The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor 
should use only industry-recognized procedures.
Heat pump systems require a specified airflow. Each ton of cooling requires between 350 and 450 cubic feet of air per minute (CFM), or 400 CFM 
nominally.
Duct design and construction should be carefully done. System performance can be lowered dramatically through bad planning or workmanship.
Air supply diffusers must be selected and located carefully. They must be sized and positioned to deliver air along the perimerter of the space. If 
they are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Air grilles must be properly sized 
to carry air back to the blower.If they are too small, they also cause noise.
The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures a comfortable living 
space.

Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size 
external static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat 
operation. 

Airflow Performance(Standard CFM)

1. Airflow based upon dry coil at 230V with no electric heat

no filter. For 24, 30,and 36 sizes, airflow at 208V is approximately the same as

230V because the mult-tap ECM motor is a constant torque motor. The torque doesn’t drop off at the speeds in which the motor operates.
2. Airflow is equivalent for front or bottom return configurations.
3. SCFM is nearly the same with cooling performance airflow, the gap is in the 1 to 2%.

Section 6. Performance and Electrical Data (WALL-MOUNT AIR HANDLERS ARE SUITABLE

FOR MOBILE HOME APPLICATIONS)

--- Shaded boxes represent airflow outside the required 300-450 cfm/ton.

* When 

JMM5A0A24M21SAA

 

is 

used with 1.5ton outdoor unit ,select SCFM between 450 and 675.

NOTES:

0

0.1

0.18

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Tap(5)

913

881

848

848

818

792

763

731

691

650

Tap(4)-Factory

825

787

756

753

717

682

650

617

580

540

Tap(3)

737

700

666

663

630

589

550

511

474

436

Tap(2)

675

632

598

596

555

521

480

440

399

366

Tap(1)

590

548

512

499

455

430

368

338

309

263

Tap(5)

1362

1325

1280

1266

1238

1197

1159

1119

1080

1040

Tap(4)

1282

1242

1195

1176

1151

1111

1071

1028

975

936

Tap(3)

1267

1225

1178

1143

1120

1078

1036

993

942

897

Tap(2)-Factory

1157

1111

1061

1052

1016

971

929

884

842

802

Tap(1)

1077

1028

978

965

932

886

850

804

768

732

Tap(5)

1362

1325

1280

1266

1238

1197

1159

1119

1080

1040

Tap(4)-Factory

1282

1242

1195

1176

1151

1111

1071

1028

975

936

Tap(3)

1267

1225

1178

1143

1120

1078

1036

993

942

897

Tap(2)

1157

1111

1061

1052

1016

971

929

884

842

802

Tap(1)

1077

1028

978

965

932

886

850

804

768

732

36

30

24

Model

BLOW ER

SPEEDS

EXTERNAL STATIC PRESSURE(in.w.c.)

JMM5A

11

Содержание OXBOX JMM5A0A24M21SAA

Страница 1: ... versatile units are applicable to air conditioning and heat pump applications Field installed electric resistance heaters are available All aluminum coil Blower and coil slide out easily for maintenance Factory sealed cabinet certified to achieve 2 or less air leakage rate at 1 0 inch water column Front or bottom return air Painted finish on galvanized steel Sturdy polycarbonate drain pans Air ha...

Страница 2: ... state electrical code on requirements for grounding Failure to follow this warning could result in property damage serious personal injury or death HAZARDOUS VAPORS Do not install an air handler with a non ducted return in the same closet alcove or utility room as a fossil fuel device Hazardous vapors can be distributed throughout the conditioned space and equipment damage can result Section 2 Sa...

Страница 3: ...ins adhesives cleaning compounds and cement creates a corrosive condition which may cause rapid deterioration of the cabinet and internal components CAUTION SAFETY HAZARD Sharp Edge Hazard Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or servicing Personal injury may result WARNING Make sure the blower motor support is tight 3 motor mount bolts then check ...

