background image

32

PKGP-SVX011A-EN

WARNING

Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors
before servicing could result in death or serious
injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify with a CAT III or IV
voltmeter rated per NFPA 70E that all capacitors have
discharged.

1. Turn the field supplied disconnect switch that provides

power to the main power terminal block or to the “Line”
side of the optional factory mounted disconnect switch
to the “Off” position.

2. Connect the phase sequence indicator leads to the

terminal block or to the “Line” side of the optional
factory mounted disconnect switch as follows;

Brown (phase A) to L1

Orange (phase B) to L2

Yellow (phase C) to L3

3. Close the field supplied main power disconnect switch

or circuit protector switch that provides the supply
power to the unit.

Note:

Upon closing main power disconnect and the unit

mounted disconnect switch or circuit breaker,
the phase monitor will verify proper phasing. If
LED on face of the monitor is red, correct supply
power fault.

WARNING

Live Electrical Components!

Failure to follow all electrical safety precautions when
exposed to live electrical components could result in
death or serious injury.
When it is necessary to work with live electrical
components, have a qualified licensed electrician or
other individual who has been properly trained in
handling live electrical components perform these
tasks.

To prevent injury or death from electrocution, it is the
responsibility of the technician to recognize this hazard and
use extreme care when performing service procedures with
the electrical power energized.

4. Observe the ABC and CBA phase indicator lights on

the face of the sequencer. The ABC indicator light will
glow if the phase is ABC. If the CBA indicator light
glows, open the disconnect switch or circuit protection
switch and reverse any two power wires.

5. Restore the main electrical power and recheck the

phasing. If the phasing is correct, open the disconnect
switch or circuit protection switch and remove the
phase sequence indicator.

Compressor Crankcase Heaters

Each compressor can be equipped with a crankcase heater
(On some units the crankcase heater comes standard).
The proper operation of the crankcase heater is important
to maintain an elevated compressor oil temperature during
the “Off” cycle to reduce oil foaming during compressor
starts.

Oil foaming occurs when refrigerant condenses in the
compressor and mixes with the oil. In lower ambient
conditions, refrigerant migration to the compressor could
increase.

When the compressor starts, the sudden reduction in
crankcase pressure causes the liquid refrigerant to boil
rapidly causing the oil to foam. This condition could
damage compressor bearings due to reduced lubrication
and could cause compressor mechanical failures.

Before starting the unit in the “Cooling” mode, set the
system switch to the “Off” position and turn the main power
disconnect to the “On” position and allow the crankcase
heater to operate a minimum of 8 hours.

Before closing the main power disconnect switch, insure
that the “System” selection switch is in the “Off” position
and the “Fan” selection switch is in the “Auto” position.

Close the main power disconnect switch and the unit
mounted disconnect switch, if applicable.

Note:

Upon closing main power disconnect and the unit

mounted disconnect switch or circuit breaker, the
phase monitor will verify proper phasing. If LED on
face of the monitor is red, correct supply power fault.

WARNING

Live Electrical Components!

Failure to follow all electrical safety precautions when
exposed to live electrical components could result in
death or serious injury.
When it is necessary to work with live electrical
components, have a qualified licensed electrician or
other individual who has been properly trained in
handling live electrical components perform these
tasks.

To prevent injury or death from electrocution, it is the
responsibility of the technician to recognize this hazard and
use extreme care when performing service procedures with
the electrical power energized.

Symbio Controls

The Symbio™ 700 supports a Service Test Mode that can
be used to energize the various components of the system,
either to support general system startup tasks or to support
troubleshooting. The user can initiate Service Test Mode
through the controller user interfaces, including the Symbio
Service and Installation mobile application.

The modes shown below can be initiated. Depending on
the equipment configuration, the controller will energize the

Pre-Start

Содержание Precedent WHJ150

Страница 1: ...perly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags s...

Страница 2: ...at is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the appli...

Страница 3: ...t than these policies those regulations supersede these policies Non Trane personnel should always follow local regulations Copyright This document and the information in it are the property of Trane...

Страница 4: ...BAYSENS135 10 Touch Screen Programmable Zone Sensor BAYSENS800 11 Evaporator Frost Control 11 Discharge Line Temp Switch DLTS 11 Smoke Detector Sensor Optional 11 Phase Monitor 11 Pre Installation 12...

Страница 5: ...nthly Maintenance 36 Filters 36 Return Air Smoke Detector Maintenance 36 Condensate Overflow Switch 36 Cooling Season 36 Heating Season 36 Coil Cleaning 37 Coil Cleaning Procedure 37 Annual Maintenanc...

Страница 6: ...Oversized High Static Motor 2 Single Zone Variable Air Volume with Standard Motor 3 Single Zone Variable Air Volume with Oversized High Static Motor 4 Multiple Zone Variable Air Volume with Standard...

