Installation Mechanical
30
RTHD-SVX01K-EN
Water Piping
General
Note:
Field piping must be arranged and supported to
avoid stress on the equipment. It is strongly
recommended that the piping contractor provide at
least 3 feet (914 mm) of clearance between the pre-
installation piping and the planned location of the
unit. This will allow for proper fit-up upon arrival of
the unit at the installation site. All necessary piping
adjustments can be made at that time. Refer to the
current engineering bulletin for further details on
installation.
•
Where specified, supply and install valves in the water
piping upstream and downstream of the evaporator
and condenser water boxes, to isolate the shells for
maintenance and to balance/trim the system.
•
Supply and install condenser water control valve(s) per
Engineering Bulletin RLC-PRB017*-EN.
•
Supply or locate ship-with flow switches. Install flow
switches or equivalent devices in both the chilled water
and condenser water piping. Wire the flow switches
into the control system as indicated on the electrical
schematics and field wiring diagrams, to ensure that
the unit can only operate when water flow is
established.
•
Supply and install taps for thermometers a
nd pressure
gauges in water piping, adjacent to the inlet and outlet
connections of both the evaporator and the condenser.
•
Supply and install drain valves on each water box.
•
Supply and install vent cocks on each water box.
•
Where specified, supply and install strainers ahead of
all pumps and automatic modulating valves.
•
Supply and install refrigerant pressure relief piping
from the pressure relief to the atmosphere.
•
If necessary, supply enough refrigerant and dry
nitrogen (75 psig) for pressure testing.
•
Where specified, supply and insulate the evaporator
and any other portion of the unit, as required, to
prevent sweating under normal operating conditions.
Figure 13.
Typical water piping setup
Evap
Water
Flow
Shutoff
Valves
Isolation
Valves
Manifold
Flow
Switch
Thermometers
Pressure
Differential
Gauge
Relief
Valve
Cond Water
Ref Valve (Opt)
Cond
Water
Flow
Shutoff
Valves
Isolation
Valves
Manifold
Flow
Switch
Thermometers
Pressure
Differential
Gauge
Relief
Valve
Содержание Optimus RTHD
Страница 27: ...Installation Mechanical RTHD SVX01K EN 27...
Страница 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Страница 29: ...Installation Mechanical RTHD SVX01K EN 29...
Страница 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Страница 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Страница 95: ...Notes RTAF SVX001K EN 95...