background image

8

TTA-R410A

Refrigerant Piping Guidelines

Refrigerant Piping Procedures
(Outdoor units)

Each TTA unit ships with dry nitrogen 
holding charge. Due to this minimal 
amount, we recommend that it be 
removed and the entire system 
evacuated (at the proper time) to avoid 
possible contamination. 
1. Remove the compressor service

access panel.

2. Locate the liquid and suction line

service valves. Check that the
piping connection stubs on the
valves (Figure 1) line up properly
with the holes in the unit cabinet.

3. Front-seat (close) both of the

service valves must be closed
before the system is opened.

suction line service valves before
puncturing the seal caps on the
connection stubs. If the seal caps are
punctured with the valves open, the
refrigerant contained in each circuit
will be lost.

unless they have been punctured. If
caps are intact, application of heat
may generate excessive pressure in
the connection stub, causing personal
injury or death due to rupturing of
components and damage to the
service valve.

4. Heat and remove the seal caps.

caps from refrigerant connections
unit prepared to braze refrigerant
lines to the connections. Excessive
exposure  to atmosphere may allow
moisture or dirt to contaminate the
system, damaging valve seats and
causing ice formation in system
components.

5.

*\[Ä[HUKIYHaL[\IPUNZ[HY[PUN

at the outdoor unit and work toward
the indoor unit.

Note:

 Use long radius ells for all 90

degree bends.

Caution:

 Fully close the liquid and

Warning:

 Do not heat the seal caps

Caution:

 Do not remove the seal

!

!

!

All brazing should be done using 2

[VWZPNKY`UP[YVNLUW\YNLÅV^PUN

through the pipe being brazed 9
(Figure 2).

between the nitrogen source and
the gauge manifold (Figure 2).
Unregulated pressures can damage
system components.

protect painted surfaces from
excessive heat. Heat can damage
system components and the unit

ÄUPZO

6. Shut off nitrogen supply.
7. Shut off  the manifold valve for

the line that is connected to the
suction line service valve.
Disconnect the line from the gauge
port on the value.

Refrigerant Piping Procedure
(Indoor Unit)

Once liquid and suction lines are
complete to the refrigerant
connections on the indoor unit, heat
and remove the seal caps on the
indoor unit connection stubs to
release the dry nitrogen charge.

Caution:

 Install a regulating valve

Caution:

 Wet-wrap all valves and

!

!

1. Remove both seal caps from the

indoor unit connection stubs.

2. Turn nitrogen supply on. Nitrogen

enters through the liquid line
gauge port.

3. Braze the liquid line connections.
4. Open the gauge port on the suction

line and then braze suction line to
the connection stub. Nitrogen will
bleed out the open gauge port on
the suction line.

5. Shut off nitrogen supply.

Leak Check

After the brazing operation of
refrigerant lines to both the outdoor

HUKPUKVVY\UP[PZJVTWSL[LK[OLÄLSK

brazed connections must be checked
for leaks. Pressurize the system
through the service valve with dry
nitrogen to 400 psi. Use soap bubbles
or other leak-checking methods to

LUZ\YL[OH[HSSÄLSKQVPU[ZHYLSLHRMYLL

If not, release pressure, repair and
repeat leak test.

Caution:

 Do not remove seal caps 

until prepared to braze refrigerant lines 
to the connections. Extended exposure 
to atmosphere may allow moisture or 
dirt to contaminate the system, 
damaging system components.

!

Figure 2

Manifold

Gauge

Pressure

Regulating

Valve

Dry

Supply

Nitrogen

Liquid Line

Gauge Port

Liquid Line Service Valve
Note: Detail Service valve  see Fig.1

Suction Line Service Valve
Note: Detail Service valve  see Fig.1

Suction Line Gauge Port

Содержание ODYSSEY TTA 051 JDF

Страница 1: ...altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are...

Страница 2: ...Design Sequence Fourth Design Sequence New Design 1 Fan New comp change Unit Hi Ambient Temp Fifth Design Sequence Q R S J F No Option Copper Fin Blue Fin Single Circuit Manifolded Compressor for TTA1...

Страница 3: ...recaution General Information Installation Refrigerant Piping Guidelines Refrigerant Charging and Evacuation General Data Refrigerant Circuit Electrical Wiring Dimensional Data Operation Maintenance T...

Страница 4: ...g leakage of water etc Be sure to cut off the main power in case of setting up the indoor electronic control P C board or wiring works It could cause an electri shock Any presence of foreign substance...

Страница 5: ...Cautions appear at appropriate places in this manual Your personal safety and the proper operation of this machine require that you follow them carefully The Company assumes no liability for installa...

Страница 6: ...to insure proper unit operation A Do not install the unit under a low overhang Condenser discharge clearance is not less than 2 5 mm Important Do not obstruct condenser discharge air This can result i...

Страница 7: ...TTA 150 200 Dual Circuit TTA B51 B65 Single Circuit TTA 075 100 Single Circuit Suction line Liquid line 1 1 8 inch sealed type L refrigerant tubing 1 2 inch sealed type L refrigerant tubing D Recommen...

Страница 8: ...d the gauge manifold Figure 2 Unregulated pressures can damage system components protect painted surfaces from excessive heat Heat can damage system components and the unit UPZO 6 Shut off nitrogen su...

