Thermostat

CHS-SVN011C-EN

19 

(F1) Units

The PENN A421 electronic temperature control is a 120v 
SPDT thermostat with a simple on/off setpoint of -40° to 
212°F and a built in anti-short cycle delay that is factory set 
at “0” (disabled). The temperature sensor is mounted in 
the return filter door. The touch pad has three buttons for 
setup and adjustments. The basic menu allows for quick 
adjustment of ON and OFF temperature values, as well as 
the Sensor Failure mode (SF) and Anti-Short Cycle Delay 
(ASd) value.

Table 3.

  Fault codes defined

Fault Code

Definition

System Status

Solution

SF flashing alternately with OP

Open temperature sensor 

or sensor wiring

Output functions according to the 
selected sensor failure mode (SF)

See Troubleshooting Procedure. Cycle 

power to reset the control.

SF flashing alternately with SH

Shorted temperature 

sensor or sensor wiring

Output functions according to the 
selected sensor failure mode (SF)

See Troubleshooting Procedure. Cycle 

power to reset the control.

EE

Program failure

Output is off

Reset control by pressing the 

MENU

 

button. If problems persist, replace the 

control.

To change the temperature setpoint

Press MENU button until the LCD displays “OFF”, press 
MENU again, the LCD now displays the “OFF” setpoint 
temperature, press or to change the value (“OFF” 
temperature is the desired room temperature). When the 
desired value is reached press MENU, this stores the 
value. The LCD will now display “On”, press MENU, the 
LCD now displays the on setpoint temperature. Press or to 
change to the desired value and press MENU to save. After 
30 seconds the controller will divert back to the home 
screen, displaying the room temperature.

Note:

When the green relay status LED is illuminated 
the thermostat is calling for cooling (a 
snowflake symbol will also appear).

    EXAMPLE:

 

To maintain room temperature of 5° F, set 

                          the “OFF” to 4° and set the “On” to 5°

Содержание PCC-1L-3210-4-7.5

Страница 1: ...tarting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an un...

Страница 2: ...equipment that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Kn...

Страница 3: ...ents perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury WARNING Improper Unit Lift Test lift uni...

Страница 4: ...Introduction 4 CHS SVN011C EN Included new design sequence low temp air handler specifications applicationsconsideration installation and operations procedures Updated for Trane Technologies...

Страница 5: ...ultiple AHU Applications 7 General Information 8 Airside Data 8 Electrical Data 8 Waterside Data 8 Features 9 Modes of Operation 10 F0 Units 10 F1 Units 12 Installation and Startup Guidelines 14 Three...

Страница 6: ...description for modes of operation The purpose of this document is to aid in the start up and installation of the equipment troubleshoot guidelines and maintenance steps Please contact Trane Rental Se...

Страница 7: ...can only be achieved by restricting the airflow Please contact Trane Rental Services for suggestions on accomplishing this task F1 model AHUs do have the capability to modulate air since they are equ...

Страница 8: ...pe Connection Type Female Pipe Thread F0 Units Garden Hose F1 Units NOTICE Water Damage Connecting all drains to a common line with only one trap could result in condensate retention and possible wate...

Страница 9: ...isy Chain Capable Table 2 Dimensions and Weights F0 F1 Length 9 ft 6 in 8 ft 6 in Width w o Long Throw Adapter 4 ft 4 in 5 ft 5 in Width w Long Throw Adapter 6 ft 0 in n a Height 7 ft 2 in 7 ft 3 in S...

Страница 10: ...licensed service individual who has been properly trained in handling exposed rotating components perform these tasks Failure to follow all safety precautions could result in rotating components cutt...

Страница 11: ...t termination fan delay thermostat settings are to be programmed per the need of each cooling coil a Unit is in defrost when Power and Defrost lights are on b Upon initiation of the defrost cycle powe...

Страница 12: ...20V signal through the communications cable initiating a cooling cycle Then for 50 minutes adjustable but factory set at 50 the FOLLOW unit runs at full cooling capacity After the 50 minute cooling cy...

Страница 13: ...inside the control cabinet In AH mode turn the defrost timer to the lowest time value setting The fan mode is either VFD or BYPASS soft start depending on the fan selection switch position on the cont...

Страница 14: ...hand use your other hand to remove the top two nuts Use both hands to remove the guard or adapter For systems with a defrost timer clock F0 units check the timer to see that it is set for the correct...

Страница 15: ...ch and cam control the open position of the valve The actuator can be rotated without power by pressing down on the override shaft connected to the actuator s gear box and rotating the shaft by hand A...

Страница 16: ...Three Way Valve Operation 16 CHS SVN011C EN F1 Units Bypass Valve Positions Spring closed position Bypass cycle Spring closed position Bypass cycle...

Страница 17: ...erential in the unit by adjusting the differential value and hence its Highest Set Point HSP for the application Shown below is a schematic which illustrates how to use the adjustment knob and differe...

Страница 18: ...Thermostat 18 CHS SVN011C EN To better understand the thermostat sequence of operation see schematic shown below Thermostat Sequence of operation schematic...

Страница 19: ...re sensor or sensor wiring Output functions according to the selected sensor failure mode SF See Troubleshooting Procedure Cycle power to reset the control EE Program failure Output is off Reset contr...

Страница 20: ...lows the coil to clear of all frost before returning to the cooling cycle If this does not occur the timer settings may need to be adjusted For changing the settings see the section below on TIMERS Th...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Отзывы: