Unit Installation
Installation Diagram
Over 20mm
Over 1,500mm
Air outlet
Air outlet
Air outlet
Ground
Over 1,500mm
Over 1,800mm
Figure 2.
Verify indoor unit installation site
Ensure no barriers in indoor unit air inlet and outlet for good ventilation.
1.
Ensure installation complying with the diagram.
2.
Select a low running noise and less vibration location which can support 4 times of indoor
3.
unit weight
Ensure horizontal installation location.
4.
Select a location, which is easy to discharge condensate water and connect to outdoor unit.
5.
Ensure enough space for repair and maintenance.
6.
The distance between indoor unit and
ground is 1,800mm at least.
Check hoist screw installation site if support 4 times of the unit weight. Strengthening it
7.
before installation if necessary (see installation paperboard for points to fi x).
Attention
There are pretty much oil smoke and powder in places such as the dining hall and kitchen.
Centrifugal fan, heat exchanger and water pump in places above are easily polluted and affect
heat exchange ability, water dropping and water pump function. In that case, please take
following measures:
Ensure the range hood has good function, avoiding oil smoke entering the air conditioning.
1.
Keep air conditioning away from the kitchen.
2.