Страница 7: ...7 Clogged Filter Switch Condensate Overflow Switch and Discharge Air Sensing Tube1 2 Digit 26 Not Used Digit 27 Hardware Enhancements 0 No Enhancements 1 Stainless Steel Drain Pan Digit 28 Short Circ...

Страница 8: ...orage Take precautions to prevent condensate from forming inside the unit s electrical compartments and motors if The unit is stored before it is installed or The unit is set on the roof curb and temp...

Страница 9: ...ilter switch has been closed for at least 2 minutes The system will continue to operate regardless of the status of the filter switch For further details refer to Installation Instructions ACC SVN238...

Страница 10: ...ated Comfort building management system Integrated Comfort System BAYSENS074 This sensor features single setpoint capability and timed override with override cancellation It is used with a Trane Integ...

Страница 11: ...re to follow these instructions will prevent the smoke detectors from performing its design function Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coi...

Страница 12: ...g Precautionary Measures Avoid breathing fiberglass dust Use a NIOSH approved dust mist respirator Avoid contact with the skin or eyes Wear long sleeved loose fitting clothing gloves and eye protectio...

Страница 13: ...MBh EVAPORATOR SECTION ACCESS PANEL CONDENSATE DRAIN INDOOR TOP PANEL CONTROL BOX SECTION ACCESS PANEL UNIT CONTROL WIRE 2 50 MM DIA HOLE UNIT POWER WIRE 2 50 MM DIA HOLE OUTDOOR TOP PANEL SERVICE GA...

Страница 14: ...8MM 8 3 8 212MM 48 1223MM 6 5 8 167 MM 55 0577 1398 467 55 2977 1404 563 8 205MM 55 3 8 1404MM THROUGH THE BASE ELECTRICAL THROUGH THE BASE GAS D_J MODELS ONLY Figure 4 12 5 to 25 tons high efficiency...

Страница 15: ...22 7 Figure 6 12 5 to 25 tons high efficiency unit clearance and roof opening UNIT OUTLINE CLEARANCE 36 914 MM CLEARANCE 48 1219 MM FRONT OF UNIT CLEARANCE 60 1524 MM CLEARANCE 68 1727 MM 76 1 2 1943...

Страница 16: ...swing diameter for hinged door s option 32 809MM 30 754MM 36 907MM Clearances Figure 9 p 17 illustrates the minimum operating and service clearances for either a single or multiple unit installation T...

Страница 17: ...cabinet 5 8 for D cabinet 1727 MM Weights Table 1 Model weights corner weights lbs and center of gravity dimensions in Tons Unit Model No Model Weights a Corner Weights b Center of Gravity in Shippin...

Страница 18: ...w Leak Economizer Horizontal 180 180 Manual Outside Air Damper 15 15 Motorized Outside Air Damper 82 82 Oversized Motor 30 Powered Convenience Outlet 50 50 Powered Exhaust 110 110 Reheat Coil 100 100...

Страница 19: ...ht of the unit Lifting cables chains or slings may not be of the same length Adjust as necessary for even unit lift WARNING Improper Unit Lift Failure to properly lift unit in a LEVEL position could r...

Страница 20: ...ous injury and property damage Confirm with a structural engineer that the roof structure is strong enough to support the combined weight of the roofcurb the unit and any accessories For rooftop appli...

Страница 21: ...roof deck for the ductwork penetrations Do not cut out the entire roof deck within the curb perimeter If a Curb Accessory Kit is not used The ductwork can be attached directly to the factory provided...

Страница 22: ...all the roof curb if applicable Refer to the latest edition of the curb installers guide that ships with each curb kit Fabricate and install ductwork secure ductwork to curb Install pitch pocket for p...

Страница 23: ...ust be removed to allow the cable to extend to the horizontal mounting location Main Electrical Power Requirements WARNING Hazardous Voltage w Capacitors Failure to disconnect power and discharge capa...

Страница 24: ...lock Figure 18 Condensate trap installation 38 1 Note Minimum if unit static is higher trap must be taller to drain appropriately Filter Installation The quantity of filters is determined by unit siz...

Страница 25: ...ns should be terminated in the control box at main panel power terminal block HTB1 Provide proper grounding for the unit in accordance with local and national codes Notes Black gasket is shipped from...

Страница 26: ...for the electrical access locations provided on the unit and Table 4 p 28 for AC conductor sizing guidelines and 1 Use copper conductors unless otherwise specified 2 Ensure that the AC control wiring...

Страница 27: ...PKGP SVX011A EN 27 Figure 20 Low voltage wiring C cabinet Figure 21 Low voltage wiring D cabinet Installation...

Страница 28: ...on the unit Table 5 p 28 lists the conductor sizing guidelines that must be followed when interconnecting the DC binary output devices and the system components utilizing a DC analog input output sig...

