background image

34

PKGP-SVX011A-EN

Unit Start-Up

Sequence of Operation

See ACC-APG002*-EN, Application Guide, Symbio™ 700
Controller with Precedent™ Packaged Rooftop Air-
Conditioners.

Return Air Smoke Detector

The return air smoke detector is designed to shut off the
unit if smoke is sensed in the return air stream. Sampling
the airflow entering the unit at the return air opening
performs this function.

In order for the smoke detector to properly sense smoke in
the return air stream, the air velocity entering the unit must
be between 500 and 4000 feet per minute. Equipment
covered in this manual will develop an airflow velocity that
falls within these limits over the entire airflow range
specified in the evaporator fan performance tables.

Compressor Start-Up

WARNING

Live Electrical Components!

Failure to follow all electrical safety precautions when
exposed to live electrical components could result in
death or serious injury.
When it is necessary to work with live electrical
components, have a qualified licensed electrician or
other individual who has been properly trained in
handling live electrical components perform these
tasks.

1. Attach a set of service gauges onto the suction and

discharge gauge ports for each circuit.

Proceed to the next Service Test step if continuing from
previous component start-up or until the desired start-
up component test is started.

2. After the compressor and condenser fan have started

and operated for approximately 30 minutes, observe
the operating pressures. Compare the operating
pressures to the label on the access panel.

3. Check system superheat. Follow the instruction listed

on the superheat charging curve in the Service Facts.
Superheat should be within ±5ºF of the superheat chart
value.

4. Repeat steps 1 through 4 for each refrigerant circuit.

5. To stop the SERVICE TEST, turn the main power

disconnect switch to the “Off” position or proceed to the
next component start-up procedure. Remove
electromechanical test mode connections (if
applicable).

Hot Gas Reheat

WARNING

Live Electrical Components!

Failure to follow all electrical safety precautions when
exposed to live electrical components could result in
death or serious injury.
When it is necessary to work with live electrical
components, have a qualified licensed electrician or
other individual who has been properly trained in
handling live electrical components perform these
tasks.

Set the unit to Service Test step Reheat. Once the unit is in
the reheat test mode, verify that the 3 way valve has shifted
to the reheat position and that the supply temperature rises
10ºF more than when in cooling mode stage 2.

Monitor the suction pressure for 15 minutes. The suction
pressure should remain within 5 psi of normal cooling
operation. If the unit has a 2 speed outdoor fan and if the
outdoor air temperature is below 70°F, verify that the OD
fan is in low speed.

1. Clamp an amp meter around one of 1st stage heater

power wires at the heater contactor.

2. Using the Service Test Guide in

Figure 24, p. 33

,

continue the SERVICE TEST start-up procedure for
each compressor circuit.

Select the next desired Service Test Mode if continuing
from previous component start up or exit Service Test if
complete.

Final System Setup

After completing all of the pre-start and startup procedures
outlined in the previous sections (i.e., operating the unit in
each of its modes through all available stages of cooling
and heating), perform these final checks before leaving the
unit:

Program the Night Setback (NSB) panel (if applicable)
for proper unoccupied operation. Refer to the
programming instructions for the specific panel.

Verify that the Remote panel “System” selection switch,
“Fan” selection switch, and “Zone Temperature”
settings for automatic operation are correct.

Inspect the unit for misplaced tools, hardware, and
debris.

Verify that all exterior panels including the control panel
doors and condenser grilles are secured in place.

Close the main disconnect switch or circuit protector
switch that provides the supply power to the unit’s
terminal block or the unit mounted disconnect switch.

Содержание Precedent WHJ150

Страница 1: ...perly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags s...

Страница 2: ...at is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the appli...

Страница 3: ...t than these policies those regulations supersede these policies Non Trane personnel should always follow local regulations Copyright This document and the information in it are the property of Trane...

Страница 4: ...BAYSENS135 10 Touch Screen Programmable Zone Sensor BAYSENS800 11 Evaporator Frost Control 11 Discharge Line Temp Switch DLTS 11 Smoke Detector Sensor Optional 11 Phase Monitor 11 Pre Installation 12...

Страница 5: ...nthly Maintenance 36 Filters 36 Return Air Smoke Detector Maintenance 36 Condensate Overflow Switch 36 Cooling Season 36 Heating Season 36 Coil Cleaning 37 Coil Cleaning Procedure 37 Annual Maintenanc...

Страница 6: ...Oversized High Static Motor 2 Single Zone Variable Air Volume with Standard Motor 3 Single Zone Variable Air Volume with Oversized High Static Motor 4 Multiple Zone Variable Air Volume with Standard...