Страница 4: ...t the air handler above the wall mounting bracket and attach the unit to the installed bracket Reference Figure 3 1 4 Install the additional bottom plate for extra support for this type mounting see figure 3 1 Note The additional plate is shipped in the bottom of the shipping carton 3 2 1 WALL MOUNT Fig 3 2 FRAME MOUNT 3 2 2 FRAME MOUNT PROVIDED WALL MOUNT BRACKET WALLMOUNT BRACKET WOOD SCREWS SUP...

Страница 5: ...idential Winter and Summer Air Conditioning and Equipment Selection Latest editions are available from ACCA Air Conditioning Contractors of America 1513 16th Street N W Washington D C 20036 If duct system incorporates flexible air duct be sure pressure drop information straight length plus all turns shown in ACCA Manual D is accounted for in system Supply plenum is attached to the 3 4 duct flanges...

Страница 6: ...gize the fan on a demand for heating or cooling Install the thermostat on an inside wall away from drafts lights or other heat sources in a location that has sufficient air circulation from other rooms being controlled by the thermostat The thermostat should be mounted 4 to 5 feet above the floor Low voltage control wiring should be 18 Awg color coded For lengths longer than 100 ft 16 Awg wire sho...

Страница 7: ...pension if used is secure and there are no tools or loose debris in around or on top of the unit 2 Properly insulate suction lines and fittings 3 Properly secure and isolate all refrigerant lines 4 Verify that all electrical connections are tight 5 Check all duct outlets they must be open and unrestricted 6 Check drain lines and be sure all joints are tight 7 Be sure the return air filter is insta...

Страница 8: ...COMPONENT ARRANGEMENT FM NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE CAUTION ATTENTION JMM5A0A24M21SAA JMM5A0B36M31SAA Fig 4 1 8 ...

Страница 9: ...COMPONENT ARRANGEMENT FM NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE CAUTION ATTENTION Fig 4 2 JMM5A0B30M21SAA 9 ...

Страница 10: ...8 1200 0 06 0 08 0 08 1100 0 06 0 08 0 08 1000 0 06 0 08 0 08 900 0 04 0 06 0 06 800 0 04 0 06 0 06 700 0 04 0 06 0 06 900 0 04 0 06 0 06 800 0 04 0 06 0 06 700 0 04 0 06 600 0 04 0 06 0 06 0 06 HEATER RACKS HEATER MODEL NO OF RACKS BAYHTRJ505BRKA 1 BAYHTRJ508BRKA 2 BAYHTRJ510BRKA 3 Accessory Heater Usage SIZES USED WITH kW INTERNAL CIRCUIT PROTECTION 1 5 Circuit Breaker 2 7 5 Circuit Breaker 3 24...

Страница 11: ...on dry coil at 230V with no electric heat no filter For 24 30 and 36 sizes airflow at 208V is approximately the same as 230V because the mult tap ECM motor is a constant torque motor The torque doesn t drop off at the speeds in which the motor operates 2 Airflow is equivalent for front or bottom return configurations 3 SCFM is nearly the same with cooling performance airflow the gap is in the 1 to...

Страница 12: ...ction 3 4 female pipe thread NPT Primary drain conncetion 3 4 female pipe thread NPT Front return shown Units may also be installed as bottom return See the applications section for more detail NOTE Hand tighten only Section 7 Dimensional Data DIMENSIONAL DATA Model Dimensions inch mm H W D UNIT WEIGHT SHIPPING WEIGHT LBS kg JMM5A0A24M21SAA W1 D1 JMM5A0B30M21SAA JMM5A0B36M31SAA 97 120 44 54 4 97 1...

Страница 13: ...ION DATA Fig 2 BACK DIMENSIONS A B C JMM5A0A24M21SAA 24 9 10 150 10 1 8 61 119 1 20 717 JMM5A0B30M21SAA 24 9 10 150 10 1 8 61 132 795 JMM5A0B36M31SAA 24 9 10 150 10 1 8 61 132 795 Dimension inch mm Model number 13 ...

Страница 14: ......

Страница 15: ......

Страница 16: ...nformation contact your local dealer distributor Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change the design and specification without notice 800 Beaty Street www oxboxhvac com 2019TwentyThreeC LLC ...

Отзывы: