TTA-R410A

7

Refrigerant Piping Guidelines

Refrigerant Piping

To ensure the return of oil in the
refrigerant lines, it is necessary to
follow these recommendations:

1. Select the tube lengths with care

DQGWU\WRDYRLGKDYLQJD¿QDOIHZ

meters of tube to use up. Refer to
table 2 for tube sizes.

2. Pitch all horizontal suction lines

down towards the unit to assist
gravity oil drainage back to the
compressor.

3. Avoid creating large oil traps in

horizontal suction lines as this will
reduce oil circulating in the system
and may eventually lead to failure
of the compressor.

4. A small oil trap at the end of a

horizontal suction line before a long
vertical riser (of more that 2.5
metres) has the advantage of
assisting the high velocity gas to
carry the oil up the vertical pipe.

5. Liquid lines require no special

installation techniques as the liquid
refrigerant R-22 and the oil mix.
The densities of the refrigerant and
oil are near enough the same so
any movement of liquid refrigerant
will carry oil with it.

6. The installation of a liquid line

sight is recommended. It is very
useful during the maintenance
procedures.

Refrigerant Piping Guidelines

A. Maximum recommended line

lengths: (per circuit)
Maximum linear length

200 Ft.

(W/o accumulator)

Maximum suction line lift

60 Ft.

Maximum liquid line lift

60 Ft.

B. Maximum allowable pressure

drops (R410A):
Suction line

14 psi.

Liquid line

65 psi.

(without subcooler)
Route refrigerant piping for
minimum linear length,
minimum number of bends and

¿WWLQJVQR

reducers) and minimum

amount of line exposed to outdoor
ambients.

C. Recommended line sizes: 

TTA 150-200 (Dual Circuit) 

TTA B51-B65 (Single Circuit) 
TTA 075-100 (Single Circuit) 

Suction line

Liquid line

1 1/8 inch sealed type L

refrigerant tubing.

1/2 inch sealed type L

refrigerant tubing.

D. Recommended line sizes: 

TTA 120 (Single Circuit) 
TTA 240 (Dual Circuit) 

Suction line

Liquid line

1 3/8 inch sealed type L

refrigerant tubing.

1/2 inch sealed type L

refrigerant tubing.

E. Recommended line sizes: 

TTA 150 (Single Circuit)
TTA 150-240 (Manifolded Compressor) 

Suction line

Liquid line

1 5/8 inch sealed type L

refrigerant tubing.

5/8 inch sealed type L

refrigerant tubing.

Figure 1

Note:

 Insulate all refrigerant piping

and connections.

TUBE CONNECTON

CAP 

CHARGING 

PORT

CAP VALVE PORT

BODY (FORGED)

TUBE CONNECTON

O - RING

O - RING 

SEAL

PLUNGER

VALVE CORE

TTA B65 JDF          1/2         7/8       1/2       7/8        1/2       7/8       1/2        1 1/8

TTA 100 JDF           1/2        1 1/8     1/2      1 1/8      1/2      1 1/8     1/2        1 1/8
TTA 120 JDF           1/2        1 3/8     1/2      1 3/8      1/2      1 3/8     1/2        1 3/8

TTA 150 JD00         1/2        1 1/8     1/2      1 1/8      1/2      1 1/8     1/2        1 1/8
TTA 180 JD00         1/2        1 1/8     1/2      1 1/8      1/2      1 1/8     1/2        1 1/8
TTA 200 JD00         1/2        1 1/8     1/2      1 1/8      1/2      1 1/8     1/2        1 1/8
TTA 240 JD00         1/2        1 3/8     1/2      1 3/8      1/2      1 3/8     1/2        1 3/8
TTA 150 JD00         5/8        1 5/8     5/8      1 5/8      5/8      1 5/8     5/8        1 5/8

TTA 150 JDF           5/8        1 5/8     5/8      1 5/8      5/8      1 5/8     5/8        1 5/8

TTA 180 JD0G        5/8        1 5/8     5/8      1 5/8      5/8      1 5/8     5/8        1 5/8
TTA 200 JD0G        5/8        1 5/8     5/8      1 5/8      5/8      1 5/8     5/8        1 5/8

Table 2 - Recommended Interconnecting Lines

Notes:

1. Two line sets are required for dual circuits units.
2. For line lengths over 80 linear feet and 15 feet liquid line riser,

consult your local Trane representative.

Length of Interconnecting Line (feet)

0-20 

21-40 

41-60 

61-80

Liq. 

Suct. 

Liq. 

Suct. 

Liq. 

Suct. 

Liq. 

Suct.

TTA B51 JDF          1/2         7/8       1/2       7/8        1/2       7/8       1/2         7/8

TTA 075 JDF           1/2        1 1/8     1/2      1 1/8      1/2      1 1/8     1/2        1 1/8

Model

TTA 240 JD0G        5/8        1 5/8     5/8      1 5/8      5/8      1 5/8     5/8        1 5/8

Содержание ODYSSEY TTA 051 JDF

Страница 1: ...altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are...

Страница 2: ...Design Sequence Fourth Design Sequence New Design 1 Fan New comp change Unit Hi Ambient Temp Fifth Design Sequence Q R S J F No Option Copper Fin Blue Fin Single Circuit Manifolded Compressor for TTA1...

Страница 3: ...recaution General Information Installation Refrigerant Piping Guidelines Refrigerant Charging and Evacuation General Data Refrigerant Circuit Electrical Wiring Dimensional Data Operation Maintenance T...

Страница 4: ...g leakage of water etc Be sure to cut off the main power in case of setting up the indoor electronic control P C board or wiring works It could cause an electri shock Any presence of foreign substance...

Страница 5: ...Cautions appear at appropriate places in this manual Your personal safety and the proper operation of this machine require that you follow them carefully The Company assumes no liability for installa...

Страница 6: ...to insure proper unit operation A Do not install the unit under a low overhang Condenser discharge clearance is not less than 2 5 mm Important Do not obstruct condenser discharge air This can result i...

Страница 7: ...TTA 150 200 Dual Circuit TTA B51 B65 Single Circuit TTA 075 100 Single Circuit Suction line Liquid line 1 1 8 inch sealed type L refrigerant tubing 1 2 inch sealed type L refrigerant tubing D Recommen...

Страница 8: ...d the gauge manifold Figure 2 Unregulated pressures can damage system components protect painted surfaces from excessive heat Heat can damage system components and the unit UPZO 6 Shut off nitrogen su...

Страница 9: ...8 60 6 30 13 89 6 30 13 89 6 10 13 45 5 40 11 90 6 75 14 88 6 75 14 88 13 50 29 76 12 60 27 78 12 20 26 90 10 30 23 81 TTA 100 JDF Tubing Sizes Additional Additional See Suction Liquid Tubing Length...

Страница 10: ...only as required to obtain correct head and suction pressure Check suction line superheat and condenser sub cooling to ensure the unit is operating properly 4 Disconnect all power to the unit 5 Remov...

Страница 11: ...mm 743 x804 x 781 743 x804 x 781 WEIGHT Crated Shipping kg 86 91 Uncrated Net kg 80 85 1 MCA Minimum Circuit Ampacity 2 CFM is rated with standard air dry coil PSC Holding Charge Hermetic Scroll Galv...

Страница 12: ...Inner groove Inner groove Inner groove Rows 2 2 2 2 Fin Type Uncoated Corrugate Fins per inch 16 16 16 16 Refrigerant Flow Control FAN Fan Type Propeller Propeller Propeller Propeller No used 2 2 2 2...

Страница 13: ...nner groove Inner groove Inner groove Inner groove Rows 2 2 2 2 Fin Type Uncoated Corrugate Fins per inch 16 16 16 16 Refrigerant Flow Control FAN Fan Type Propeller Propeller Propeller Propeller No u...

Страница 14: ...14 TTA R410A Refrigerant Circuit TTA B51 B65 JDF Single Circuit TTA 075 150 JDF Single Circuit TTA 150 240 JD00 Dual Circuit TTA 150 240 JD0G Manifolded Comp Figure 4A Figure 4B...

Страница 15: ...PVU VM KPZJVUULJ Z P JOLZ T Z JVTWS P O HSS HWWSPJHISL JVKLZ KPZJVUULJ Z P JO HUK SVJR PU VWLU WVZP PVU V WYL LU HJJPKLU HS WV LY HWWSPJH PVU HPS YL V KV ZV TH YLZ S PU WLYZVUHS PUQ Y VY KLH O K L V...

Страница 16: ...LINE ARE CIRCUIT IDENTIFICATION COMPRESSOR HTR 4 6 5 T1 T2 T3 TTA B51 B65 JDF SINGLE CIRCUIT WIRING DIAGRAM ELEMENTARY DIAGRAM 4 9 13 12 10 11 8 7 5 6 N 7A TERMINAL GROUND HTR 3 2 1 POWER SUPPLY 380V...

Страница 17: ...ON FIELD WIRING OPTION FACTORY WIRING DEVICES BY MFR 1TB TERMINAL BLOCK CONTROL CIRCUIT RELAY TIME DELAY 3 MIN THERMOSTAT RELAY CONTROL LOCKOUT CONTROL LOW PRESS CONTACTOR COMPRESSOR HEATER CRANKCASE...

Страница 18: ...MINAL BLOCK HIGH VOLTAGE 2HTR 8 9 10 T3 1TH 1PB 2PB 3M 1HTR 2HTR 2TR 1TR 1R 2R 1M 2M T1 T2 LEGEND 1LP 2LP FU 1HP 2HP FUSE 5 AMP 20 19 GRAPHIC ELECTRICAL STANDARDS RELAY CONTACTS CIRCUIT IDENTIFICATION...

Страница 19: ...B 2PB 4M CONTACTOR COMPRESSOR RELAY CONTROL LOCKOUT RELAY TIME DELAY 4 5 MIN RELAY TIME DELAY 3 MIN HEATER CRANKCASE SWITCH PUSH BOTTON FUSE 5 AMP CONTROL LOW PRESS CONTROL HIGH PRESS A1 A2 AUXILIARY...

Страница 20: ...INE CONNECTION FEMALE BLAZED DIA 7 8 C LIQUID LINE CONNECTION FEMELE BLAZED DIA 1 2 TTAB65 TTAB51 A ELECTRIC WIRING OUTLET B GAS LINE CONNECTION FEMALE BLAZED DIA 7 8 C LIQUID LINE CONNECTION FEMELE B...

Страница 21: ...TTA R410A 21 Dimensional Data TTA 075 100 120 JDF SINGLE CIRCUIT HORIZONTAL AND VERTICAL DISCHARGE...

Страница 22: ...22 TTA R410A Dimensional Data TTA 150 JDF SINGLE CIRCUIT HORIZONTAL AND VERTICAL DISCHARGE...

Страница 23: ...TTA R410A 23 Dimensional Data TTA 150 180 200 240 JD00 DUAL CIRCUIT...

Страница 24: ...24 TTA R410A Dimensional Data TTA 150 180 200 240 JD0G MANIFOLDED COMPRESSOR...

Страница 25: ...ge pressure exceeds the High Pressure Cut Out s setting Internal Overload Protector IOL This device is a current thermal actuated warp switch imbedded in the compressor motor windings If will shut off...

Страница 26: ...nnually Cooling Season The following maintenance procedures must be performed at the beginning of HDFK FRROLQJ VHDVRQ WR LQVXUH HI FLHQW unit operation Perform all of the monthly maintenance inspectio...

Страница 27: ...ning the unit by avoiding serious and costly breakdown S S S S S S Table 6 Troubleshooting Chart Refrigerant Circuit S S P S P h g i H o o T e r u s s e r P d a e H P S S S P S P P P S P P S P P P P P...