Страница 9: ...8 60 6 30 13 89 6 30 13 89 6 10 13 45 5 40 11 90 6 75 14 88 6 75 14 88 13 50 29 76 12 60 27 78 12 20 26 90 10 30 23 81 TTA 100 JDF Tubing Sizes Additional Additional See Suction Liquid Tubing Length...

Страница 10: ...only as required to obtain correct head and suction pressure Check suction line superheat and condenser sub cooling to ensure the unit is operating properly 4 Disconnect all power to the unit 5 Remov...

Страница 11: ...mm 743 x804 x 781 743 x804 x 781 WEIGHT Crated Shipping kg 86 91 Uncrated Net kg 80 85 1 MCA Minimum Circuit Ampacity 2 CFM is rated with standard air dry coil PSC Holding Charge Hermetic Scroll Galv...

Страница 12: ...Inner groove Inner groove Inner groove Rows 2 2 2 2 Fin Type Uncoated Corrugate Fins per inch 16 16 16 16 Refrigerant Flow Control FAN Fan Type Propeller Propeller Propeller Propeller No used 2 2 2 2...

Страница 13: ...nner groove Inner groove Inner groove Inner groove Rows 2 2 2 2 Fin Type Uncoated Corrugate Fins per inch 16 16 16 16 Refrigerant Flow Control FAN Fan Type Propeller Propeller Propeller Propeller No u...

Страница 14: ...14 TTA R410A Refrigerant Circuit TTA B51 B65 JDF Single Circuit TTA 075 150 JDF Single Circuit TTA 150 240 JD00 Dual Circuit TTA 150 240 JD0G Manifolded Comp Figure 4A Figure 4B...

Страница 15: ...PVU VM KPZJVUULJ Z P JOLZ T Z JVTWS P O HSS HWWSPJHISL JVKLZ KPZJVUULJ Z P JO HUK SVJR PU VWLU WVZP PVU V WYL LU HJJPKLU HS WV LY HWWSPJH PVU HPS YL V KV ZV TH YLZ S PU WLYZVUHS PUQ Y VY KLH O K L V...

Страница 16: ...LINE ARE CIRCUIT IDENTIFICATION COMPRESSOR HTR 4 6 5 T1 T2 T3 TTA B51 B65 JDF SINGLE CIRCUIT WIRING DIAGRAM ELEMENTARY DIAGRAM 4 9 13 12 10 11 8 7 5 6 N 7A TERMINAL GROUND HTR 3 2 1 POWER SUPPLY 380V...

Страница 17: ...ON FIELD WIRING OPTION FACTORY WIRING DEVICES BY MFR 1TB TERMINAL BLOCK CONTROL CIRCUIT RELAY TIME DELAY 3 MIN THERMOSTAT RELAY CONTROL LOCKOUT CONTROL LOW PRESS CONTACTOR COMPRESSOR HEATER CRANKCASE...

Страница 18: ...MINAL BLOCK HIGH VOLTAGE 2HTR 8 9 10 T3 1TH 1PB 2PB 3M 1HTR 2HTR 2TR 1TR 1R 2R 1M 2M T1 T2 LEGEND 1LP 2LP FU 1HP 2HP FUSE 5 AMP 20 19 GRAPHIC ELECTRICAL STANDARDS RELAY CONTACTS CIRCUIT IDENTIFICATION...

Страница 19: ...B 2PB 4M CONTACTOR COMPRESSOR RELAY CONTROL LOCKOUT RELAY TIME DELAY 4 5 MIN RELAY TIME DELAY 3 MIN HEATER CRANKCASE SWITCH PUSH BOTTON FUSE 5 AMP CONTROL LOW PRESS CONTROL HIGH PRESS A1 A2 AUXILIARY...

Страница 20: ...INE CONNECTION FEMALE BLAZED DIA 7 8 C LIQUID LINE CONNECTION FEMELE BLAZED DIA 1 2 TTAB65 TTAB51 A ELECTRIC WIRING OUTLET B GAS LINE CONNECTION FEMALE BLAZED DIA 7 8 C LIQUID LINE CONNECTION FEMELE B...

Страница 21: ...TTA R410A 21 Dimensional Data TTA 075 100 120 JDF SINGLE CIRCUIT HORIZONTAL AND VERTICAL DISCHARGE...

Страница 22: ...22 TTA R410A Dimensional Data TTA 150 JDF SINGLE CIRCUIT HORIZONTAL AND VERTICAL DISCHARGE...

Страница 23: ...TTA R410A 23 Dimensional Data TTA 150 180 200 240 JD00 DUAL CIRCUIT...

Страница 24: ...24 TTA R410A Dimensional Data TTA 150 180 200 240 JD0G MANIFOLDED COMPRESSOR...

Страница 25: ...ge pressure exceeds the High Pressure Cut Out s setting Internal Overload Protector IOL This device is a current thermal actuated warp switch imbedded in the compressor motor windings If will shut off...

Страница 26: ...nnually Cooling Season The following maintenance procedures must be performed at the beginning of HDFK FRROLQJ VHDVRQ WR LQVXUH HI FLHQW unit operation Perform all of the monthly maintenance inspectio...

Страница 27: ...ning the unit by avoiding serious and costly breakdown S S S S S S Table 6 Troubleshooting Chart Refrigerant Circuit S S P S P h g i H o o T e r u s s e r P d a e H P S S S P S P P P S P P S P P P P P...

Страница 28: ...nd specifications without notice We are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient...

Отзывы: