Minimum Position Setting – FIADMPR102*/103*
To adjust the minimum position setting and check out the
economizer, the power must be connected.
1. Close the unit disconnect and place the zone sensor fan
selector in the fan ON position and the heat/cool
selector in the OFF position. This will place the damper
in the minimum ventilation position.
2. To adjust the minimum position setting for the
required ventilation air, use the Symbio service and
installation mobile app or Symbio™ 700 on-board UI
to adjust the economizer minimum position setpoint
BAS in the fresh/return air settings menu. The damper
will open to this setting each time the blower circuit is
energized.
When adjusting minimum position, the damper may
move to the new setting in several small steps. Once
the damper has remained in position for 10 - 15
seconds without movement, it can be assumed it is at
the new position.
3. Replace the filter access panel.
The damper will close when the blower circuit is
de-energized.