Страница 7: ...7 Clogged Filter Switch Condensate Overflow Switch and Discharge Air Sensing Tube1 2 Digit 26 Not Used Digit 27 Hardware Enhancements 0 No Enhancements 1 Stainless Steel Drain Pan Digit 28 Short Circ...

Страница 8: ...orage Take precautions to prevent condensate from forming inside the unit s electrical compartments and motors if The unit is stored before it is installed or The unit is set on the roof curb and temp...

Страница 9: ...ilter switch has been closed for at least 2 minutes The system will continue to operate regardless of the status of the filter switch For further details refer to Installation Instructions ACC SVN238...

Страница 10: ...ated Comfort building management system Integrated Comfort System BAYSENS074 This sensor features single setpoint capability and timed override with override cancellation It is used with a Trane Integ...

Страница 11: ...re to follow these instructions will prevent the smoke detectors from performing its design function Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coi...

Страница 12: ...g Precautionary Measures Avoid breathing fiberglass dust Use a NIOSH approved dust mist respirator Avoid contact with the skin or eyes Wear long sleeved loose fitting clothing gloves and eye protectio...

Страница 13: ...MBh EVAPORATOR SECTION ACCESS PANEL CONDENSATE DRAIN INDOOR TOP PANEL CONTROL BOX SECTION ACCESS PANEL UNIT CONTROL WIRE 2 50 MM DIA HOLE UNIT POWER WIRE 2 50 MM DIA HOLE OUTDOOR TOP PANEL SERVICE GA...

Страница 14: ...8MM 8 3 8 212MM 48 1223MM 6 5 8 167 MM 55 0577 1398 467 55 2977 1404 563 8 205MM 55 3 8 1404MM THROUGH THE BASE ELECTRICAL THROUGH THE BASE GAS D_J MODELS ONLY Figure 4 12 5 to 25 tons high efficiency...

Страница 15: ...22 7 Figure 6 12 5 to 25 tons high efficiency unit clearance and roof opening UNIT OUTLINE CLEARANCE 36 914 MM CLEARANCE 48 1219 MM FRONT OF UNIT CLEARANCE 60 1524 MM CLEARANCE 68 1727 MM 76 1 2 1943...

Страница 16: ...swing diameter for hinged door s option 32 809MM 30 754MM 36 907MM Clearances Figure 9 p 17 illustrates the minimum operating and service clearances for either a single or multiple unit installation T...

Страница 17: ...cabinet 5 8 for D cabinet 1727 MM Weights Table 1 Model weights corner weights lbs and center of gravity dimensions in Tons Unit Model No Model Weights a Corner Weights b Center of Gravity in Shippin...

Страница 18: ...w Leak Economizer Horizontal 180 180 Manual Outside Air Damper 15 15 Motorized Outside Air Damper 82 82 Oversized Motor 30 Powered Convenience Outlet 50 50 Powered Exhaust 110 110 Reheat Coil 100 100...

Страница 19: ...ht of the unit Lifting cables chains or slings may not be of the same length Adjust as necessary for even unit lift WARNING Improper Unit Lift Failure to properly lift unit in a LEVEL position could r...

Страница 20: ...ous injury and property damage Confirm with a structural engineer that the roof structure is strong enough to support the combined weight of the roofcurb the unit and any accessories For rooftop appli...

Страница 21: ...roof deck for the ductwork penetrations Do not cut out the entire roof deck within the curb perimeter If a Curb Accessory Kit is not used The ductwork can be attached directly to the factory provided...

Страница 22: ...all the roof curb if applicable Refer to the latest edition of the curb installers guide that ships with each curb kit Fabricate and install ductwork secure ductwork to curb Install pitch pocket for p...

Страница 23: ...ust be removed to allow the cable to extend to the horizontal mounting location Main Electrical Power Requirements WARNING Hazardous Voltage w Capacitors Failure to disconnect power and discharge capa...

Страница 24: ...lock Figure 18 Condensate trap installation 38 1 Note Minimum if unit static is higher trap must be taller to drain appropriately Filter Installation The quantity of filters is determined by unit siz...

Страница 25: ...ns should be terminated in the control box at main panel power terminal block HTB1 Provide proper grounding for the unit in accordance with local and national codes Notes Black gasket is shipped from...

Страница 26: ...for the electrical access locations provided on the unit and Table 4 p 28 for AC conductor sizing guidelines and 1 Use copper conductors unless otherwise specified 2 Ensure that the AC control wiring...

Страница 27: ...PKGP SVX011A EN 27 Figure 20 Low voltage wiring C cabinet Figure 21 Low voltage wiring D cabinet Installation...

Страница 28: ...on the unit Table 5 p 28 lists the conductor sizing guidelines that must be followed when interconnecting the DC binary output devices and the system components utilizing a DC analog input output sig...

