Wiring Connection
14
ACC-SVN199E-EN
Power Exhaust Operation and
Settings
Standard Economizer
The Power Exhaust setpoint (point at which the Power
Exhaust is turned on) is adjustable from 0% to 100%
economizer damper outside air setting, corresponding to
the setting of the "exhaust setpoint" potentiometer on the
RTEM-EM. The Power Exhaust is turned on when the
indoor blower is running and the damper position is
greater than the Power Exhaust setpoint.
Low Leak Economizer
The Power Exhaust setpoint (point at which the Power
Exhaust is turned on) is adjustable from 0% to 100%
economizer damper outside air setting, corresponding to
the setting of the EXH1 SET value in the SETPOINTS menu
in the JADE controller.
The JADE display will display EXH1 OUT as ON when the
Power Exhaust is turned on. Power Exhaust is turned on
when the damper position is greater than the Power
Exhaust setpoint.