Страница 29: ...of remote sensors is required Example 2 illustrates three sensors squared in a series parallel circuit Using BAYSENS077 two sensors are required to accomplish space temperature averaging Example 3 il...

Страница 30: ...56 5 15 0 74 65 10 12 2 63 80 15 9 4 54 66 20 6 7 46 94 25 3 8 40 40 30 1 1 34 85 35 1 7 30 18 40 4 4 26 22 Table 6 Temperature vs resistance continued Temperature Nominal Resistance kOhms Degrees F...

Страница 31: ...e Three phase electrical power to the unit must meet stringent requirements for the unit to operate properly Measure each leg phase to phase of the power supply Each reading must fall within the utili...

Страница 32: ...e Heaters Each compressor can be equipped with a crankcase heater On some units the crankcase heater comes standard The proper operation of the crankcase heater is important to maintain an elevated co...

Страница 33: ...ler will remain in any given state once initiated For detailed information on how each Service Test State is interpreted based on the equipment s configuration see ACC APG002 EN Symbio 700 for Precede...

Страница 34: ...ectromechanical test mode connections if applicable Hot Gas Reheat WARNING Live Electrical Components Failure to follow all electrical safety precautions when exposed to live electrical components cou...

Страница 35: ...e following tasks you MUST Follow all instructions in the unit s Installation Operation and Maintenance manual including warnings cautions and notices Perform all required tasks in any applicable Serv...

Страница 36: ...dures refer to the appropriate section s of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit Condensate Overflow Switch During maintenanc...

Страница 37: ...move the access panel from the roof located next to the rear condenser fan 2 Protect all electrical devices such as motors and controllers from any over spray 3 Straighten any bent coil fins with a fi...

Страница 38: ...oil has been added in the factory for all Hot Gas Reheat units If major components MCHE coil valve assembly etc are replaced or serviced the following steps must be taken 1 Measure the amount of oil...

Страница 39: ...mple maintenance log Date Current Ambient Temp F C Refrigerant Circuit 1 Refrigerant Circuit 2 Compr Oil Level Suct Press Psig kPa Disch Press Psig kPa Liquid Press Psig kPa Super heat F C Sub cool F...

Страница 40: ...40 PKGP SVX011A EN Troubleshooting See ACC APG002 EN Application Guide Symbio 700 Controller with Precedent Packaged Rooftop Air Conditioners...

Страница 41: ...l 12134343 SCHEMATIC SHEET 2 POWER SINGLE INDOOR FAN COOLING ONLY ELECTRIC HEAT HIGH SCCR Main Unit Symbio 700 230V 12134344 SCHEMATIC SHEET 2 POWER SINGLE INDOOR FAN 2 STAGE GAS HEAT 230V HIGH SCCR M...

Страница 42: ...ATIC SHEET 1 ELECTRIC HEAT 27 36 KW 240V Electric Heat Symbio 700 230V 12134303 SCHEMATIC SHEET 1 ELECTRIC HEAT 54 KW 240V Electric Heat Symbio 700 460V 575V 12134304 SCHEMATIC SHEET 1 ELECTRIC HEAT 9...

Страница 43: ...AIR SERVICE VALVE SUCTION LINE LIQUID LINE FITER DRIER TXV TXV BULB EQUALIZING LINE SERVICE VALVE AIR OUTDOOR COIL LOW PRESSURE CONTROL DISCHARGE LINE COMPRESSOR 1A S D COMPRESSOR 1B DISCHARGE LINE TH...

Страница 44: ...IR SERVICE VALVE N O I T C U S LINE LIQUID LINE FILTER DRIER TXV TXV BULB EQUALIZING LINE SERVICE VALVE AIR OUTDOOR COIL LOW PRESSURE CONTROL COMPRESSOR 1A S D COMPRESSOR 1B DISCHARGE LINE THERMOSTAT...

Страница 45: ...SUCTION LINE LIQUID LINE FITER DRIER TXV 1 EQUALIZING LINE SERVICE VALVE OUTDOOR COIL LOW PRESSURE CONTROL DISCHARGE LINE DISCHARGE LINE THERMOSTAT HIGH PRESSURE CONTROL AIR AIR INDOOR COIL 1 INDOOR C...

Страница 46: ...1 EQUALIZING LINE SERVICE VALVE OUTDOOR COIL LOW PRESSURE CONTROL DISCHARGE LINE THERMOSTAT HIGH PRESSURE CONTROL AIR AIR INDOOR COIL 1 INDOOR COIL 2 TXV BULB 2 TXV BULB 1 TXV 2 EQUALIZING LINE DISCHA...

Страница 47: ...ucts have been paid for and then liability shall be limited solely to the purchase price of the equipment under warranty shown to be defective THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU O...

Страница 48: ...ormation please visit trane com or americanstandardair com Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and speci...

Отзывы: