26
RT-SVX075A-EN
Clearances
illustrates the minimum operating and
service clearances for either a single or multiple unit
installation. These clearances are the minimum distances
necessary to assure adequate serviceability, cataloged unit
capacity, and peak operating efficiency. Providing less than
the recommended clearances may result in condenser coil
starvation, “short-circuiting” of exhaust and economizer
airflows, or recirculation of hot condenser air.
Figure 25.
Typical installation clearances for single and multiple unit applications
Side by Side
Note 1
End to End
Note 1, 2
7’0”
2134 MM
6’0”
1829 MM
3’0”
914 MM
Single Unit
3’0”
914 MM
3’0”
914 MM
4’0”
1219 MM
Notes:
1. When equipped with economizer
or barometric relief damper, clearance
distance is to be measured from
protruding hood instead of base.
2. Clearance is the same if any unit
is rotated 180 degrees.
4’0”
1219 MM
for D cabinet
5’0”
1525 MM
for D cabinet
5’8” for D cabinet
1727 MM
Weights
Table 1.
Model weights, corner weights (lbs) and center of gravity dimensions (in.)
Tons
Unit Model No.
Model Weights
(a)
Corner Weights
(b)
Center of Gravity (in.)
Shipping
Net
A
B
C
D
Length
Width
6
YHJ072
1107
1009
331
309
178
191
43
19
7.5
YHJ090
1111
1013
333
310
178
191
43
19
8
YHJ102
1127
1029
338
315
181
194
43
19
10
YHJ120
1137
1039
341
318
183
196
43
19
12.5
YHJ150
1512
1318
385
389
273
270
50
26
15
YHJ180
2220
2000
671
492
354
483
52
36
17.5
YHJ210
2250
2030
672
509
366
484
53
36
20
YHJ240
2320
2100
754
516
337
493
50
34
25
YHJ300
2370
2150
746
529
363
512
51
35
(a)
Weights are approximate. Weights do not include additional factory or field installed options/accessories. For option/accessory additional weights to be added to unit weight,
reference the following table.
(b)
Corner weights are given for information only.