Страница 29: ...of remote sensors is required Example 2 illustrates three sensors squared in a series parallel circuit Using BAYSENS077 two sensors are required to accomplish space temperature averaging Example 3 il...

Страница 30: ...56 5 15 0 74 65 10 12 2 63 80 15 9 4 54 66 20 6 7 46 94 25 3 8 40 40 30 1 1 34 85 35 1 7 30 18 40 4 4 26 22 Table 6 Temperature vs resistance continued Temperature Nominal Resistance kOhms Degrees F...

Страница 31: ...e Three phase electrical power to the unit must meet stringent requirements for the unit to operate properly Measure each leg phase to phase of the power supply Each reading must fall within the utili...

Страница 32: ...e Heaters Each compressor can be equipped with a crankcase heater On some units the crankcase heater comes standard The proper operation of the crankcase heater is important to maintain an elevated co...

Страница 33: ...ler will remain in any given state once initiated For detailed information on how each Service Test State is interpreted based on the equipment s configuration see ACC APG002 EN Symbio 700 for Precede...

Страница 34: ...ectromechanical test mode connections if applicable Hot Gas Reheat WARNING Live Electrical Components Failure to follow all electrical safety precautions when exposed to live electrical components cou...

Страница 35: ...e following tasks you MUST Follow all instructions in the unit s Installation Operation and Maintenance manual including warnings cautions and notices Perform all required tasks in any applicable Serv...

Страница 36: ...dures refer to the appropriate section s of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit Condensate Overflow Switch During maintenanc...

Страница 37: ...move the access panel from the roof located next to the rear condenser fan 2 Protect all electrical devices such as motors and controllers from any over spray 3 Straighten any bent coil fins with a fi...

Страница 38: ...oil has been added in the factory for all Hot Gas Reheat units If major components MCHE coil valve assembly etc are replaced or serviced the following steps must be taken 1 Measure the amount of oil...

Страница 39: ...mple maintenance log Date Current Ambient Temp F C Refrigerant Circuit 1 Refrigerant Circuit 2 Compr Oil Level Suct Press Psig kPa Disch Press Psig kPa Liquid Press Psig kPa Super heat F C Sub cool F...

Страница 40: ...40 PKGP SVX011A EN Troubleshooting See ACC APG002 EN Application Guide Symbio 700 Controller with Precedent Packaged Rooftop Air Conditioners...

Страница 41: ...l 12134343 SCHEMATIC SHEET 2 POWER SINGLE INDOOR FAN COOLING ONLY ELECTRIC HEAT HIGH SCCR Main Unit Symbio 700 230V 12134344 SCHEMATIC SHEET 2 POWER SINGLE INDOOR FAN 2 STAGE GAS HEAT 230V HIGH SCCR M...

Страница 42: ...ATIC SHEET 1 ELECTRIC HEAT 27 36 KW 240V Electric Heat Symbio 700 230V 12134303 SCHEMATIC SHEET 1 ELECTRIC HEAT 54 KW 240V Electric Heat Symbio 700 460V 575V 12134304 SCHEMATIC SHEET 1 ELECTRIC HEAT 9...

Страница 43: ...AIR SERVICE VALVE SUCTION LINE LIQUID LINE FITER DRIER TXV TXV BULB EQUALIZING LINE SERVICE VALVE AIR OUTDOOR COIL LOW PRESSURE CONTROL DISCHARGE LINE COMPRESSOR 1A S D COMPRESSOR 1B DISCHARGE LINE TH...

Страница 44: ...IR SERVICE VALVE N O I T C U S LINE LIQUID LINE FILTER DRIER TXV TXV BULB EQUALIZING LINE SERVICE VALVE AIR OUTDOOR COIL LOW PRESSURE CONTROL COMPRESSOR 1A S D COMPRESSOR 1B DISCHARGE LINE THERMOSTAT...

Страница 45: ...SUCTION LINE LIQUID LINE FITER DRIER TXV 1 EQUALIZING LINE SERVICE VALVE OUTDOOR COIL LOW PRESSURE CONTROL DISCHARGE LINE DISCHARGE LINE THERMOSTAT HIGH PRESSURE CONTROL AIR AIR INDOOR COIL 1 INDOOR C...

Страница 46: ...1 EQUALIZING LINE SERVICE VALVE OUTDOOR COIL LOW PRESSURE CONTROL DISCHARGE LINE THERMOSTAT HIGH PRESSURE CONTROL AIR AIR INDOOR COIL 1 INDOOR COIL 2 TXV BULB 2 TXV BULB 1 TXV 2 EQUALIZING LINE DISCHA...

Страница 47: ...ucts have been paid for and then liability shall be limited solely to the purchase price of the equipment under warranty shown to be defective THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU O...

Страница 48: ...ormation please visit trane com or americanstandardair com Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and speci...

Отзывы: