TTA-R410A

25

Operation

Sequence of Operation

General

Operation of the system cooling
cycles is controlled by the position of
the system switch on the room
thermostat.

Evaporator Fan (Indoor Supply Air)

The evaporator fan is controlled by
an ON/AUTO switch on the room
thermostat. With the switch positioned
at AUTO and the system operating in
the cooling mode, fan operation
coincides with the cooling run cycles.
When the fan switch is positioned at
ON, fan operation is continuous.

Cooling Mode

With the disconnect switch in the
“ON” position, current is supplied
to the compressor crankcase heater
(s) and control transformer. The
crankcase heater (s) supplies heat to
the compressor (s) during the “OFF”
cycle. With the room thermostat
system switch positioned at COOL
and the fan switch at AUTO, the
compressor contactor energizes on a
call for cooling. When the contacts of
the compressor contactor energizes
on a call for cooling. When the
contacts of the compressor contactor
close, operation of the compressor
and condenser fan begins.
The evaporator fan contactor also
energizes on a call for cooling and
initiates evaporator fan operation.

On dual circuit units, when second
stage cooling is required, Y2 from the
indoor thermostat will energize 2nd
compressor.

Note:

 With the thermostat fan switch

in the ON position, the evaporator
fan will operate continuously,
regardless of compressor or
condenser fan operation.

Safety Controls

Note: All of these controls may not be
installed on your unit, check electrical
schematic.

Low Pressure Cut-Out (LPCO)

This control’s sensor is located in the
suction (gas line, near the compressor).
This control will stop the compressor
and the outdoor fans in suction
pressure drops below the Low
Pressure Cut-Out setting.

High Pressure Cut-Out (HPCO)

This control’s sensor is located in the
liquid line. This device will shut off the
compressor and the outdoor fan (s) if
the discharge pressure exceeds the
High Pressure Cut-Out’s setting.

Internal Overload Protector (IOL)

This device is a current/thermal
actuated warp switch, imbedded
in the compressor motor windings.
If will shut off the compressor if
the temperature or current of the
compressor motor windings exceeds
its design trip temperature.

Note:

 The IOL will put the

compressor back in operation once
the compressor motor heat has
dropped below the trip setting;
however, a check of the refrigerant
and electrical systems should be
made to determine the cause and
be corrected.

Installation Checklist

Complete this checklist once the
unit is installed to verify that all
recommended procedures have
been accomplished before starting
the system. Do not operate the
system until all items covered by this
checklist are complete.

• Inspect unit location for proper

required service clearances.

• Inspect unit location for proper free

air clearances.

• Inspect unit location for secure.

Level mounting position.

Refrigerant Piping

• Performed initial leak test?
• Connected properly sized and

constructed liquid and suction lines
to the connection stubs at both the
indoor and outdoor units?

• Insulated the entire suction line?
• Insulated portions of liquid line

exposed to extremes in
temperature?

• Charge each circuit with proper

amount of R-22/R407C?

Electrical Wiring

• Provided unit power wiring (with

disconnect) to proper terminals in
the unit control Section?

• Installed system indoor thermostat?
• Installed system low voltage

interconnecting wiring to proper
terminals of outdoor unit, indoor
unit and system thermostat?

Unit Start-Up

Once the unit is properly installed and
pre-start procedures are complete,
start the unit by turning the System
Switch on the indoor thermostat to
either COOL or AUTO. The system
should operate normally.

the indoor air handler is closed before
operating the system. Operating the
outdoor unit without the indoor fan
energized, can cause unit trip-out on
high pressure control and/or liquid

ÀRRGEDFNWRWKHFRPSUHVVRUV

Evacuated each refrigerant circuit 
to 350 microns (-76 cm.Hg)?

Caution:

 Ensure the disconnect for

!

Содержание ODYSSEY TTA 051 JDF

Страница 1: ...altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are...

Страница 2: ...Design Sequence Fourth Design Sequence New Design 1 Fan New comp change Unit Hi Ambient Temp Fifth Design Sequence Q R S J F No Option Copper Fin Blue Fin Single Circuit Manifolded Compressor for TTA1...

Страница 3: ...recaution General Information Installation Refrigerant Piping Guidelines Refrigerant Charging and Evacuation General Data Refrigerant Circuit Electrical Wiring Dimensional Data Operation Maintenance T...

Страница 4: ...g leakage of water etc Be sure to cut off the main power in case of setting up the indoor electronic control P C board or wiring works It could cause an electri shock Any presence of foreign substance...

Страница 5: ...Cautions appear at appropriate places in this manual Your personal safety and the proper operation of this machine require that you follow them carefully The Company assumes no liability for installa...

Страница 6: ...to insure proper unit operation A Do not install the unit under a low overhang Condenser discharge clearance is not less than 2 5 mm Important Do not obstruct condenser discharge air This can result i...

Страница 7: ...TTA 150 200 Dual Circuit TTA B51 B65 Single Circuit TTA 075 100 Single Circuit Suction line Liquid line 1 1 8 inch sealed type L refrigerant tubing 1 2 inch sealed type L refrigerant tubing D Recommen...

Страница 8: ...d the gauge manifold Figure 2 Unregulated pressures can damage system components protect painted surfaces from excessive heat Heat can damage system components and the unit UPZO 6 Shut off nitrogen su...

Страница 9: ...8 60 6 30 13 89 6 30 13 89 6 10 13 45 5 40 11 90 6 75 14 88 6 75 14 88 13 50 29 76 12 60 27 78 12 20 26 90 10 30 23 81 TTA 100 JDF Tubing Sizes Additional Additional See Suction Liquid Tubing Length...

Страница 10: ...only as required to obtain correct head and suction pressure Check suction line superheat and condenser sub cooling to ensure the unit is operating properly 4 Disconnect all power to the unit 5 Remov...

Страница 11: ...mm 743 x804 x 781 743 x804 x 781 WEIGHT Crated Shipping kg 86 91 Uncrated Net kg 80 85 1 MCA Minimum Circuit Ampacity 2 CFM is rated with standard air dry coil PSC Holding Charge Hermetic Scroll Galv...

Страница 12: ...Inner groove Inner groove Inner groove Rows 2 2 2 2 Fin Type Uncoated Corrugate Fins per inch 16 16 16 16 Refrigerant Flow Control FAN Fan Type Propeller Propeller Propeller Propeller No used 2 2 2 2...

Страница 13: ...nner groove Inner groove Inner groove Inner groove Rows 2 2 2 2 Fin Type Uncoated Corrugate Fins per inch 16 16 16 16 Refrigerant Flow Control FAN Fan Type Propeller Propeller Propeller Propeller No u...

Страница 14: ...14 TTA R410A Refrigerant Circuit TTA B51 B65 JDF Single Circuit TTA 075 150 JDF Single Circuit TTA 150 240 JD00 Dual Circuit TTA 150 240 JD0G Manifolded Comp Figure 4A Figure 4B...

Страница 15: ...PVU VM KPZJVUULJ Z P JOLZ T Z JVTWS P O HSS HWWSPJHISL JVKLZ KPZJVUULJ Z P JO HUK SVJR PU VWLU WVZP PVU V WYL LU HJJPKLU HS WV LY HWWSPJH PVU HPS YL V KV ZV TH YLZ S PU WLYZVUHS PUQ Y VY KLH O K L V...

Страница 16: ...LINE ARE CIRCUIT IDENTIFICATION COMPRESSOR HTR 4 6 5 T1 T2 T3 TTA B51 B65 JDF SINGLE CIRCUIT WIRING DIAGRAM ELEMENTARY DIAGRAM 4 9 13 12 10 11 8 7 5 6 N 7A TERMINAL GROUND HTR 3 2 1 POWER SUPPLY 380V...

Страница 17: ...ON FIELD WIRING OPTION FACTORY WIRING DEVICES BY MFR 1TB TERMINAL BLOCK CONTROL CIRCUIT RELAY TIME DELAY 3 MIN THERMOSTAT RELAY CONTROL LOCKOUT CONTROL LOW PRESS CONTACTOR COMPRESSOR HEATER CRANKCASE...

Страница 18: ...MINAL BLOCK HIGH VOLTAGE 2HTR 8 9 10 T3 1TH 1PB 2PB 3M 1HTR 2HTR 2TR 1TR 1R 2R 1M 2M T1 T2 LEGEND 1LP 2LP FU 1HP 2HP FUSE 5 AMP 20 19 GRAPHIC ELECTRICAL STANDARDS RELAY CONTACTS CIRCUIT IDENTIFICATION...

Страница 19: ...B 2PB 4M CONTACTOR COMPRESSOR RELAY CONTROL LOCKOUT RELAY TIME DELAY 4 5 MIN RELAY TIME DELAY 3 MIN HEATER CRANKCASE SWITCH PUSH BOTTON FUSE 5 AMP CONTROL LOW PRESS CONTROL HIGH PRESS A1 A2 AUXILIARY...

Страница 20: ...INE CONNECTION FEMALE BLAZED DIA 7 8 C LIQUID LINE CONNECTION FEMELE BLAZED DIA 1 2 TTAB65 TTAB51 A ELECTRIC WIRING OUTLET B GAS LINE CONNECTION FEMALE BLAZED DIA 7 8 C LIQUID LINE CONNECTION FEMELE B...

Страница 21: ...TTA R410A 21 Dimensional Data TTA 075 100 120 JDF SINGLE CIRCUIT HORIZONTAL AND VERTICAL DISCHARGE...

Страница 22: ...22 TTA R410A Dimensional Data TTA 150 JDF SINGLE CIRCUIT HORIZONTAL AND VERTICAL DISCHARGE...

Страница 23: ...TTA R410A 23 Dimensional Data TTA 150 180 200 240 JD00 DUAL CIRCUIT...

Страница 24: ...24 TTA R410A Dimensional Data TTA 150 180 200 240 JD0G MANIFOLDED COMPRESSOR...

Страница 25: ...ge pressure exceeds the High Pressure Cut Out s setting Internal Overload Protector IOL This device is a current thermal actuated warp switch imbedded in the compressor motor windings If will shut off...

Страница 26: ...nnually Cooling Season The following maintenance procedures must be performed at the beginning of HDFK FRROLQJ VHDVRQ WR LQVXUH HI FLHQW unit operation Perform all of the monthly maintenance inspectio...

Страница 27: ...ning the unit by avoiding serious and costly breakdown S S S S S S Table 6 Troubleshooting Chart Refrigerant Circuit S S P S P h g i H o o T e r u s s e r P d a e H P S S S P S P P P S P P S P P P P P...

Страница 28: ...nd specifications without notice We are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient...

Отзывы: