Table 3.
Unit MCA & MOP electrical data (standard indoor fan motor) (heat pump)
WSC
Volts
MCA
MOP
WSC
Volts
MCA
MOP
036
208-230/1
31.2
45
072
208-230/3
36.3
50
208-230/3
23.8
35
460/3
20.3
30
460/3
11.4
15
575/3
12.4
20
575/3
8.8
15
090
208-230/3
38.4
60
048
208-230/1
38.9
60
460/3
19
30
208-230/3
27.5
40
575/3
14.5
20
460/3
12.3
15
120
208-230/3
51.9
60
575/3
9.5
15
460/3
26.1
35
060
208-230/1
44.6
70
575/3
20.1
25
208-230/3
30.2
45
460/3
14.7
20
575/3
11.0
15
Table 4.
3-10 ton unit indoor fan data (heat pump)
Standard
HP - RPM
Oversize
HP - RPM
Standard
HP - RPM
Oversize
HP - RPM
WSC
Volts
WSC
Volts
036
208-230/1
(a)
(a) Direct drive motor
3/4 - MULT
N/A
072
208-230/3
1-1725
2-1725
208-230/3
1 - 1725
N/A
460/3
460/3
N/A
575/3
575/3
N/A
090
208-230/3
1-1725
2-1725
048
208-230/1
(a)
3/4 - MULT
N/A
460/3
208-230/3
1 - 1725
N/A
575/3
460/3
N/A
120
208-230/3
3.75/MULTI
N/A
575/3
N/A
460/3
060
208-230/1
(a)
3/4 - MULT
N/A
575/3
208-230/3
1 - 1725
N/A
460/3
N/A
575/3
N/A
Table 5.
Unit dimensional data
B
C
D
E
Unit Length UL
69 7/8
88 5/8
88 5/8
99 11/16
Unit Width UW
44 1/4
53 1/4
53 1/4
63 3/16
Unit Height UH
36 1/4
40 7/8
46 7/8
50 7/8
Clearance C1
48
48
48
48
Clearance C2
36
36
36
36
Clearance C3
36
36
36
36
Clearance C4
36
36
36
36
Clearance C5
72
72
72
72
Curb Length CL
65 13/16
84 1/2
84 1/2
84 1/2
Curb Width CW
41 7/16
50 3/8
50 3/8
60 3/8
Supply Length SL
(a)
(a) Dimensions are for roof curb openings and not duct inserts. Reference the product catalog for duct insert
dimensions.
16 3/4
18 1/2
18 1/2
18 1/2
Supply Width SW
(a)
17 7/8
34 3/8
34 3/8
34 3/8
Return Length RL
(a)
14 9/16
18 1/4
18 1/4
18 1/4
Return Width RW
(a)
25 3/16
34 3/8
34 3/8
34 3/8