basic Input Devices used
within the RTRM network are to acquaint the operator with
their function as they interface with the various modules.
Refer to the unit’s electrical schematic for the specific
module connections.
The following controls are available from the factory for
field installation.
Wall Mounted Relative Humidity Sensor
(BAYSENS036*)
Field installed, wall mounted humidity sensor is used to
control activation of Enhanced Dehumidification and the
Hot Gas Reheat Dehumidification options. Humidity set
points can be selected for relative humidity levels between
40% and 60% by adjusting the DEHUMID setting on the
ReliaTel™ Options Module. See
.
Wireless Zone Sensor (BAYSENS050*)
This electronic sensor features five system settings (Auto,
Off, Cool, Heat, and Emergency Heat) and with On and
Auto fan settings. It is a manual or auto changeover
control with dual setpoint capability. Other features
include a timed override function, lockable system
settings, and Fahrenheit or Celsius temperature display.
Included with the wireless zone sensor will be a receiver
that is to be mounted inside the unit, a mounting bracket,
and a wire harness.
Zone Sensor Module (ZSM) (BAYSENS106*)
This electronic sensor features three system switch
settings (Heat, Cool, and Off) and two fan settings (On and
Auto). It is a manual changeover control with single
setpoint. (Cooling Setpoint Only)
Zone Sensor Module (ZSM) (BAYSENS108*)
This electronic sensor features four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and
Auto). It is a manual or auto changeover control with dual
setpoint capability. It can be used with a remote zone
temperature sensor BAYSENS077*.
Zone Sensor (BAYSENS110*)
This electronic sensor features four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and
Auto) with four system status LED’s. It is a manual or auto
changeover control with dual setpoint capability. It can be
used with a remote zone temperature sensor
BAYSENS077*.